Plan Review Details - Permit 18040645
Plan Review Stops For Permit 18040645
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-27 Cont ID  
Sent By rmcdouga Date 2019-02-27 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2019-02-27 Time 15:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-09 Cont ID  
Sent By rmcdouga Date 2019-01-09 Time 16:29 Rev Time 0.00
Received By rmcdouga Date 2019-01-08 Time 18:54 Sent To  
Notes
2019-01-09 16:29:17PLAN REVIEW COMMENTS
 FOUNDATION ONLY PERMIT
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1- NOT COMPLIED. THE SUBMIT A COPY OF THE LOMR FROM
 FEMA THAT IS MENTIONED IN YOUR RESPONSE. RESIDENTIAL
 BUILDINGS LOCATED IN A SPECIAL FLOOD HAZARD AREA ARE
 NOT ALLOWED TO HAVE BASEMENTS BELOW THE BFE. THE
 PROPOSED STRUCTURE IS LOCATED IN FLOOD ZONE AE WITH
 BASE FLOOD ELEVATIONS 6 AND 7. ACCORDING TO CITY
 ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR ELEVATION
 NEEDS TO BE TWO FEET (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
 BASEMENT FLOOR NEEDS TO BE RAISED.
 NOTE: ELEVATION CERTIFICATES ARE REQUIRED. INCLUDING
 CONSTRUCTION DRAWINGS, DURING CONSTRUCTION AND FINAL.
  
 2- PARTIAL COMPLIANCE. THIS DATA WILL NOT BE REQUIRED
 IF THE PROPERTY IS REMOVED FROM THE FLOOD HAZARD AREA.
 PROVIDE ALL THE INFORMATION REQUIRED BY FBC 1603.1.7
 FLOOD DESIGN DATA.
  
 3- A) & B) COMPLIED.
  
 4- NOT COMPLIED. PLAN SHEETS 000.1 THRU 000.4 ARE
 MARKED "PRELIMINARY NOT FOR CONSTRUCTION" AND IT IS
 STATED THAT THE DOCUMENT IS NOT FOR PERMITS OR OTHER
 OFFICIAL PURPOSES IN THE TITLE BLOCK. PLEASE REMOVE
 THIS INFORMATION. ALL PLANS AND CONSTRUCTION DOCUMENTS
 THAT ARE SUBMITTED FOR PERMIT ARE REQUIRED TO BE SIGNED
 AND SEALED BY THE ENGINEER OR ARCHITECT THAT PREPARED
 THEM. FS 471 & 481
  
 5- A) COMPLIED.
  
 B) COMPLIED.
  
 6- NOTED. WILL COMPLY. THE CITY OF WEST PALM BEACH ART
 IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO
 ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 7- NOT COMPLIED. PLEASE COORDINATE WITH RICHARD
 GATHRIGHT AT [email protected]. THE PROPOSED BUILDING
 QUALIFIES AS A THRESHOLD BUILDING. A COMPLETED THREHOLD
 INSPECTION AGREEMENT IS REQUIRED TO BE SUBMITTED AND
 APPROVED BY THIS OFFICE. I WILL BE HAPPY TO EMAIL A
 COPY OF THE CITY'S THRESHOLD/SPECIAL INSPECTOR
 GUIDELINES AND FORMS TO YOU. JUST SEND ME AN EMAIL
 REQUESTING IT. FBC 110.8 CITY AMENDMENTS.
  
 8- NOT COMPLIED. SEC. 110.8.4 CITY AMENDMENTS: EACH
 ENFORCEMENT AGENCY SHALL REQUIRE THAT, ON EVERY
 THRESHOLD BUILDING: SEC. 110.8.4.3 ALL SHORING AND
 RESHORING PROCEDURES, PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORD KEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR .
  
 NOT COMPLIED. THIS STATEMENT ONLY APPEARS ON THE
 ARCHITECTURAL PLANS. PLEASE ADD IT TO THE STRUCTURAL
 PLANS THAT ARE SIGNED BY THE ENGINEER. THE STATEMENT
 CAN BE PLACED ON THE STRUCTURAL COVER SHEET S-000.
 SEC.110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633.
  
 9- NOTED. WILL COMPLY.
  
 10- NOTED. WILL COMPLY.
  
 11- COMPLIED.
  
 12- NOTED. WILL COMPLY.
  
 13- A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NOTE: CHECK FOR COMPLIANCE WITH THE TWO FIRE
 SERVICE ACCESS ELEVATORS SEC. 403.6.1 FBC.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-08 Cont ID  
Sent By rmcdouga Date 2018-11-08 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2018-11-07 Time 15:27 Sent To  
Notes
2018-11-08 07:35:40PLAN REVIEW COMMENTS
 FOUNDATION ONLY PERMIT
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1- NOT COMPLIED. SUBMIT A COPY OF THE LOMR FROM FEMA
 THAT IS MENTIONED IN YOUR RESPONSE. RESIDENTIAL
 BUILDINGS LOCATED IN A SPECIAL FLOOD HAZARD AREA ARE
 NOT ALLOWED TO HAVE BASEMENTS BELOW THE BFE. THE
 PROPOSED STRUCTURE IS LOCATED IN FLOOD ZONE AE WITH
 BASE FLOOD ELEVATIONS 6 AND 7. ACCORDING TO CITY
 ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR ELEVATION
 NEEDS TO BE TWO FEET (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
 BASEMENT FLOOR NEEDS TO BE RAISED.
 NOTE: ELEVATION CERTIFICATES ARE REQUIRED. INCLUDING
 CONSTRUCTION DRAWINGS, DURING CONSTRUCTION AND FINAL.
  
  
 2- PARTIAL COMPLIANCE. THIS DATA WILL NOT BE REQUIRED
 IF THE PROPERTY IS REMOVED FROM THE FLOOD HAZARD AREA.
 PROVIDE ALL THE INFORMATION REQUIRED BY FBC 1603.1.7
 FLOOD DESIGN DATA.
  
  
 3- A) & B) COMPLIED.
  
 4- PARTIAL COMPLIANCE. THE SITE PLANS ARE REQUIRED
 MARKED FOR REFERENCE ONLY. ALL PLANS AND CONSTRUCTION
 DOCUMENTS THAT ARE SUBMITTED FOR PERMIT ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ENGINEER OR ARCHITECT THAT
 PREPARED THEM. FS 471 & 481
  
 5- A) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT.
 SEC.105.13 CITY AMENDMENTS.
  
 B) THIS IA A PHASED PERMIT APPLICATION FOR FOUNDATION
 ONLY. SEC. 105.13 CITY AMENDMENTS. A COMPLETE REVIEW
 FOR BUILDING CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME. A VERY LIMITED REVIEW WAS DONE ON THE LIFESAFETY
 PLANS SUBMITTED. INFORMATION ON THE STAIRWAY WAY ACCESS
 IS NOT VERY CLEAR. ALSO, THE WAY THE TRAVEL DISTANCES
 FROM THE MOST REMOTE POINTS ARE NOT CLEAR AT THIS
 POINT. THE EXIT DISCHARGE ON SOME STAIRWAYS IS NOT
 CLEAR. BASED ON A PRELIMINARY REVIEW OF THE LIFESAFETY
 PLANS SUBMITTED IT WAS OBSERVED THAT DESIGN
 PROFESSIONAL IS USING THE TOTAL SIZE OF THE DOORS FOR
 EGRESS CAPACITY CALCULATIONS. THIS IS INCORRECT. NEED
 TO USE THE CLEAR WIDTH OPENING OF THE DOOR FOR EGRESS
 CAPACITY. REVISE ALL CALCULATIONS SHOWN ON ALL PLANS AS
 REQUIRED. SEE SEC. 1010.1.1 FOR DETERMINATION OF
 MINIMUM CLEAR WIDTH OF DOOR. COMPLETE REVIEW OF LIFE
 SAFETY PLANS WILL BE DONE WHEN SUBMITTING THE PLANS FOR
 THE BUILDING PERMIT.
  
  
 6- NOTICE ONLY: THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
 7- THE PROPOSED BUILDING QUALIFIES AS A THRESHOLD
 BUILDING. A COMPLETED THREHOLD INSPECTION AGREEMENT IS
 REQUIRED TO BE SUBMITTED AND APPROVED BY THIS OFFICE. I
 WILL BE HAPPY TO EMAIL A COPY OF THE CITY'S
 THRESHOLD/SPECIAL INSPECTOR GUIDELINES AND FORMS TO
 YOU. JUST SEND ME AN EMAIL REQUESTING IT. FBC 110.8
 CITY AMENDMENTS.
  
