Plan Review Details - Permit 18040586
Plan Review Stops For Permit 18040586
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 10:38 Rev Time 0.00
Received By shill Date 2018-05-27 Time 10:28 Sent To  
Notes
2018-05-27 10:40:55****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC R = FBC RESIDENTIAL
  
 A SHUTTER INSTALLATION SCHEDULE IS REQUIRED (SCHEDULE
 FOR INSTALLATION OF OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES); THIS FORM IS AVAILABLE IN THE BUILDING
 DIVISION LOBBY OR ON THE INTERNET:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 COMPLETE THE FORM AND SUBMIT FOR REVIEW PRIOR TO
 INSTALLATION OF SHUTTERS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 11:34 Rev Time 0.00
Received By shill Date 2018-04-28 Time 11:30 Sent To  
Notes
2018-04-28 11:43:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW SLEEPING ROOMS, FBC R
 310, FBC 107.
  
 2. REVISE THE PLAN TO INDICATE WHICH WINDOW TYPE IS
 PROPOSED IN EACH OPENING, FBC R 310, FBC 107.
  
 3. FOR THE FLAT ROOF, INDICATE WHICH APPROVED ASSEMBLY
 IS PROPOSED. IF THE ASSEMBLY DOES NOT MEET WORST CASE
 DESIGN PRESSURES, PROVIDE ENGINEERING (RAS117
 CALCULATIONS), FBC R 301.
  
 4. FOR THE FLORIDA STATE PRODUCT APPROVALS, INCLUDE THE
 COVER SHEET WHICH SHOWS THE VERSION AND STATUS OF EACH
 PRODUCT, FBC R 301.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-18 Cont ID  
Sent By jpearson Date 2018-05-18 Time 12:27 Rev Time 0.00
Received By jpearson Date 2018-05-18 Time 12:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-26 Cont ID  
Sent By jpearson Date 2018-04-26 Time 08:04 Rev Time 0.00
Received By jpearson Date 2018-04-26 Time 08:04 Sent To  
Notes
2018-04-26 08:04:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 10:41 Rev Time 0.00
Received By shill Date 2018-05-14 Time 14:34 Sent To  
Notes
2018-05-15 14:34:48RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 11:34 Rev Time 0.00
Received By shill Date 2018-04-12 Time 15:30 Sent To  
Notes
2018-04-13 15:31:08R33

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-04-20 Cont ID  
Sent By gjohnson Date 2018-04-20 Time 15:14 Rev Time 0.00
Received By gjohnson Date 2018-04-20 Time 11:01 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 10:41 Rev Time 0.00
Received By shill Date 2018-05-27 Time 10:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 11:36 Rev Time 0.00
Received By shill Date 2018-04-28 Time 11:36 Sent To  
Notes
2018-04-28 11:37:39ROOFING - SEE BUILDING REVIEW
 THIS INFORMATION IS REQUIRED AT THIS TIME BECAUSE A
 ROOF PERMIT APPLICATION WAS SUBMITTED. THIS APPLICATION
 MAY BE SUBMITTED LATER WITH THE REQUIRED INFORMATION.
  