Plan Review Details - Permit 18040690
Plan Review Stops For Permit 18040690
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-19 Cont ID  
Sent By shill Date 2018-07-19 Time 09:41 Rev Time 0.00
Received By shill Date 2018-07-19 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-06-16 Cont ID  
Sent By shill Date 2018-06-16 Time 18:42 Rev Time 0.00
Received By shill Date 2018-06-16 Time 18:42 Sent To  
Notes
2018-06-16 18:43:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, PLAN STILL STATES THAT THIS IS EXPOSURE
 B. ROOF CALCS STILL FOR EXPOSURE B.
  
 AS THERE IS OVER 5000' DISTANCE OVER WATER, THIS
 STRUCTURE IS LOCATED IN EXPOSURE D. REVISE PLAN AND
 ROOF CALCS ACCORDINGLY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-30 Cont ID  
Sent By rmcdouga Date 2018-05-30 Time 17:45 Rev Time 0.00
Received By rmcdouga Date 2018-05-30 Time 14:43 Sent To  
Notes
2018-05-30 17:45:09PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC EXISTING BUILDING SECTION 606.1
  
 4) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE FOR
 EXPOSURE CATEGORY B. THIS PROJECT IS LOCATED ON CLEAR
 LAKE AND IS EXPOSURE C. THE STRUCTURAL PLANS THAT HAVE
 BEEN SIGNED AND SEALED BY MICHEAL A. GIOVANNOZZI, P.E.
 SPECIFY THE EXPOSURE AS C. SUBMIT RAS 117 CALCULATIONS
 THAT ARE FOR EXPOSURE C. LIMITATION NUMBER 7 ON PAGE 16
 OF THE ROOFING PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES
 THE RAS 117 CALCULATIONS TO BE SIGNED AND SEALED. FAC
 61G15-23.001 REQUIRES A FLORIDA LICENSED PROFESSIONAL
 ENGINEER TO SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT
 ARE SUBMITTED FOR PUBLIC RECORD. FS 471.025
  
 5) THE WATER HEATER ENCLOSURE THAT WAS SUBMITTED DOES
 NOT HAVE PRODUCT APPROVALS AND HAS NOT BEEN TESTED FOR
 WINDLOADS. SUBMIT PRODUCT APPROVALS FOR A WATER HEATER
 ENCLOSURE THAT MEETS THE REQUIRED WINDLOADS. FBC
 107.3.4 THE PLANS INDICATE THAT THE EXISTING GAS WATER
 HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE.
 PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS
 WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE
 WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A
 STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT
 FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND
 FBCR-P2801.3
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By rmcdouga Date 2018-04-18 Time 13:40 Rev Time 0.00
Received By rmcdouga Date 2018-04-18 Time 07:36 Sent To  
Notes
2018-04-18 11:39:36PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S PLANS REFERENCE THE FBC FIFTH EDITION
 (2014). THE FBC SIXTH EDITION (2017) WENT INTO EFFECT
 ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553
  
 2) THE WIND DESIGN DATA IS NOT SPECIFIED ON THE
 ENGINEER'S DRAWINGS. FBC EXISTING BUILDING SECTION
 606.1
  
 3) THE ENGINEER SHALL SPECIFY THE REQUIRED DESIGN
 UPLIFT , GRAVITY AND LATERAL LOADS FOR THE NEW
 STRUCTURAL BEAMS ON THE SIGNED AND SEALED PLANS. THE
 EXISTING CONNECTORS WILL HAVE TO BE EVALUATED BY THE
 ENGINEER TO DETERMINE IF THEY ARE ADEQUATE OR NEED TO
 BE REPLACED. SPECIFY ANY NEW CONNECTORS ON THE PLANS.
 FBC EXISTING BUILDING SECTION 606.1
  
 4) LIMITATION NUMBER 7 ON PAGE 16 OF THE ROOFING
 PRODUCT ( NOA NO. 13-0204.14 ) REQUIRES THE RAS 117
 CALCULATIONS TO BE SIGNED AND SEALED. FAC 61G15-23.001
 REQUIRES A FLORIDA LICENSED PROFESSIONAL ENGINEER TO
 SIGN AND SEAL ALL OF THEIR DOCUMENTS THAT ARE SUBMITTED
 FOR PUBLIC RECORD. FS 471.025
  
