Plan Review Details - Permit 18040760
Plan Review Stops For Permit 18040760
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By shill Date 2018-05-25 Time 11:05 Rev Time 0.00
Received By shill Date 2018-05-25 Time 11:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By jwitmer Date 2018-05-21 Time 18:42 Rev Time 0.00
Received By shill Date 2018-05-21 Time 18:42 Sent To  
Notes
2018-05-21 18:46:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SHEET A2090-10A, BATH 2, BATH 3, BATH 4 ARE NOT
 LABELED CORRECTLY (SEE SHEET A6-25-10A, A7-90-10A),
 PLEASE CORRELATE, FBC 107.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-05-02 Cont ID  
Sent By jleahy Date 2018-05-02 Time 16:24 Rev Time 0.00
Received By jleahy Date 2018-05-02 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-25 Cont ID  
Sent By pleduc Date 2018-04-25 Time   Rev Time 0.00
Received By pleduc Date 2018-04-25 Time 16:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-25 Cont ID  
Sent By shill Date 2018-05-25 Time 11:06 Rev Time 0.00
Received By shill Date 2018-05-23 Time 10:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-22 Cont ID  
Sent By lmarchan Date 2018-05-22 Time 07:52 Rev Time 0.00
Received By lmarchan Date 2018-04-20 Time 16:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-09 Cont ID  
Sent By ccole Date 2018-05-09 Time 16:10 Rev Time 0.00
Received By ccole Date 2018-05-09 Time 15:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-05-22 Cont ID  
Sent By gjohnson Date 2018-05-22 Time 07:37 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 05:35 Sent To  
Notes
2018-05-22 07:37:44PROVISO:
 1. ALL PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS,
 AND FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR
 DRINKING OR COOKING PURPOSES SHALL COMPLY WITH NSF 372
 AND SHALL HAVE A WEIGHTED AVERAGE LEAD CONTENT OF
 0.25-PERCENT LEAD OR LESS. PER FBC PL 605.2.1
 2. PROVIDE MANUFACTURE SPECIFICATIONS THAT SHOW THAT
 THEY MEET THIS CODE REQUIREMENT PRIOR TO ROUGH
 INSPECTION.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By lmarchan Date 2018-05-25 Time 11:18 Rev Time 0.00
Received By lmarchan Date 2018-05-25 Time 11:18 Sent To  
Notes
2018-05-22 07:40:395/22/18 DIG SIG ON PLUMB SHT. IS GOOD/GPJ
2018-05-21 18:47:36ARCH SHEETS OK REVIEW CYCLE 1, S.HILL
  
  
2018-05-09 16:11:15MECH DIG/SIG OK
 CCOLE