Plan Review Details - Permit 18040873
| Plan Review Stops For Permit 18040873 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-06-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-06-04 |
Time |
05:53 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-06-04 |
Time |
05:52 |
Sent To |
I |
|
| Notes |
| 2018-06-04 05:53:34 | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WPB | | | [email protected] | | | CELL: 561-657-1653 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-04-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-04-28 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-04-28 |
Time |
10:35 |
Sent To |
M |
|
| Notes |
| 2018-04-30 07:22:56 | ELECTRICAL PERMIT REQUIRED FOR 120V CIRCUITS TO NEW | | | FACP AND POWER SUPPLIES. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 5TH EDITION | | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 5TH | | | EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 5TH EDITION, PART | | | VIII ELECTRICAL | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | [email protected] | | | 561-657-1653 | | | | | 2018-04-28 09:26:51 | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-05-25 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-05-25 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-04-23 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-04-23 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-04-23 |
Time |
11:24 |
Sent To |
E |
|
| Notes |
| 2018-04-23 11:35:10 | PERMIT # 18040873 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) SHEET FA-2: INSUFFICIENT COVERAGE IN COMMUNITY ROOM | | | AND MEDIA ROOM. | | | | | | 2) SHEETS FA-3 TO FA-7: PLEASE CONFIRM THAT | | | NOTIFICATION DEVICE IS NOT REQUIRED IN THE LAUNDRY | | | ROOMS. | | | | | | 3) SHEETS FA-3 AND FA-4: ALSO, LABEL ROOM TO THE LEFT | | | OF UNIT 101. IS THIS A RESIDENTIAL UNIT? DOES IT | | | REQUIRE A NOTIFICATION DEVICE? | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2018-06-04 |
Time |
05:53 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2018-05-18 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2018-05-21 14:11:02 | RESUB ROUTED TO FIRE INBOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-05-02 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-04-19 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2018-04-20 15:03:43 | ROUTED TO FIRE INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-05-02 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-05-02 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-05-02 |
Time |
10:47 |
Sent To |
I |
|
| Notes |
|
|
|