2018-04-23 10:54:00PERMIT # 18040713
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF
 THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL
 FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS.
  
 2) PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE
 MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND
 RADIUS PERMITTED IN THE LISTING DATA.
  
 3) INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE
 USED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-01 Cont ID  
Sent By cpuell Date 2018-05-01 Time 12:47 Rev Time 0.00
Received By cpuell Date 2018-04-26 Time 11:31 Sent To  
Notes
2018-04-27 11:31:38RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-25 Cont ID  
Sent By hmoser Date 2018-04-25 Time 09:35 Rev Time 0.00
Received By hmoser Date 2018-04-17 Time 13:23 Sent To  
Notes
2018-04-18 13:23:30ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-04-25 Cont ID  
Sent By hmoser Date 2018-04-25 Time 09:35 Rev Time 0.00
Received By hmoser Date 2018-04-25 Time 09:29 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved