Plan Review Details - Permit 18040874
Plan Review Stops For Permit 18040874
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 12:12 Rev Time 0.00
Received By shill Date 2018-05-22 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 18:12 Rev Time 0.00
Received By shill Date 2018-04-30 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-30 Cont ID  
Sent By jleahy Date 2018-04-30 Time 16:25 Rev Time 0.00
Received By jleahy Date 2018-04-30 Time 16:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 12:04 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 07:28 Rev Time 0.00
Received By tklarge Date 2018-05-09 Time 14:52 Sent To  
Notes
2018-05-09 14:52:51B21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-02 Cont ID  
Sent By thunt Date 2018-05-02 Time 16:46 Rev Time 0.00
Received By thunt Date 2018-04-19 Time 15:28 Sent To I
Notes
2018-04-30 18:12:44TO T.HUNT DESK (IN TL OFFICE)
  
2018-04-20 15:28:52B02

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-05-14 Cont ID  
Sent By ccole Date 2018-05-14 Time 15:16 Rev Time 0.00
Received By ccole Date 2018-05-14 Time 15:14 Sent To  
Notes
2018-05-14 15:17:23SEPARATE PERMIT REQUIRED FOR MECHANICAL
 CCOLE- 5/14/18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-25 Cont ID  
Sent By ccole Date 2018-04-25 Time 17:43 Rev Time 0.00
Received By ccole Date 2018-04-25 Time 17:36 Sent To  
Notes
2018-04-25 17:45:291ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040874
 4/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS IF APPLICABLE TO THE
 PROPOSED PROJECT- SECTIOON 107.2.1 WEST PALM BEACH
 AMENDMENTS TO THE FBC-17.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By tklarge Date 2018-05-23 Time 07:27 Rev Time 0.00
Received By tklarge Date 2018-05-22 Time 14:03 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By thunt Date 2018-05-02 Time 16:44 Rev Time 0.00
Received By thunt Date 2018-05-01 Time 17:53 Sent To  
Notes
2018-05-02 16:32:0405/02/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE OCCUPANCY TYPE.(A-3). FBC 107.3.5
  
 2) PROVIDE OCCUPANCY LOAD OF BUILDING. FBC 107.3.5
  
 3) YOU ARE REMOVING PLUMBING FIXTURE THAT MAY BE
 REQUIRED . PLEASE SHOW THAT BY REMOVING THESE FIXTURE'S
 YOU STILL COMPLY WITH MINIMUM FIXTURE REQUIRMENTS IN
 FBC P 403.1
  
 4) BOTH THE PLUMBING CODE AND ACCESSIBILITY CODE
 REQUIRE A MIN 2 DRINKING FOUNTAINS. 1 HIGH AND 1 LOW.
 PLEASE SHOW HOW YOU INTENT TO COMPLY. FBC P 410.3 AND
 FBC A 602.7
  
 5) SHOW REQUIRED CLEAR FLOOR SPACE ON SHT. 1.60 FOR THE
 ADA URINAL. FBC A 603.2.3
  
 6) THE DOOR FROM THE TOILET COMPARTMENT LOOKS TO SWING
 INTO THE CLEAR FLOOR SPACE OF THE ADA URINAL. PLEASE
 CLEARIFY. FBC A 603.2.3
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  
  