Plan Review Details - Permit 18040474
Plan Review Stops For Permit 18040474
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By shill Date 2018-06-07 Time 14:17 Rev Time 0.00
Received By shill Date 2018-06-07 Time 14:17 Sent To  
Notes
2018-06-07 14:18:21DOOR FRAMING DETAIL REQUIRED; SUBJECT TO INSPECTOR'S
 DISCRETION, A REVISION MAY BE REQUIRED
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 16:44 Rev Time 0.00
Received By shill Date 2018-04-30 Time 16:41 Sent To  
Notes
2018-04-30 16:47:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NO INFORMATION WAS PROVIDED REGARDING LIFE SAFETY;
 TRAVEL DISTANCES, OCCUPANT LOAD, OCCUPANCY
 CLASSIFICATION, FBC CHAPTER 10.
  
 2. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A 227.1,
 904, CHECK OUT AISLES AND SALES AND SERVICE COUNTERS.
  
 3. REVISE PLAN TO SHOW COMPLIANCE WITH FBC A 226.1,
 902, BAR AREA.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By jpearson Date 2018-06-07 Time 11:09 Rev Time 0.00
Received By jpearson Date 2018-06-07 Time 11:09 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 16:04 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 16:04 Sent To  
Notes
2018-04-30 16:04:22CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. THE NEC (ON SHEET A-0 AND E-1) AND FBC (ON SHEET
 E-1) SPECIFIED FOR DESIGN IS NOT THE CURRENT CODE.
 PROVIDE CORRECTION. FBC PREFACE (ALSO SEE CURRENT CODES
 ABOVE)
 2. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By scaldero Date 2018-06-07 Time 11:05 Rev Time 0.00
Received By scaldero Date 2018-06-07 Time 11:05 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-16 Cont ID  
Sent By scaldero Date 2018-04-16 Time 13:12 Rev Time 0.00
Received By scaldero Date 2018-04-16 Time 13:05 Sent To  
Notes
2018-04-16 13:12:33PERMIT # 18040474
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL, ETC.
  
 5) PROVIDE A SITE LAYOUT INDICATING THE
 FURNITURE/SEATING TO BE USED AND PLACEMENT. MAY BE
 INCLUDED IN THE LIFE SAFETY SHEET.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 16:54 Rev Time 0.00
Received By shill Date 2018-04-11 Time 15:10 Sent To  
Notes
2018-04-13 15:10:51B21

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-04-27 Cont ID  
Sent By gjohnson Date 2018-04-27 Time 14:14 Rev Time 0.00
Received By gjohnson Date 2018-04-27 Time 14:14 Sent To  
Notes
***NONE***