Plan Review Details - Permit 18040873
Plan Review Stops For Permit 18040873
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By fgiaquin Date 2018-06-04 Time 05:53 Rev Time 0.00
Received By fgiaquin Date 2018-06-04 Time 05:52 Sent To I
Notes
2018-06-04 05:53:34FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-28 Cont ID  
Sent By fgiaquin Date 2018-04-28 Time 09:29 Rev Time 0.00
Received By fgiaquin Date 2018-04-28 Time 10:35 Sent To M
Notes
2018-04-30 07:22:56ELECTRICAL PERMIT REQUIRED FOR 120V CIRCUITS TO NEW
 FACP AND POWER SUPPLIES.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 5TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 5TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653
  
2018-04-28 09:26:51 
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By scaldero Date 2018-05-25 Time 10:32 Rev Time 0.00
Received By scaldero Date 2018-05-25 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 11:35 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:24 Sent To E
Notes
2018-04-23 11:35:10PERMIT # 18040873
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SHEET FA-2: INSUFFICIENT COVERAGE IN COMMUNITY ROOM
 AND MEDIA ROOM.
  
 2) SHEETS FA-3 TO FA-7: PLEASE CONFIRM THAT
 NOTIFICATION DEVICE IS NOT REQUIRED IN THE LAUNDRY
 ROOMS.
  
 3) SHEETS FA-3 AND FA-4: ALSO, LABEL ROOM TO THE LEFT
 OF UNIT 101. IS THIS A RESIDENTIAL UNIT? DOES IT
 REQUIRE A NOTIFICATION DEVICE?
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-04 Cont ID  
Sent By fgiaquin Date 2018-06-04 Time 05:53 Rev Time 0.00
Received By fgiaquin Date 2018-05-18 Time 14:10 Sent To  
Notes
2018-05-21 14:11:02RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-02 Cont ID  
Sent By hmoser Date 2018-05-02 Time 11:11 Rev Time 0.00
Received By hmoser Date 2018-04-19 Time 15:03 Sent To  
Notes
2018-04-20 15:03:43ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-05-02 Cont ID  
Sent By hmoser Date 2018-05-02 Time 11:11 Rev Time 0.00
Received By hmoser Date 2018-05-02 Time 10:47 Sent To I
Notes
***NONE***