| 2018-05-21 16:23:06 | |
| | |
| | RESIDENTIAL (R3) REVISION, THIRD MECHANICAL REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | 1-ORIGINAL COMMENT: |
| | PLANS NEED TO BE REVISED AND SIGNED AND SEALED BY THE |
| | MECHANICAL ENGINEER OF RECORD AS REQUIRED BY CHAPTER |
| | 471 F.S. |
| | |
| | RESPONSE: |
| | NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS. THIS IS NOT A DIGITAL SUBMITTAL. |
| | THE ORIGINAL PLANS ARE HARD COPIES. |
| | |
| | 2- ORIGINAL COMMENT: |
| | EQUIPMENT SEER AND MANUFACTURER'S MODEL WAS CHANGED. |
| | NEED TO REVISE THE ENERGY CALCULATIONS TO REFLECT THE |
| | NEW EQUIPMENT SEER. SEC. R103.4 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | RESPONSE TO REVISED ENERGY CALCULATIONS SUBMITTED: |
| | A) THE ENERGY FORM R405-2014 IS REQUIRED TO BE SIGNED |
| | AND DATED BY THE OWNER OR OWNER'S LEGALLY DESIGNATED |
| | AGENT AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B) ENGINEER OF RECORD PREPARING THE ENERGY CALCULATIONS |
| | TO PROVIDE HIS NAME AND LICENSE INFORMATION AS REQUIRED |
| | BY BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR |
| | PUBLIC RECORDS. |
| | SEC. R405.4.2.1 FBC- ENERGY CONSERVATION. NOTE: NEED TO |
| | HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED |
| | BY CHAPTER 471 F.S. WHEN SUBMITTING DOCUMENTS FOR |
| | PUBLIC RECORDS. THIS IS NOT A DIGITAL SUBMITTAL. THE |
| | ORIGINAL PLANS ARE HARD COPIES. |
| | |
| | C) PROVIDE CORRECT INFORMATION ON TOP OF FORM. SOHO |
| | BUILDERS IS NOT THE BUILDER OF THIS PROJECT. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION |
| | |
| | 3- ORIGINAL COMMENT: REVISED PLAN IS MISSING THE |
| | EXHAUST FAN IN BATHROOM LOCATED BETWEEN BEDROOM #2 AND |
| | BEDROOM #3. REVISE AS REQUIRED. ORIGINAL APPROVED PLAN |
| | PLAN HAD THIS EXHAUST FAN SHOWN. SEC. R303.3 |
| | FBC-RESIDENTIAL. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ARCHITECTS-ENGINEERS |
| | FLORIDA STATUTE 553.80(2)(B): |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| | |
| | |
| | |