| 2018-05-15 13:49:28 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE ON PLAN STATES THAT THE "EXISTING ELECTRICAL |
| | COMPLIES WITH FBC 708.3.1 NO CHANGES TO ELECTRIC ARE |
| | PROPOSED OR REQUIRED." THIS CODE SECTION DOES NOT EXIST |
| | IN THE FBC. PROVIDE CLARIFICATION. ALSO, UNDER |
| | "ENGINEERING NOTES", IT IS INDICATED THAT THE FBC |
| | RESIDENTIAL WAS USED FOR DESIGN. THE RESIDENTIAL |
| | EDITION DOES NOT APPLY TO MULTI-FAMILY DWELLING. |
| | PROVIDE CORRECTION. FBC RE R101.2; WPB FBC 107.2.1 |
| | 2. FOR DWELLING UNITS, ATTACHED GARAGES, AND DETACHED |
| | GARAGES WITH ELECTRIC POWER, AT LEAST ONE WALL |
| | SWITCH-CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED ON |
| | THE EXTERIOR SIDE OF OUTDOOR ENTRANCES/EXITS WITH GRADE |
| | LEVEL ACCESS. PROVIDE CORRECTION. NEC 210.70(A)(2)(B) |
| | 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(2) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |