Plan Review Details - Permit 18040760
| Plan Review Stops For Permit 18040760 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-25 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-25 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2018-05-21 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-21 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2018-05-21 18:46:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET A2090-10A, BATH 2, BATH 3, BATH 4 ARE NOT | | | LABELED CORRECTLY (SEE SHEET A6-25-10A, A7-90-10A), | | | PLEASE CORRELATE, FBC 107. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2018-05-02 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-05-02 |
Time |
16:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-05-02 |
Time |
16:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-04-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-04-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-04-25 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-25 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-23 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-05-22 |
Time |
07:52 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-20 |
Time |
16:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-05-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-05-09 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-05-09 |
Time |
15:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-05-22 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-05-22 |
Time |
05:35 |
Sent To |
|
|
| Notes |
| 2018-05-22 07:37:44 | PROVISO: | | | 1. ALL PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS, | | | AND FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR | | | DRINKING OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 | | | AND SHALL HAVE A WEIGHTED AVERAGE LEAD CONTENT OF | | | 0.25-PERCENT LEAD OR LESS. PER FBC PL 605.2.1 | | | 2. PROVIDE MANUFACTURE SPECIFICATIONS THAT SHOW THAT | | | THEY MEET THIS CODE REQUIREMENT PRIOR TO ROUGH | | | INSPECTION. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-05-25 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-05-25 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2018-05-22 07:40:39 | 5/22/18 DIG SIG ON PLUMB SHT. IS GOOD/GPJ | | 2018-05-21 18:47:36 | ARCH SHEETS OK REVIEW CYCLE 1, S.HILL | | | | | | | | 2018-05-09 16:11:15 | MECH DIG/SIG OK | | | CCOLE |
|
|
|