Plan Review Details - Permit 18040609
Plan Review Stops For Permit 18040609
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-24 Cont ID  
Sent By jgomez Date 2018-05-24 Time 11:30 Rev Time 0.00
Received By jgomez Date 2018-05-24 Time 11:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-05-24 Cont ID  
Sent By jgomez Date 2018-05-24 Time 11:30 Rev Time 0.00
Received By jgomez Date 2018-05-24 Time 11:25 Sent To  
Notes
2018-05-24 11:26:16SAM RESUBMITTED REVISIONS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-21 Time 17:26 Rev Time 0.00
Received By jgomez Date 2018-05-16 Time 14:36 Sent To I
Notes
2018-05-17 14:36:28RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 17:15 Rev Time 0.00
Received By jgomez Date 2018-04-19 Time 13:25 Sent To  
Notes
2018-04-20 13:26:10RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-18 Cont ID  
Sent By jgomez Date 2018-04-18 Time 08:47 Rev Time 0.00
Received By jgomez Date 2018-04-13 Time 13:20 Sent To I
Notes
2018-04-16 13:20:32REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-05-21 Cont ID  
Sent By jgomez Date 2018-05-21 Time 17:26 Rev Time 0.00
Received By jgomez Date 2018-05-21 Time 16:13 Sent To  
Notes
2018-05-21 16:23:06 
  
 RESIDENTIAL (R3) REVISION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1-ORIGINAL COMMENT:
 PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE
 MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER
 471 F.S.
  
 RESPONSE:
 NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS
 FOR PUBLIC RECORDS. THIS IS NOT A DIGITAL SUBMITTAL.
 THE ORIGINAL PLANS ARE HARD COPIES.
  
 2- ORIGINAL COMMENT:
 EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED.
 NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE
 NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE TO REVISED ENERGY CALCULATIONS SUBMITTED:
 A) THE ENERGY FORM R405-2014 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER OR OWNER'S LEGALLY DESIGNATED
 AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS
 TO PROVIDE HIS NAME AND LICENSE INFORMATION AS REQUIRED
 BY BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS.
 SEC. R405.4.2.1 FBC- ENERGY CONSERVATION. NOTE: NEED TO
 HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED
 BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR
 PUBLIC RECORDS. THIS IS NOT A DIGITAL SUBMITTAL. THE
 ORIGINAL PLANS ARE HARD COPIES.
  
 C) PROVIDE CORRECT INFORMATION ON TOP OF FORM. SOHO
 BUILDERS IS NOT THE BUILDER OF THIS PROJECT. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION
  
 3- ORIGINAL COMMENT: REVISED PLAN IS MISSING THE
 EXHAUST FAN IN BATHROOM LOCATED BETWEEN BEDROOM #2 AND
 BEDROOM #3. REVISE AS REQUIRED. ORIGINAL APPROVED PLAN
 PLAN HAD THIS EXHAUST FAN SHOWN. SEC. R303.3
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-04-24 Cont ID  
Sent By jgomez Date 2018-04-24 Time 17:11 Rev Time 0.00
Received By jgomez Date 2018-04-24 Time 17:04 Sent To  
Notes
2018-04-24 17:14:0504/24/18 MET WITH SAM. HE SAID HE DIDN'T SEE THE REVIEW
 COMMENTS. THEREFORE, COMMENTS FROM FIRST REVIEW STILL
 APPLIES.
  
  
 RESIDENTIAL (R3) REVISION, SECOND MECHANICAL REVIEW
 CHECKLIST. COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE
 MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER
 471 F.S..
  
 2- EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED.
 NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE
 NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY
 CONSERVATION.
  
 3- REVISED PLAN IS MISSING THE EXHAUST FAN IN BATHROOM
 LOCATED BETWEEN BEDROOM #2 AND BEDROOM #3. REVISE AS
 REQUIRED. ORIGINAL APPROVED PLAN PLAN HAD THIS EXHAUST
 FAN SHOWN. SEC. R303.3 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By jgomez Date 2018-04-18 Time 08:47 Rev Time 0.00
Received By jgomez Date 2018-04-18 Time 07:51 Sent To  
Notes
2018-04-18 08:47:17RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014).
  
 1-PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE
 MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER
 471 F.S..
  
 2- EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED.
 NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE
 NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY
 CONSERVATION.
  
 3- REVISED PLAN IS MISSING THE EXHAUST FAN IN BATHROOM
 LOCATED BETWEEN BEDROOM #2 AND BEDROOM #3. REVISE AS
 REQUIRED. ORIGINAL APPROVED PLAN PLAN HAD THIS EXHAUST
 FAN SHOWN. SEC. R303.3 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  