 8- SEC. 110.8.4 CITY AMENDMENTS: EACH ENFORCEMENT
 AGENCY SHALL REQUIRE THAT, ON EVERY THRESHOLD BUILDING:
 SEC. 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORD KEEPING.
 EACH SHORING AND RESHORING INSTALLATION SHALL BE
 SUPERVISED, INSPECTED AND CERTIFIED TO BE IN COMPLIANCE
 WITH THE SHORING DOCUMENTS BY THE CONTRACTOR .
  
 SEC.110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633.
  
 NOTE: ALL PLANS SUBMITTED BY ARCHITECT AND ENGINEER
 NEED THIS STATEMENT.
  
  
 9- NOTED. WILL COMPLY.
  
 10- NOTED. WILL COMPLY.
  
 11- NOT COMPLIED. I WAS UNABLE TO LOCATE NOTE 11 ON
 SHEET S-100 AS INDICATED ON THE RESPONSE LETTER. PLEASE
 PROVIDE COMPLIANCE WITH PROTECTION OF PEDESTRIANS AS
 REQUIRED BY SEC. 3306.1 FBC.
  
 12- BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13- A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ****NOTE: CHECK FOR COMPLIANCE WITH THE TWO FIRE
 SERVICE ACCESS ELEVATORS SEC. 403.6.1 FBC.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By jgomez Date 2018-05-23 Time 19:03 Rev Time 0.00
Received By jgomez Date 2018-05-22 Time 09:32 Sent To  
Notes
2018-05-22 11:44:55FOUNDATION ONLY BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
  
 1- THE PROPOSED STRUCTURE IS LOCATED IN FLOOD ZONE AE
 WITH BASE FLOOD ELEVATIONS 6 AND 7. ACCORDING TO CITY
 ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR ELEVATION
 NEEDS TO BE TWO FEET FREEBOARD ABOVE THE BASE FLOOD
 ELEVATION.
 BASEMENT FLOOR NEEDS TO BE RAISED.
  
 NOTE: ELEVATION CERTIFICATES ARE REQUIRED. INCLUDING
 CONSTRUCTION DRAWINGS, DURING CONSTRUCTION AND FINAL.
  
  
 2- NEW FLOOD MAPS WENT INTO EFFECT ON OCTOBER 5TH 2017.
 THE NEW MAPS BASED FLOOD ELEVATIONS ARE BASED NAVD
 1988. PLANS AND INFORMATION SUBMITTED ARE BASED ON NGVD
 1929. NEED TO UPDATE ALL THE INFORMATION SUBMITTED
 INCLUDING PLANS TO REFERENCE THE CURRENT ADOPTED MAPS.
 PROVIDE ALL THE INFORMATION REQUIRED BY SEC. 1603.17.7
 FBC.
  
  
 3- A) SHEET S-001: CITY AMENDMENTS SEC. 120.1 REQUIRES
 TO USE THE ULTIMATE WIND LOAD OF 170 MPH VULT. REVISE
 SEC. CD-3 AS REQUIRED AND CLARIFY WHY THE NOMINAL WIND
 LOAD IS 112MPH VASD INSTEAD OF 132MPHVASD?
  
 B) CODES AND DESIGN CRITERIA ON SHEET S-001 REFERENCES
 ACI 530-11. CHAPTER 35 FBC REFERENCES ACI 530-13.
 UPDATE AS REQUIRED.
  
 4- PROVIDE SURVEY SHOWING THE PROPOSED STRUCTURE. SEC.
 107.3.5 CITY AMENDMENTS.
  
 5- A) NOTICE AT RISK, THIS PERMIT IS FOR A FOUNDATION
 ONLY, PLEASE PROVIDE AN APPENDIX TO THE PERMIT
 APPLICATION, DESCRIPTION OF WORK, AS TO WHAT WORK IS TO
 BE ACCOMPLISHED UNDER THIS FOUNDATION PERMIT.
 SEC.105.13 CITY AMENDMENTS.
  