 5) THE PLANS INDICATE THAT THE EXISTING GAS WATER
 HEATER IS TO BE MOVED TO THE EXTERIOR OF THE STRUCTURE.
 PROVIDE ADDITIONAL INFORMATION SUCH AS IS IT A TANKLESS
 WATER HEATER LABELED FOR OUTDOOR INSTALLATION OR ONE
 WITH A TANK THAT REQUIRES IT TO BE INSIDE OF A
 STRUCTURE. IF A STRUCTURE IS REQUIRED TO PROTECT IT
 FROM THE ELEMENTS PROVIDE DETAILS. FBC 107.2.1 AND
 FBCR-P2801.3
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-07-19 Cont ID  
Sent By jpearson Date 2018-07-19 Time 11:14 Rev Time 0.00
Received By jpearson Date 2018-06-25 Time 10:35 Sent To  
Notes
2018-06-25 11:14:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE COPY OF REVISED PLAN SUBMITTED, MUST HAVE 2
 COPIES. PROVIDE CORRECTION. WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-20 Cont ID  
Sent By jpearson Date 2018-05-20 Time 09:52 Rev Time 0.00
Received By jpearson Date 2018-05-20 Time 09:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 09:51 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 08:48 Sent To I
Notes
2018-04-30 09:51:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2018-07-19 Cont ID  
Sent By tklarge Date 2018-07-19 Time 09:09 Rev Time 0.00
Received By tklarge Date 2018-07-19 Time 08:53 Sent To  
Notes
2018-07-19 09:09:51EXISTING GAS WATER HEATER IS NOT BEING RELOCATED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 03:11 Rev Time 0.00
Received By tklarge Date 2018-06-02 Time 02:56 Sent To I
Notes
2018-06-02 03:11:261) INDICATE ON THE GAS PLANS THE TYPE OF PIPE MATERIAL
 BEING INSTALLED FOR THE GAS LINE.
 2) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 4) SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 5) SHOW THE SQUARE INCH AREA OF BOTH LOUVERS ON THE
 ENCLOSURE. ATHE NET FREE AREA OF METAL LOUVERS SHALL BE
 ASSUMED TO 75 PERCENT OF THE SQUARE INCH AREA OF THE
 LOUVER PER THE 2017 FBC-FUEL GAS SEC. 304.10.
 6) COMBUSTION AIR REQUIREMENTS SHALL COMPLY WITH 2017
 FBC-FUEL GAS SEC.304.6.
 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE WATER HEATER.THE HOUSE PLAN CAN BE HAND
 DRAWN.WPB AMEND TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 14:18 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 14:18 Sent To  
Notes
2018-04-26 14:19:24GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-07-19 Cont ID  
Sent By shill Date 2018-07-19 Time 09:41 Rev Time 0.00
Received By shill Date 2018-06-11 Time 15:17 Sent To  
Notes
2018-06-12 15:17:55R04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 03:11 Rev Time 0.00
Received By tklarge Date 2018-05-16 Time 14:20 Sent To  
Notes
2018-05-17 14:20:57R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-16 Time 13:31 Sent To  
Notes
2018-04-17 13:31:26R17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By cmontell Date 2018-05-22 Time 14:12 Rev Time 0.00
Received By cmontell Date 2018-05-22 Time 14:09 Sent To  
Notes
2018-05-22 14:11:16A/C CHANGEOUT ONLY NO MECHANICAL PLANS
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-25 Cont ID  
Sent By cmontell Date 2018-04-25 Time 14:25 Rev Time 0.00
Received By cmontell Date 2018-04-25 Time 14:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-02 Cont ID  
Sent By tklarge Date 2018-06-02 Time 02:56 Rev Time 0.00
Received By tklarge Date 2018-05-31 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 06:02 Sent To  
Notes
2018-04-26 14:18:021ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE DOCUMENTATION THAT SHOWS THE EXISTING GAS
 WATER HEATER IS APPROVED FOR EXTERIOR INSTILLATION IN
 WET LOCATION OR PROVIDE A WEATHER PROOF ENCLOSURE. PER
 WPB AMEND TO FBC 107.2.1 AND FBC RES M2001.1
  
 2. A SEPARATE PERMIT IS REQUIRED FOR THE GAS SYSTEM
 MODIFICATION IT SHALL BE SHOWN TO BE CODE COMPLIANT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  