Plan Review Details - Permit 18040496
Plan Review Stops For Permit 18040496
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-09 Cont ID  
Sent By shill Date 2018-05-09 Time 09:46 Rev Time 0.00
Received By shill Date 2018-05-09 Time 09:45 Sent To  
Notes
2018-05-09 09:52:09SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROVISO
  
 PRODUCT APPROVALS WITH OPTIONS PROPOSED MARKED ARE TO
 BE SUBMITTED, REVIEWED, AND ISSUED PRIOR TO
 INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWD BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 SPEC SHEETS WERE SUBMITTED. COMPLETE PRODUCT APPROVALS,
 INCLUDING FLORIDA STATE PRODUCT APPROVAL COVER SHEET
 (WWW.FLORIDABUILDING.ORG) IF APPLICABLE, ARE REQUIRED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 15:43 Rev Time 0.00
Received By shill Date 2018-04-30 Time 15:43 Sent To  
Notes
2018-04-30 15:44:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SPECIFY DESIGN PRESSURES FOR THE GLAZING, FBC B
 1603.1.4(5).
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-09 Cont ID  
Sent By jpearson Date 2018-05-09 Time 10:16 Rev Time 0.00
Received By jpearson Date 2018-05-09 Time 10:16 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 15:38 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 14:22 Sent To  
Notes
2018-04-30 15:38:29CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NOTE ON PLAN STATES THAT ALL KITCHEN RECEPTACLE
 SHALL BE GFCI PROTECTED, ALL OTHER ROOMS TO BE AFCI
 PROTECTED. THIS IS CONTRARY TO CODE, WHICH STATES: ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 2. BLOCK NOTE LIST THE 2017 FBC RESIDENTIAL, AND THE
 2011 NEC AS BASIS FOR DESIGN. THE FBC RESIDENTIAL DOES
 NOT APPLY TO THIS PROJECT DUE TO THE FACT THAT THE
 BUILDING EXCEEDS 3 STORIES, AND THE 2011 NEC IS NOT THE
 CURRENT CODE. PROVIDE CORRECTION. FBC PREFACE, FBC RE
 R101.2
 3. THERE ARE CONFLICTING NOTES ON PLAN. ONE NOTE STATES
 THAT ALL ELECTRICAL WIRING WILL BE REMOVED, WHILE
 ANOTHER NOTE STATES THAT ALL EXISTING ELECTRICAL TO
 REMAIN AND ONLY NEW WORK IS SHOWN. PROVIDE CORRECTION.
 FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-13 Cont ID  
Sent By pleduc Date 2018-04-13 Time   Rev Time 0.00
Received By pleduc Date 2018-04-13 Time 13:47 Sent To  
Notes
2018-04-13 15:49:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF
 THE 6TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
  
  
 PLEASE NSURE COMPLIANCE AND UPDATE YOUR REFERENCES FOR
 FUTURE SUBMITTALS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-05-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-01 Time 10:10 Sent To  
Notes
2018-05-02 10:10:48B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 15:45 Rev Time 0.00
Received By shill Date 2018-04-11 Time 15:06 Sent To  
Notes
2018-04-12 15:07:09B15

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-09 Cont ID  
Sent By skennedy Date 2018-05-09 Time 09:47 Rev Time 0.00
Received By skennedy Date 2018-05-09 Time 09:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-04-26 Cont ID  
Sent By gjohnson Date 2018-04-26 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2018-04-26 Time 16:34 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved