| Plan Review Stops For Permit 18040690 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-19 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-19 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-06-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-06-16 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-16 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2018-06-16 18:43:56 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 301, PLAN STILL STATES THAT THIS IS EXPOSURE | | | B. ROOF CALCS STILL FOR EXPOSURE B. | | | | | | AS THERE IS OVER 5000' DISTANCE OVER WATER, THIS | | | STRUCTURE IS LOCATED IN EXPOSURE D. REVISE PLAN AND | | | ROOF CALCS ACCORDINGLY. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-05-30 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-05-30 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2018-05-30 17:45:09 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC EXISTING BUILDING SECTION 606.1 | | | | | | 4) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR | | | EXPOSURE CATEGORY B. THIS PROJECT IS LOCATED ON CLEAR | | | LAKE AND IS EXPOSURE C. THE STRUCTURAL PLANS THAT HAVE | | | BEEN SIGNED AND SEALED BY MICHEAL A. GIOVANNOZZI, P.E. | | | SPECIFY THE EXPOSURE AS C. SUBMIT RAS 117 CALCULATIONS | | | THAT ARE FOR EXPOSURE C. LIMITATION NUMBER 7 ON PAGE 16 | | | OF THE ROOFING PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES | | | THE RAS 117 CALCULATIONS TO BE SIGNED AND SEALED. FAC | | | 61G15-23.001 REQUIRES A FLORIDA LICENSED PROFESSIONAL | | | ENGINEER TO SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT | | | ARE SUBMITTED FOR PUBLIC RECORD. FS 471.025 | | | | | | 5) THE WATER HEATER ENCLOSURE THAT WAS SUBMITTED DOES | | | NOT HAVE PRODUCT APPROVALS AND HAS NOT BEEN TESTED FOR | | | WINDLOADS. SUBMIT PRODUCT APPROVALS FOR A WATER HEATER | | | ENCLOSURE THAT MEETS THE REQUIRED WINDLOADS. FBC | | | 107.3.4 THE PLANS INDICATE THAT THE EXISTING GAS WATER | | | HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE. | | | PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS | | | WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE | | | WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A | | | STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT | | | FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND | | | FBCR-P2801.3 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-04-18 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2018-04-18 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2018-04-18 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2018-04-18 11:39:36 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEER'S PLANS REFERENCE THE FBC FIFTH EDITION | | | (2014). THE FBC SIXTH EDITION (2017) WENT INTO EFFECT | | | ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR | | | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | | REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553 | | | | | | 2) THE WIND DESIGN DATA IS NOT SPECIFIED ON THE | | | ENGINEER'S DRAWINGS. FBC EXISTING BUILDING SECTION | | | 606.1 | | | | | | 3) THE ENGINEER SHALL SPECIFY THE REQUIRED DESIGN | | | UPLIFT , GRAVITY AND LATERAL LOADS FOR THE NEW | | | STRUCTURAL BEAMS ON THE SIGNED AND SEALED PLANS. THE | | | EXISTING CONNECTORS WILL HAVE TO BE EVALUATED BY THE | | | ENGINEER TO DETERMINE IF THEY ARE ADEQUATE OR NEED TO | | | BE REPLACED. SPECIFY ANY NEW CONNECTORS ON THE PLANS. | | | FBC EXISTING BUILDING SECTION 606.1 | | | | | | 4) LIMITATION NUMBER 7 ON PAGE 16 OF THE ROOFING | | | PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES THE RAS 117 | | | CALCULATIONS TO BE SIGNED AND SEALED. FAC 61G15-23.001 | | | REQUIRES A FLORIDA LICENSED PROFESSIONAL ENGINEER TO | | | SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT ARE SUBMITTED | | | FOR PUBLIC RECORD. FS 471.025 | | | | | | 5) THE PLANS INDICATE THAT THE EXISTING GAS WATER | | | HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE. | | | PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS | | | WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE | | | WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A | | | STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT | | | FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND | | | FBCR-P2801.3 | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-19 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-06-25 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2018-06-25 11:14:42 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ONLY ONE COPY OF REVISED PLAN SUBMITTED, MUST HAVE 2 | | | COPIES. PROVIDE CORRECTION. WPB FBC 107.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-05-20 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-20 |
Time |
09:52 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-20 |
Time |
09:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-30 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-30 |
Time |
08:48 |
Sent To |
I |
|
| Notes |
| 2018-04-30 09:51:51 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND | | | SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE | | | ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); | | | 471.025; WPB FBC 107.2.1, 107.3.5 | | | 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | RE R314.3, R315.1; WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-07-19 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-07-19 |
Time |
08:53 |
Sent To |
|
|
| Notes |
| 2018-07-19 09:09:51 | EXISTING GAS WATER HEATER IS NOT BEING RELOCATED. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-06-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-02 |
Time |
03:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-06-02 |
Time |
02:56 |
Sent To |
I |
|
| Notes |
| 2018-06-02 03:11:26 | 1) INDICATE ON THE GAS PLANS THE TYPE OF PIPE MATERIAL | | | BEING INSTALLED FOR THE GAS LINE. | | | 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM | | | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 | | | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. | | | 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL | | | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) | | | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, | | | G2413.1, G2413.2, & G2413.3. | | | 4) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, | | | SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND | | | ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL | | | GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 | | | THROUGH G2439. | | | 5) SHOW THE SQUARE INCH AREA OF BOTH LOUVERS ON THE | | | ENCLOSURE. ATHE NET FREE AREA OF METAL LOUVERS SHALL BE | | | ASSUMED TO 75 PERCENT OF THE SQUARE INCH AREA OF THE | | | LOUVER PER THE 2017 FBC-FUEL GAS SEC. 304.10. | | | 6) COMBUSTION AIR REQUIREMENTS SHALL COMPLY WITH 2017 | | | FBC-FUEL GAS SEC.304.6. | | | 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | | LOCATION OF THE WATER HEATER.THE HOUSE PLAN CAN BE HAND | | | DRAWN.WPB AMEND TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2018-04-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-26 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-26 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2018-04-26 14:19:24 | GAS PLAN REVIEW | | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | | FBC-R, SEC. G2404.3. | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | | GAS SEC. 301.3. | | | | | | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS | | | INSTALLATION OR MODIFICATION OF SYSTEM. | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-07-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-19 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-06-11 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-06-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-02 |
Time |
03:11 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-16 |
Time |
14:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-04-16 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-05-22 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-05-22 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2018-05-22 14:11:16 | A/C CHANGEOUT ONLY NO MECHANICAL PLANS | | | | | | CHRIS MONTELLO | | | 561-805-6733 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-04-25 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-04-25 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-04-25 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-06-02 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2018-06-02 |
Time |
02:56 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2018-05-31 |
Time |
14:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-04-26 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-26 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-26 |
Time |
06:02 |
Sent To |
|
|
| Notes |
| 2018-04-26 14:18:02 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PROVIDE DOCUMENTATION THAT SHOWS THE EXISTING GAS | | | WATER HEATER IS APPROVED FOR EXTERIOR INSTILLATION IN | | | WET LOCATION OR PROVIDE A WEATHER PROOF ENCLOSURE. PER | | | WPB AMEND TO FBC 107.2.1 AND FBC RES M2001.1 | | | | | | 2. A SEPARATE PERMIT IS REQUIRED FOR THE GAS SYSTEM | | | MODIFICATION IT SHALL BE SHOWN TO BE CODE COMPLIANT. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|