Plan Review Details - Permit 18040726
Plan Review Stops For Permit 18040726
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 12:57 Rev Time 0.00
Received By cthroop Date 2018-04-24 Time 11:34 Sent To Z
Notes
2018-04-24 13:01:04BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. LIABILITY AND WORKERS COMP. INSURANCE HAS EXPIRED.
 2. QUALITY OF PLANS NOT ACCEPTABLE FOR RECORDS
 MANAGEMENT.
 3. CONSTRUCTION DOCUMENTS TO BE SUBMITTED IN TWO OR
 MORE SETS.
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-23 Cont ID  
Sent By jleahy Date 2018-04-23 Time 11:37 Rev Time 0.00
Received By jleahy Date 2018-04-23 Time 09:56 Sent To B
Notes
2018-04-23 11:18:57 
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 ONLY ONE SET OF PLANS AND SPECS SUBMITTED, ALSO PLANS
 NEED TO BE 1/8" SCALE MINIMUM. TO SMALL TO READ
  
 NEED A SHEET SHOWING THE SIGNS THAT ARE TO BE APPLIED
 TO THIS SYSTEM AND WHERE THEY GO.690.7, 690.7, 690.10,
 690.13(B), 690.17(E) 690.31(G)(3), 690.31(G)(4),
 690.35(F), 690.56(B), 690.56(C)
  
 PLANS SHOW INVERTER FEEDING TWO SEPARATE PANELS, PLEASE
 EXPLAIN WHAT SMALL SECOND PANEL IS FOR AND IF IT IS
 EXISTING. HOW DOES THIS WORK? TWO LOADS?
  
 NEED TO EXPLAIN HOW BATTERY SYSTEM WILL WORK AND WHAT
 THE PURPOSE OF BATTERY SYSTEM. DOES IT HAVE AN OUTSIDE
 BRANCH CIRCUIT FEEDING IT TO CHARGE IT?
 IF USED FOR STORAGE SEE 690.71
  
 WHAT IS THE FUNCTION OF THE AUTO TRANSFROMER.
  
 PLEASE SUBMIT A SIGNED CONTRACTO FOR THE WORK INVOLVED.
 $3.50 PER WATT IS WHAT WE USE FOR SYSTEMS WITHOUT
 BATTERY BACKUP OR STORAGE?
  
 NEED TO SHOW ACCESS PATHWAYS ON ROOF ON PLAN FIRE CODE
 11.12.2.2.2..1
  
 MAIN TO BE GROUPED 690.13(E) CAN NOT TELL FROM DRAWING
 IF LOAD SIDE MAINS OF INVERTER ARE GROUPED.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By lmarchan Date 2018-04-30 Time 10:20 Rev Time 0.00
Received By lmarchan Date 2018-04-17 Time 13:00 Sent To  
Notes
2018-04-18 13:00:22ROUTED TO JLEAHY

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-30 Cont ID  
Sent By hmtribou Date 2018-04-30 Time 07:56 Rev Time 0.00
Received By hmtribou Date 2018-04-30 Time 07:56 Sent To I
Notes
***NONE***