 B) THIS IA A PHASED PERMIT APPLICATION FOR FOUNDATION
 ONLY. SEC. 105.13 CITY AMENDMENTS. A THOUGHTFULLY
 REVIEW FOR BUILDING CODE COMPLIANCE CAN NOT BE DONE AT
 THIS TIME. A VERY LIMITED REVIEW WAS DONE ON THE
 LIFESAFETY PLANS SUBMITTED. INFORMATION ON THE STAIRWAY
 WAY ACCESS IS NO VERY CLEAR. ALSO, THE WAY THE TRAVEL
 DISTANCES FROM THE MOST REMOTE POINTS ARE NOT CLEAR AT
 HIS POINT. THE EXIT DISCHARGE ON SOME STAIRWAYS IS NOT
 CLEAR. BASED ON A PRELIMINARY REVIEW OF THE LIFESAFETY
 PLANS SUBMITTED IT WAS OBSERVED THAT DESIGN
 PROFESSIONAL IS USING THE TOTAL SIZE OF THE DOORS FOR
 EGRESS CAPACITY CALCULATIONS. THIS IS INCORRECT. NEED
 TO USE THE CLEAR WIDTH OPENING OF THE DOOR FOR EGRESS
 CAPACITY. REVISE ALL CALCULATIONS SHOWN ON ALL PLANS AS
 REQUIRED. SEE SEC. 1010.1.1 FOR DETERMINATION OF
 MINIMUM CLEAR WIDTH OF DOOR. COMPLETE REVIEW OF LIFE
 SAFETY PLANS WILL DONE WHEN SUBMITTING THE PLANS FOR
 THE BUILDING PERMIT.
  
  
 NOTE: A FOUNDATION PERMIT MAY NOT BE ISSUED UNTIL A
 BUILDING PERMIT APPLICATION IS SUBMITTED FOR THE
 CONSTRUCTION OF THE BUILDING.
  
  
 6- NOTICE ONLY: THE CITY OF WEST PALM BEACH ART IN
 PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO ANY
 REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE
 PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE
 TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $500,000. PER CITY OF WEST PALM BEACH
 ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE
 OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION
 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS
 1% OF THE TOTAL PROJECT CONSTRUCTION COST.
  
  
 7- THE PROPOSED BUILDING QUALIFIES AS A THRESHOLD
 BUILDING. SPECIAL INSPECTOR IS REQUIRED. CONTACT JULIO
 GOMEZ (561)805-6712 FOR MORE INFORMATION REGARDING
 SPECIAL INSPECTOR REQUIREMENTS AND APPROVAL. SEC. 110.8
 CITY AMENDMENTS.
  
 8- SEC. 110.8.4 CITY AMENDMENTS: EACH ENFORCEMENT
 AGENCY SHALL REQUIRE THAT, ON EVERY THRESHOLD BUILDING:
  
 SEC. 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE
 SUBMITTED TO THE ENFORCEMENT AGENCY FOR RECORD KEEPING.
 EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE
 SHORING DOCUMENTS BY THE CONTRACTOR .
  
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED
 BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633.
  
 NOTE: ALL PLANS SUBMITTED BY ARCHITECT AND ENGINEER
 NEED THIS STATEMENT.
  
  
 9- FOR DIGITAL PLANS, AFTER PERMIT APPROVAL PLEASE
 E-MAIL THE PERMIT LIBRARIAN FOR PROPER PROCESSING.
 SEC. 107.2.1.3 CITY AMENDMENTS.
  
 10- PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 11-PLEASE PROVIDE COMPLIANCE WITH PROTECTION OF
 PEDESTRIANS AS REQUIRED BY SEC. 3306.1 FBC.
  
 12-BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13- A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 ****NOTE: CHECK FOR COMPLIANCE WITH THE TWO FIRE
 SERVICE ACCESS ELEVATORS SEC. 403.6.1 FBC.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-03 Cont ID  
Sent By jpearson Date 2018-10-03 Time 15:08 Rev Time 0.00
Received By jpearson Date 2018-10-03 Time 15:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-06 Cont ID  
Sent By jpearson Date 2018-05-06 Time 09:11 Rev Time 0.00
Received By jpearson Date 2018-05-01 Time 16:13 Sent To  
Notes
2018-05-06 09:11:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 2. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE AND FEEDERS IS ADEQUATE. NEC 215.2,
 220, 408.30
 3. PLAN PROVIDED STATES THAT THE PLAN IS NOT FOR
 CONSTRUCTION. PROVIDE CORRECTION. WPB FBC 107.1,
 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-12-28 Cont ID  
Sent By RRossano Date 2018-12-28 Time   Rev Time 0.00
Received By rrossano Date 2018-12-28 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-11-05 Cont ID  
Sent By mgonzale Date 2018-11-05 Time   Rev Time 1.00
Received By mgonzale Date 2018-11-05 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By shill Date 2018-05-02 Time 16:33 Rev Time 0.00
Received By shill Date 2018-05-02 Time 16:33 Sent To  
Notes
2018-05-02 16:34:56CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-12-12 Cont ID  
Sent By scaldero Date 2018-12-12 Time 10:43 Rev Time 0.00
Received By scaldero Date 2018-12-12 Time 10:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-09-26 Cont ID  
Sent By scaldero Date 2018-09-26 Time 11:02 Rev Time 0.00
Received By scaldero Date 2018-09-26 Time 11:00 Sent To  
Notes
2018-09-26 11:02:06PERMIT # 18040645
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS
  
