Plan Review Details - Permit 18040840
Plan Review Stops For Permit 18040840
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-16 Cont ID  
Sent By cthroop Date 2018-05-16 Time 07:35 Rev Time 0.00
Received By cthroop Date 2018-05-16 Time 07:25 Sent To  
Notes
2018-05-16 07:36:03INCREASED VALUE TO $16,995. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 11:18 Rev Time 0.00
Received By cthroop Date 2018-04-24 Time 10:52 Sent To  
Notes
2018-04-24 11:19:22BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
  
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-20 Cont ID  
Sent By jleahy Date 2018-04-20 Time 16:33 Rev Time 0.00
Received By jleahy Date 2018-04-20 Time 16:33 Sent To B1
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-16 Cont ID  
Sent By cthroop Date 2018-05-16 Time 07:35 Rev Time 0.00
Received By cthroop Date 2018-05-08 Time 11:05 Sent To I
Notes
2018-05-09 11:06:14ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 11:19 Rev Time 0.00
Received By cthroop Date 2018-04-18 Time 10:57 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-05-21 Cont ID  
Sent By gjohnson Date 2018-05-21 Time 09:06 Rev Time 0.00
Received By gjohnson Date 2018-05-21 Time 09:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-15 Cont ID  
Sent By tklarge Date 2018-05-15 Time 04:51 Rev Time 0.00
Received By tklarge Date 2018-05-15 Time 03:07 Sent To B
Notes
2018-05-15 04:51:1205/15/2018 PLUMBING 2ND REVIEW**DENIED**
  
 1) THE 2017 5TH EDITION OF THE FBC PLUMBING 421.2 NOW
 REQUIRES ALL WHIRLPOOL TUBS TO BE UL1795 LISTED,
 PROVIDES DOCUMENTS TO SUPPORT THIS.2ND REQUEST.
  
 2) THE THERMOSTATIC MIXING VALVE SUBMITTALS YOU HAVE
 PROVIDED DOES NOT SHOW THE VALVE AS BEING NSF 61
 APPROVED. FBC-P 605.5. 2ND REQUEST.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-19 Cont ID  
Sent By cthroop Date 2018-04-24 Time 11:19 Rev Time 0.00
Received By thunt Date 2018-04-19 Time 18:32 Sent To E
Notes
2018-04-19 18:34:1404/19/2018 PLUMBING 1ST REVIEW**DENIED**
  
 1) JOB VALUE SEEMS TOO LOW. PROVIDE BONA FIDE SIGNED
 CONTRACT. COST MUST INCLUDE ALL MATERIAL, LABOR,
 OVERHEAD, AND PROFIT. WPB AMEND TO THE FBC 109.3
  
 2) PROVIDE UP TO DATE PRODUCT APPROVALS AS THIS PLAN
 REVIEW HAS ATTEMPTED TO CONTACT HOME INNOVATION LABS
 AND THE PHONE LINE IS ALWAYS BUSY. APPROVALS SUBMITTED
 ARE 4 YEARS OLD AND NOT DATED BY PERSON CERTIFYING
 APPROVALS. FBC 107.3.5
  
 3) PROVIDE MANUFACTURES INSTALLATION MANUAL FOR TUB.
 FBC-P 421.2
  
 4) THE 2017 5TH EDITION OF THE FBC PLUMBING 421.2 NOW
 REQUIRES ALL WHIRLPOOL TUBS TO BE UL1795 LISTED,
 PROVIDES DOCUMENTS TO SUPPORT THIS.
  
 5) THE THERMOSTATIC MIXING VALVE SUBMITTALS YOU HAVE
 PROVIDED DOES NOT SHOW THE VALVE AS BEING NSF 61
 APPROVED. FBC-P 605.5
  
 6) PROVIDE LOCATION OF EXISTING TUB DRAIN ON FLOOR
 PLAN. FBC 107.3.5
  
 7) REMOVE COMMENT THAT NO TILE OR DRYWALL WORK TO BE
 DONE FROM PLAN AS YOU HAVE SUBMITTED DUROCK PRODUCT
 APPROVAL SHOWING THAT WORK WILL BE DONE. FBC 107.3.5
  
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  