Plan Review Details - Permit 18040555
Plan Review Stops For Permit 18040555
Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-07-02 Cont ID  
Sent By hhall Date 2018-07-02 Time 09:59 Rev Time 0.00
Received By hhall Date 2018-07-02 Time 09:59 Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By hhall Date 2018-04-18 Time 10:26 Rev Time 0.00
Received By hhall Date 2018-04-18 Time 10:26 Sent To I
Notes
2018-04-18 10:30:47NO LOCATION SKETCH
 ADDRESS PLUMBING ISSUES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-02 Cont ID  
Sent By lmarchan Date 2018-07-02 Time 11:37 Rev Time 0.00
Received By lmarchan Date 2018-06-27 Time 13:13 Sent To  
Notes
2018-06-28 13:13:57RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-18 Cont ID  
Sent By cpuell Date 2018-04-18 Time 10:53 Rev Time 0.00
Received By cpuell Date 2018-04-12 Time 10:15 Sent To  
Notes
2018-04-13 10:15:56PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-30 Cont ID  
Sent By tklarge Date 2018-06-30 Time 05:24 Rev Time 0.00
Received By tklarge Date 2018-06-30 Time 05:05 Sent To ENG
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-18 Cont ID  
Sent By tklarge Date 2018-04-18 Time 10:11 Rev Time 0.00
Received By tklarge Date 2018-04-18 Time 09:42 Sent To ENG
Notes
2018-04-18 09:48:381) SUBMIT TWO COPIES OF GREASE INTERCEPTOR SIZING
 CALCULATIONS DONE BY SCHIER FOR REVIEW. 2017
 FBC-PLUMBING SEC. 1003.2. THE MASTER PLANS SHOWED A
 TRAPZILLA UNIT.
 2) A TWO-WAY CLEANOUT IS REQUIRED ON THE INLET TO THE
 INTERCEPTOR AND ONE ON THE OUTLET PER CITY OF WPB
 STANDARD GREASE TRAP DRAWING.THE OUTLET CLEANOUT SHALL
 BE A MINIMUM OF 4 INCHES TO BE USED AS A SAMPLING PORT
 FOR THE UTILITIES DEPT.
 3) SUBMIT TWO COMPLETE SETS OF THE SPECIFICATIONS. ALL
 PAGES SHALL BE SUBMITTED (1-7). WPB AMEND. TO FBC SEC.
 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  