 1) PERMIT AND APPROVAL IS FOR FOUNDATION ONLY.
  
 2) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 3) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE AND FIRE HYDRANTS.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-20 Cont ID  
Sent By scaldero Date 2018-04-20 Time 09:41 Rev Time 0.00
Received By scaldero Date 2018-04-20 Time 09:28 Sent To  
Notes
2018-04-20 09:41:39PERMIT # 18040645
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND
 WATER MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 2) SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 INSTALLATION AND/OR MODIFICATION OF THE UNDERGROUND
 FIRE LINE AND FIRE HYDRANTS.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-07 Cont ID  
Sent By lmarchan Date 2019-03-07 Time 10:49 Rev Time 0.00
Received By lmarchan Date 2019-02-10 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-22 Cont ID  
Sent By lmarchan Date 2019-01-22 Time 13:36 Rev Time 0.00
Received By lmarchan Date 2018-12-11 Time 12:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-17 Cont ID  
Sent By rmcdouga Date 2018-11-17 Time 11:39 Rev Time  
Received By shill Date 2018-09-24 Time 09:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-06-04 Cont ID  
Sent By lmarchan Date 2018-06-04 Time 13:29 Rev Time 0.00
Received By lmarchan Date 2018-04-19 Time 16:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-01-11 Cont ID  
Sent By lmarchan Date 2019-01-10 Time 15:49 Rev Time 0.00
Received By lmarchan Date 2019-01-08 Time 13:46 Sent To  
Notes
2019-01-10 16:40:31PLANS STAMPED NO FEE DUE. AWAITING COPY OF BACKUP IN
 LIEU OF RECEIPT AS NO RECEIPT IS PRODUCED WHEN NO MONEY
 DUE. SAK
2019-01-10 15:49:49PER IMPACT FEE OFFICE, NO FEES OWED. LEM
2019-01-08 13:46:361/8/19 SENT EMAIL TO IMPACT FEE OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By shill Date 2018-12-20 Time 15:28 Rev Time 0.00
Received By shill Date 2018-12-20 Time 15:28 Sent To  
Notes
2018-12-20 15:29:03PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By jgomez Date 2018-05-24 Time 18:55 Rev Time 0.00
Received By jgomez Date 2018-05-24 Time 18:23 Sent To  
Notes
2018-05-24 18:56:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By rmcdouga Date 2019-02-27 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2019-02-27 Time 15:02 Sent To  
Notes
2019-02-27 15:34:08LETTER OF MAP REVISION BASED ON FILL (LOMR-F) DATED
 JANURARY 10, 2019, CASE NUMBER 19-04-1248A. PROPERTY
 AROUND BUILDING WAS REMOVED FROM THE SFHA AND CHANGED
 TO FLOOD ZONE X.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By rmcdouga Date 2018-11-08 Time 10:52 Rev Time 0.00
Received By rmcdouga Date 2018-11-08 Time 10:52 Sent To  
Notes
2018-11-08 10:53:22ELEVATION CERTIFICATE OR LOMR IS REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By gjohnson Date 2018-10-18 Time 16:18 Rev Time 0.00
Received By gjohnson Date 2018-10-18 Time 16:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-21 Cont ID  
Sent By gjohnson Date 2018-05-21 Time 16:29 Rev Time 0.00
Received By gjohnson Date 2018-05-21 Time 15:45 Sent To  
Notes
2018-05-21 16:35:551ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE ISOMETRIC DRAWINGS FOR UNDERGROUND PIPING
 ONLY TO INCLUDE DFU LOAD ON THE SANITARY AND THE SQFT
 ON THE STORM DRAIN PIPING ALSO ANY COND. AND WATER
 PIPING THAT IS UNDERGROUND. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 2. THE PLAN SHEET IS NOTED NOT FOR CONSTRUCTION
 PRELIMINARY NOT FOR PERMIT PLEASE REMOVE NOTE AND STATE
 FOR FOUNDATION ONLY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 18:49 Rev Time 0.00
Received By shill Date 2018-12-21 Time 18:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 06:32 Rev Time 0.00
Received By shill Date 2018-11-06 Time 06:23 Sent To  
Notes
2018-10-03 13:57:291. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS
 471, FS 481.
 LAST PLAN REVIEWER SHOULD ENTER STATUS OF PASSED IF ALL
 OTHER REVIEWS PASS. IF ANY DISCIPLINE FAILS, A STATUS
 OF FAIL SHOULD BE ENTERED SO THAT NEW SHEETS SUBMITTED
 IN THE NEXT REVIEW CYCLE CAN BE REVIEWED FOR SIGNATURE.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-05-24 Cont ID  
Sent By shill Date 2018-05-24 Time 17:47 Rev Time 0.00
Received By shill Date 2018-05-24 Time 17:47 Sent To  
Notes
2018-05-24 17:48:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS ARE IN ACCORDANCE WITH FS
 471, FS 481. NEW SHEETS SUBMITTED IN THE NEXT REVIEW
 CYCLE REQUIRE REVIEW.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By rmcdouga Date 2019-01-14 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2019-01-14 Time 09:38 Sent To  
Notes
2019-01-14 09:44:12THORNTON TOMASETTI (954) 903-9300
 101 NE 3RD AVE, SUITE 1170, FORT LAUDERDALE, FL 33301
 [email protected]
 ERIC DAVID SEARCH (786) 385-1518
 PE 54984
 SI 7018775

