Plan Review Details - Permit 18040631
Plan Review Stops For Permit 18040631
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By jleahy Date 2018-04-20 Time 06:39 Rev Time 0.00
Received By fgiaquin Date 2018-04-20 Time 06:23 Sent To I
Notes
2018-04-20 06:39:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. "1 SET OF 3# 4/0 IN 3" RMC FROM METER TO CONTROLLER"
 DOES NOT MEET THE REQUIREMENTS OF NEC 250.24(C). THE
 GROUNDED CONDUCTOR MUST BE BROUGHT TO THE SERVICE
 DISCONNECTING MEANS (FIRE PUMP CONTROLLER).
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 5TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 5TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-20 Cont ID  
Sent By jleahy Date 2018-04-20 Time 16:26 Rev Time 0.00
Received By jleahy Date 2018-04-13 Time 12:48 Sent To  
Notes
2018-04-16 12:48:40REVISION ROUTED TO JLEAHY


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved