Plan Review Details - Permit 18040720
Plan Review Stops For Permit 18040720
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-18 Cont ID  
Sent By skennedy Date 2018-06-18 Time 11:24 Rev Time 0.00
Received By skennedy Date 2018-06-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 11:43 Rev Time 0.00
Received By shill Date 2018-05-13 Time 11:25 Sent To  
Notes
2018-05-13 11:43:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EC C502.1, NO INFORMATION PROVIDED. AS THIS IS
 AN INCREASE IN CONDITIONED SPACE, THIS IS CONSIDERED AN
 ADDITION IN ADDITION TO A LEVEL 2 ALTERATION (FBC EB),
 PLEASE REVISE GENERAL NOTES A1.
  
 2. FBC B 1609, SPECIFY COMPONENT AND CLADDING DESIGN
 PRESSURES AND INCLUDE WIND DESIGN CRITERIA (170 MPH
 EXPOSURE D MINIMUM).
  
 3. ON THE SLIDING GLASS DOOR PRODUCT APPROVAL, INDICATE
 OPTIONS ELECTED TO SHOW COMPLIANCE WITH THE DESIGN
 PRESSURE REQUIREMENTS.
  
 4. REVISE PLAN TO INCLUDE TYPE OF FLOORING PROPOSED,
 FBC 107.
  
 IF A FLOORING UNDERLAYMENT IS PROPOSED (FOR TILE OR
 OTHER RESILIENT FLOORING), ADVISE AS TO UNDERLAYMENT
 PROPOSED. THREE TEST REPORTS ARE REQUIRED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 5. FBC 107, REVISE PLAN TO INCLUDE UNDER AIR
 CALCULATIONS:
 EXISTING SQUARE FOOT UNDER AIR
 PROPOSED NEW UNDER AIR
 NEW TOTAL
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-05 Cont ID  
Sent By ppetty Date 2018-06-05 Time 10:03 Rev Time 0.00
Received By ppetty Date 2018-06-05 Time 09:59 Sent To  
Notes
2018-06-05 10:03:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: OK, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 09:56 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 09:56 Sent To  
Notes
2018-05-05 09:55:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION. A NOTE WILL SUFFICE. NEC 210.12
 2. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 3. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 4. PER CODE: LIGHTING WITH OPEN OR PARTIALLY ENCLOSED
 LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT
 BE PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION.
 NEC 410.16
 5. PANEL SCHEDULE IS INCOMPLETE. PROVIDE PANEL SCHEDULE
 INDICATING ANY NEW OR ALTERED CIRCUITS, THE WIRE AND
 BREAKER SIZE FOR THESE CIRCUITS, AND AFCI OR GFCI
 PROTECTION WHERE APPLICABLE TO COMPLY WITH CODE. NEC
 210.8, 210.12, 215.5, 408.4; WPB FBC 107.3.5
 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-23 Cont ID  
Sent By scaldero Date 2018-04-23 Time 11:49 Rev Time 0.00
Received By scaldero Date 2018-04-23 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-18 Cont ID  
Sent By skennedy Date 2018-06-18 Time 11:24 Rev Time 0.00
Received By skennedy Date 2018-05-22 Time 13:36 Sent To  
Notes
2018-05-23 13:36:39B09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 11:45 Rev Time 0.00
Received By gjohnson Date 2018-04-17 Time 14:25 Sent To  
Notes
2018-04-18 14:25:34B07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-06-14 Cont ID  
Sent By skennedy Date 2018-06-14 Time 09:57 Rev Time 0.00
Received By skennedy Date 2018-06-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-13 Cont ID  
Sent By shill Date 2018-05-13 Time 11:43 Rev Time 0.00
Received By shill Date 2018-05-13 Time 11:43 Sent To  
Notes
2018-05-13 11:44:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AFTER THE PLANS ARE STAMPED, CHECK OUT ONE SET OF PLANS
 AND TAKE TO PALM BEACH COUNTY FOR IMPACT FEE
 ASSESSMENT.
  
 561-233-5025 FOR ADDITIONAL INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-05-14 Cont ID  
Sent By hmoser Date 2018-05-14 Time 10:27 Rev Time 0.00
Received By hmoser Date 2018-05-14 Time 09:54 Sent To  
Notes
2018-05-14 10:27:02CALLED DONNIE BRICKLEMYER G C
 NO AIR CONDITIONING WORK AT THIS TIME.
 IF A/C WORK IS REQUIRED A/C CONTRACTOR
 WILL APPLY FOR A SEPARATE PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-13 Cont ID  
Sent By gjohnson Date 2018-06-13 Time 11:58 Rev Time 0.00
Received By gjohnson Date 2018-06-13 Time 11:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 11:45 Rev Time 0.00
Received By gjohnson Date 2018-05-15 Time 09:16 Sent To  
Notes
***NONE***