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-11-08 Cont ID  
Sent By rmcdouga Date 2018-11-08 Time 10:48 Rev Time 0.00
Received By rmcdouga Date 2018-11-08 Time 10:48 Sent To  
Notes
2018-11-08 10:51:06THRESHOLD INSPECTION AGREEMENT AND INSPECTION PLAN IS
 REQUIRED. FBC 110.8

Review Stop Z ZONING
Rev No 4 Status P Date 2019-03-07 Cont ID  
Sent By eschneid Date 2019-03-07 Time 09:01 Rev Time 0.25
Received By eschneid Date 2019-03-07 Time 09:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2019-01-22 Cont ID  
Sent By eschneid Date 2019-01-22 Time 09:55 Rev Time 0.75
Received By eschneid Date 2019-01-22 Time 09:55 Sent To  
Notes
2019-01-22 10:24:29PASSED W/PROVISO
  
 1) THE DEVELOPER SHALL PERFORM A "CONDITION SURVEY" OF
 THE ADJOINING PROPERTIES PRIOR TO THE COMMENCEMENT OF
 ANY CONSTRUCTION ACTIVITIES. THE DEVELOPER SHALL
 CONFORM TO THE APPROPRIATE INDUSTRY STANDARDS APPROVED
 BY THE CITY'S CONSTRUCTION SERVICES DEPARTMENT IN
 MONITORING THE VIBRATION EFFECTS ON THE ADJOINING
 PROPERTIES; THIS SHALL INCLUDE, BUT IS NOT LIMITED TO,
 THE PLACEMENT OF SEISMIC METERS, INSPECTIONS, AND
 SIMILAR ACTIVITIES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2018-11-16 Cont ID  
Sent By eschneid Date 2018-11-16 Time 15:21 Rev Time 2.00
Received By eschneid Date 2018-11-09 Time 16:04 Sent To  
Notes
2018-11-16 16:30:16FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE MINOR AMENDMENT FOR THE CHANGES TO THE PLANS HAS
 NOT BEEN APPROVED. THE OUTSTANDING COMMENTS RELATING TO
 THE FOUNDATION ARE LISTED BELOW:
  
 A. ZONING - UPON REVIEW OF THE REVISED PLANS WHICH
 INCLUDE THE EGRESS PATHWAY, STAFF NOTED THAT THE
 RETAINING WALL LOCATION IS SHOWN FURTHER FROM THE WEST
 PROPERTY LINE ON THE ARCHITECTURAL SITE PLAN AND THE
 LANDSCAPE PLAN THAN IT IS SHOWN ON THE CIVIL PLANS.
 WHICH RETAINING WALL LOCATION IS CORRECT? - THE
 LOCATION OF THIS RETAINING WALL AFFECTS THE LOCATION OF
 THE WALLS FOR THE BELOW GRADE PARKING.
  
