| 2018-04-24 13:19:43 | 04/24/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THERE IS AN EXISTING RESTROOM, PERMIT 18010296, ON |
| | THIS PROPERTY. IS THIS THE RESTROOM THAT WAS FINISHED |
| | AND PLAN THAT WAS SUBMITTED, IS IT BEING CHANGED OR IS |
| | IT A NEW RESTROOM? PLEASE CLARIFY THIS. 2017 FBC ACC |
| | CODE 604.3 CLEARANCE. |
| | 2. IF IT IS A NEW RESTROOM SHOW THAT IT COMPLIES WITH |
| | FBC ACCEPTABILITY, PLEASE SHOW CLEAR FLOOR SPACE AND |
| | DIMENSION REFLECT THE LOCATION OF FIXTURES DETAIL OF |
| | HEIGHTS AND DIMENSION NOT SHOWN, PLEASE PROVIDE DETAIL |
| | DRAWINGS PER 2017 FBC ACCESSIBILITY CODE. |
| | 3. PROVIDE MINIMUM SANITARY FACILITIES ACCORDING TO |
| | 2017 FBC P TABLE 403.1. |
| | 4. VENTING OF PLUMBING RISER DIAGRAM REQUIRED WPB |
| | AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL |
| | PLUMBING |
| | 5. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON |
| | THE APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED |
| | CONTRACT. WPB AMENDMENTS TO THE FBC SEC. 109.3 BUILDING |
| | PERMIT VALUATIONS. |
| | 6. IS THIS FLOOR BEING CUT AND PIPES BEING MOVED, |
| | SUBMIT A SLAB REPAIR DETAIL FOR REVIEW. SHOW THE WIDTH |
| | OF THE REPAIR, THE MINIMUM THICKNESS OF THE CONCRETE TO |
| | BE REPLACED, AND THE PSI OF THE CONCRETE. SHOW THE SIZE |
| | AND LENGTH OF THE DOWELS, THE MINIMUM EMBEDMENT DEPTH |
| | INTO THE EXISTING SLAB, AND THE SPACING OF THE DOWELS |
| | ON CENTER. THE REPAIR SHALL ALSO INCLUDE TERMITE |
| | TREATMENT OF THE SOIL AND THE REQUIRED VAPOR BARRIER |
| | OVER THE SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL |
| | BE ONSITE FOR FINAL INSPECTION. |
| | 7. THIS LOCATION HAS BEEN CITED FOR WORK BEING DONE |
| | WITHOUT A PERMIT AND INSPECTION SO IT APPEARS THAT |
| | THERE IS THE OTHER TRADE THAT REQUIRES A PERMIT |
| | APPLICATION, ELECTRICAL, MECHANICAL AND DRYWALL |
| | FRAMING. FBC WPB A 105.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING INSPECTOR / |
| | PLUMBING PLAN REVIEW |
| | [email protected] |
| | 561-805-6720 |
| | |