Plan Review Details - Permit 18040558
Plan Review Stops For Permit 18040558
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-05-04 Cont ID  
Sent By shill Date 2018-05-04 Time 08:34 Rev Time 0.00
Received By shill Date 2018-05-04 Time 08:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-06 Cont ID  
Sent By jpearson Date 2018-06-06 Time 14:55 Rev Time 0.00
Received By jpearson Date 2018-06-06 Time 14:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 12:11 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 12:01 Sent To  
Notes
2018-05-02 12:11:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. DIGITAL PLAN REQUIRES
 A DIGITAL SIGNATURE. FS 471.003(2)(H); 471.025; WPB FBC
 107.2.1, 107.3.5
 2. SHOW ON PLAN ALL EXISTING RECEPTACLES IN AREAS BEING
 REMODELED. IF ANY ARE BEING REPLACED OR ADDED FOR CODE
 COMPLIANCE, PROVIDE AFCI AND GFCI PROTECTION. FBC
 107.2.1; NEC 210.8, 210.12, 406.4(D)(3)AND(4)
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-19 Cont ID  
Sent By scaldero Date 2018-04-19 Time 14:24 Rev Time 0.00
Received By scaldero Date 2018-04-19 Time 14:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-06-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-30 Time 14:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 16:37 Rev Time 0.00
Received By gjohnson Date 2018-04-17 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-06-07 Cont ID  
Sent By ccole Date 2018-06-07 Time 15:52 Rev Time 0.00
Received By ccole Date 2018-06-07 Time 15:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-08 Cont ID  
Sent By ccole Date 2018-05-08 Time 17:27 Rev Time 0.00
Received By ccole Date 2018-05-08 Time 17:27 Sent To  
Notes
2018-05-08 17:32:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040558
 5/8/2018
  
 1) NO MECHANICAL PLANS SUBMITTED. PLEASE PROVIDE A
 SCOPE OF WORK FOR MECHANICAL ALTERATIONS IF APPLICABLE.
 SHOW ALL PROPOSED ALTERATIONS TO THE EXISTING HVAC
 SYSTEM ON THE PLANS.
  
 2) CLARIFY IF A NEW RANGE OR EXHAUST HOOD WILL BE
 INSTALLED AS PART OF THE KITCHEN REMODEL AND SUBMIT
 SPECS FOR EACH IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By gjohnson Date 2018-06-07 Time 14:10 Rev Time 0.00
Received By gjohnson Date 2018-06-07 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 16:20 Rev Time 0.00
Received By gjohnson Date 2018-05-15 Time 15:43 Sent To  
Notes
2018-05-15 16:34:021ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDE FOR WATERPROOF MEMBRANE FOR SHOWER PAN SHALL
 COMPLY WITH FBC PL 417.5.2.5 OR 417.5.2.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2018-05-04 Cont ID  
Sent By shill Date 2018-05-04 Time 09:56 Rev Time 0.00
Received By shill Date 2018-05-04 Time 09:56 Sent To  
Notes
***NONE***