 B. BUILDING - APPLICANT THOUGHT THEY WOULD HAVE THE
 LOMR LETTER BY OCTOBER 8. AS OF TODAY, THEY HAVE NOT
 ADVISED THAT IT WAS ISSUED (AND IT IS NOT ON THE FEMA
 WEBSITE). I'VE ASKED FOR AN UPDATE TWICE SO I DO NOT
 THINK THEY HAVE AN ANSWER FROM FEMA YET. - NOTE: THE
 LOMR WAS SUBSEQUENTLY RECEIVED BY THE CITY AND WAS NOT
 APPROVED.
  
 2) SHEET S-100 DOES NOT MATCH THE FOUNDATION WALL
 LAYOUT SHOWN ON SHEETS S-100A. THE MATCH LINE BETWEEN
 SHEETS S-100A AND S-100B DO NOT ACTUALLY MATCH ALONG
 THE SOUTH PORTION OF THE PLANS. THIS IS THE SAME ISSUE
 IDENTIFIED IN COMMENT NO. 1 ABOVE. THIS SEEMS TO BE AN
 ISSUE ON ALL THE PLANS UPLOADED ON 4/19/2018.
  
 3) REVISED CIVIL PLANS WERE NOT UPLOADED WITH THE LAST
 PERMIT RESUBMITTAL AND THUS THESE ARE NOT THE MOST
 RECENT PLANS REVIEWED AS PART OF THE MINOR AMENDMENT.
  
 CONDITIONS FOR WHEN PERMIT IS ISSUED:
  
 1) THE DEVELOPER SHALL PERFORM A "CONDITION SURVEY" OF
 THE ADJOINING PROPERTIES PRIOR TO THE COMMENCEMENT OF
 ANY CONSTRUCTION ACTIVITIES. THE DEVELOPER SHALL
 CONFORM TO THE APPROPRIATE INDUSTRY STANDARDS APPROVED
 BY THE CITY'S CONSTRUCTION SERVICES DEPARTMENT IN
 MONITORING THE VIBRATION EFFECTS ON THE ADJOINING
 PROPERTIES; THIS SHALL INCLUDE, BUT IS NOT LIMITED TO,
 THE PLACEMENT OF SEISMIC METERS, INSPECTIONS, AND
 SIMILAR ACTIVITIES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2018-06-04 Cont ID  
Sent By ES Date 2018-06-04 Time 11:19 Rev Time 0.00
Received By eschneid Date 2018-06-04 Time 11:19 Sent To  
Notes
2018-06-04 13:20:15FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS:
  
 1) ORDINANCE NO. 4245-09 CONTAINS THE LATEST
 DEVELOPMENT REGULATIONS FOR THE 1515 SITE APPROVAL.
 PLEASE ADDRESS THE FOLLOWING REQUIREMENTS:
  
 A. RECORD, IN THE PUBLIC RECORDS OF PALM BEACH COUNTY,
 AN ABANDONMENT OF ALL EASEMENTS THAT CONFLICT WITH THE
 BUILDING, AS WELL AS ANY OTHER UNNECESSARY EASEMENTS.
  
 B. VERIFY THAT THE PROJECT SHALL BE CONSTRUCTED USING
 AN AUGURED PILING OR SIMILAR PILING SYSTEM.
  
 C. THE DEVELOPER SHALL PERFORM A "CONDITION SURVEY" OF
 THE ADJOINING PROPERTIES PRIOR TO THE COMMENCEMENT OF
 ANY CONSTRUCTION ACTIVITIES. THE DEVELOPER SHALL
 CONFORM TO THE APPROPRIATE INDUSTRY STANDARDS APPROVED
 BY THE CITY'S CONSTRUCTION SERVICES DEPARTMENT IN
 MONITORING THE VIBRATION EFFECTS ON THE ADJOINING
 PROPERTIES; THIS SHALL INCLUDE, BUT IS NOT LIMITED TO,
 THE PLACEMENT OF SEISMIC METERS, INSPECTIONS, AND
 SIMILAR ACTIVITIES.
  
 D. REGISTER THE PROJECT WITH THE U.S. GREEN BUILDING
 COUNCIL.
  
 2) PROVIDE VERIFICATION THAT THE FOLLOWING ITEMS FROM
 THE MAY 11, 2017 MINOR AMENDMENT APPROVAL LETTER, HAVE
 BEEN MET:
  
 A. IF THE GARAGE IS REQUIRED TO BE VENTED, THE
 EQUIPMENT MAY NOT BE LOCATED ON A FACADE ADJACENT TO
 THE NEIGHBORING STRUCTURES OR RIGHTS-OF-WAY AND MUST
 NOT VENT FUMES OR DIRECT NOISE TOWARD THE NEIGHBORING
 STRUCTURES OR RIGHTS-OF-WAY.
  
 B. PRIOR TO THE ISSUANCE OF PERMITS FOR THE PROJECT,
 THE METHOD FOR CONTROLLING GROUNDWATER FROM ENTERING
 THE SUBTERRANEAN PARKING GARAGE AND HOW GROUNDWATER
 WILL BE DISCHARGED FROM THE SITE ARE TO BE APPROVED BY
 THE CITY'S ENGINEERING SERVICES DEPARTMENT.
  
 C. DRAINAGE CALCULATIONS THAT ACCOUNT FOR SEA LEVEL
 RISE IMPACTS ON THE ON-SITE STORMWATER SYSTEM SHALL BE
 SUBMITTED WITH THE ENGINEERING PERMIT APPLICATION.
  
 D. IN THE ENGINEERING PERMIT PLANS, SHOW CONFLICT
 INFORMATION (BOTTOM AND TOP OF CROSSING PIPES) AT THE
 CONFLICT POINTS OF THE PROPOSED WATER AND SANITARY
 SEWER PIPES WITH THE EXISTING AND PROPOSED STORM DRAINS
 JUST TO THE NORTH OF THE BUILDING AND INSIDE THE
 PROPERTY.
  
 E. THE ENGINEERING PERMIT PLANS SHALL SHOW THE CITY'S
 "POINT-OF-SERVICE" MANHOLE WITHIN THE CITY'S
 RIGHT-OF-WAY.
  
 F. THE ENGINEERING PERMIT PLANS SHALL SHOW THE "FIRE
 POINT-OF-SERVICE" PER 2016 NFPA 24, FROM THE CONNECTION
 POINT OF THE PROPOSED FIRE LINE TO THE EXISTING WATER
 MAIN LOCATED WITHIN THE CITY'S RIGHT-OF-WAY I.E. WHERE
 TAPPING SLEEVE AND VALVES IS SHOWN TO BE FOR BOTH SOUTH
 FLAGLER DR. AND ARKONA CT.
  
 G. THE FINAL WATER AND SEWER PLANS SHALL INCLUDE A NOTE
 STATING, "ALL BACKFLOW DEVICES MUST BE LEAD FREE."
  
 3) THE PLANS HAVE CHANGED FROM WHAT WAS APPROVED BY THE
 MAY 11, 2017 MINOR AMENDMENT. THESE CHANGES INCLUDE AN
 ENLARGED BASEMENT PARKING, A REWORKED ENTRY COURT AND A
 DIFFERENT POOL DECK LAYOUT. STAFF NEEDS TO REVIEW THE
 ENTIRE PACKAGE AS PART OF A MINOR AMENDMENT PRIOR TO
 ISSUING THE APPROVAL OF THE FOUNDATION PERMIT TO MAKE
 SURE EVERYTHING MEETS THE APPROVAL DOCUMENTS AS WELL AS
 THE CODE REQUIREMENTS, AND THUS THE FOUNDATION CAN BE
 BUILT AS SHOWN. ZONING STAFF HAS NOTED THAT THERE IS A
 DRIVE AISLE SHOWN AT 23 FEET IN WIDTH, WHICH IS LESS
 THAN THE REQUIRED 24 FOOT MINIMUM. A FULL REVIEW WILL
 BE DONE AS PART OF THE MINOR AMENDMENT.
  
 4) THE LIFE SAFETY AND THE SITE PLAN SHOW THE GARAGE AT
 8 FEET 7 INCHES, WHILE SHEET C.5.00 SHOWS THE SAME AREA
 AT 9.58 NGVD. PLEASE CLARIFY.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]