Plan Review Details - Permit 18040517
Plan Review Stops For Permit 18040517
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 09:11 Rev Time 0.00
Received By cthroop Date 2018-06-14 Time 09:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 16:25 Rev Time 0.00
Received By cthroop Date 2018-05-23 Time 11:08 Sent To M
Notes
2018-05-23 16:46:10BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR PROPOSED ROOFING SYSTEM COMPONENTS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 2. CANNOT VERIFY VALUE AT THIS TIME.
 THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE OF
 WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 3. THIS PERMIT FOR STRUCTURAL ROOF REPAIR SHALL BE
 PLACED ON HOLD UNTIL APPLICATION RECIEVED FOR ROOFING
 REPAIR/REPLACEMENT. BUILDING ENVELOPE SHALL NOT BE
 OPENED PRIOR TO PLAN TO CLOSE IT UP.
  
 4. REFERENCE PLAN PAGE S1.1 FOR THE FOLLOWING -
 4A. GENERAL STRUCTURAL NOTES STATE "REFER TO
 SPECIFICATION 01010". PLEASE PROVIDE SPECIFICATION.
 4B. ROUGH CARPENTRY NOTE STATE " REFER TO SPECIFICATION
 061001". PLEASE PROVIDE SPECIFICATION.
  
 5. MECHANICAL PERMIT REQUIRED.
  
 6. REFERENCE PLAN PAGE S-1 FOR THE FOLLOWING -
 6A. PROVIDE PRODUCT APPROVAL FOR NEW MECHANICAL CURB OR
 PROVIDE SITE SPECIFIC ENGINEERING SIGNED AND SEALD BY A
 FLORIDA LICENSED PROFESSIONAL ENGINEER.
 6B. NOTES 1 AND 2 REFERENCE EL = 119.67 (UNO) AND
 108.67 (UNO) RESPECTIVELY. NO FINISHED FLOOR ELEVATION
 IS PROVIDED FOR REFERENCE. THESE STRUCTURES ARE ONLY
 THREE STORIES IN HEIGHT. PLEASE CLARIFY.
 6C. NOTE 4 REFERENCES REPLACING INSULATION PER ARCH.
 AND MECH. DRAWINGS. NO ARCH. ELEVATION DRAWINGS ARE
 PROVIDED AND NO MECH. PLAN HAS BEEN PROVIDED. PROVIDE
 DETAIL AND SPECIFICATIONS FOR PROPOSED INSULATION.
 6D. TYPICAL "SCAB RAFTER REPAIR" DETAIL REFERENCES
 EXISTING TERMITE DAMAGE TO BE SCABBED OVER. PROVIDE
 DOCUMENTATION THAT THE BUILDING HAS BEEN TREATED FOR
 TERMITES.
 6E. PROVIDE WELDER CERTIFICATIONS FOR PUDDLE WELDS AND
 ANY OTHER STRUCTURAL STEEL WELDED CONNECTIONS AT TIME
 OF INSPECTION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 16:23 Rev Time 0.00
Received By cthroop Date 2018-04-24 Time 15:54 Sent To  
Notes
2018-04-24 16:25:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE COPY OF CONTRACT SIGNED BY OWNER.
 2. PLANS ARE MARKED FOR BIDDING PURPOSES ONLY - SUBMIT
 PLANS SIGNED AND SEALED BY DESIGN PROFESSIONAL.
 3. SCOPE OF WORK TO INCLUDE WORK THAT WAS PREVIOUSLY
 DONE BY AN UNLICENSED CONTRACTOR.
  
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 09:12 Rev Time 0.00
Received By cthroop Date 2018-06-07 Time 14:15 Sent To I
Notes
2018-06-08 14:15:33RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-05-31 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-21 Time 13:56 Sent To  
Notes
2018-05-22 13:56:41RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 16:40 Rev Time 0.00
Received By cthroop Date 2018-04-12 Time 13:36 Sent To I
Notes
2018-04-17 13:37:03BLDG MISC 1

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2018-06-14 Cont ID  
Sent By ccole Date 2018-06-14 Time 08:28 Rev Time 0.00
Received By ccole Date 2018-06-14 Time 08:28 Sent To  
Notes
2018-06-14 08:29:14SEPARATE PERMIT REQUIRED FOR RTU REPLACEMENT.
 CCOLE- 6/14/18

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-31 Cont ID  
Sent By ccole Date 2018-05-31 Time 12:31 Rev Time 0.00
Received By ccole Date 2018-05-31 Time 12:31 Sent To I
Notes
2018-05-31 12:39:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040517
 5/31/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AERIAL PHOTOGRAPHS INDICATE A LARGE RTU IN THE
 SOUTHEAST CORNER OF THE COMPLEX IN THE AREA OF THE FLAT
 ROOF REPAIRS DEPICTED ON SHEET S2.0. PROVIDE A SCOPE OF
 WORK FOR MECHANICAL RELATING TO TEMPORARY REMOVAL, OR
 REPLACEMENT OF THE RTU AND THE CURB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-06-14 Cont ID  
Sent By cthroop Date 2018-06-14 Time 09:11 Rev Time 0.00
Received By cthroop Date 2018-06-14 Time 09:11 Sent To  
Notes
2018-06-14 09:11:47SEPERATE ROOFING PERMIT ON-FILE. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 16:23 Rev Time 0.00
Received By cthroop Date 2018-05-23 Time 15:01 Sent To  
Notes
2018-05-23 16:25:20BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOFING SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  