Plan Review Details - Permit 18040448
Plan Review Stops For Permit 18040448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 15:16 Rev Time 0.00
Received By shill Date 2018-05-22 Time 15:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 15:00 Rev Time 0.00
Received By shill Date 2018-04-30 Time 15:00 Sent To  
Notes
2018-04-30 15:04:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THE NAME OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE INFORMATION AND DESIGN IS ILLEGIBLE, PLEASE
 PROVIDE, FBC 107.
  
 2. WINDOW DESIGN PRESSURES HAVE BEEN SPECIFIED AS PSI,
 REVISE TO PSF TO CORRELATE WITH BUILDING CODE
 REQUIREMENTS AND WITH PRODUCT APPROVALS, FBC R 301.
  
 3. THE DETAIL FOR THE NEW WINDOW OPENING IS
 INSUFFICIENT; REVISE TO INCLUDE BAR SIZE, LENGTH,
 MINIMUM EMBEDMENT INTO EXISTING, FBC R 301.
  
 4. AS THE BUILDING ENVELOPE IS AFFECTED, REVISE PLAN TO
 INCLUDE WIND DESIGN CRITERIA FBC R 301.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By jpearson Date 2018-05-22 Time 15:10 Rev Time 0.00
Received By jpearson Date 2018-05-22 Time 15:10 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 13:33 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 12:23 Sent To  
Notes
2018-04-30 13:32:59CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW, SIGNED
 (AND SEALED, IF APPLICABLE) BY THE PERSON RESPONSIBLE
 FOR THE DESIGN. INCLUDE ALL ELECTRICAL WORK. THE PLAN
 PROVIDED DOES NOT SHOW ANY ELECTRICAL FOR THE KITCHEN
 AREA THAT IS BEING RECONFIGURED. FS 471.003(2)(H);
 471.025, 481.229; WPB FBC 107.2.1, 107.3.5
 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 COMPLIANCE, A NOTE WILL SUFFICE. NEC 210.12; FBC RE
 E3902.16
 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC
 107.3.5; FBC RE E3706.2, E3902
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-22 Cont ID  
Sent By lcrespo Date 2018-05-22 Time 15:19 Rev Time 0.00
Received By lcrespo Date 2018-05-22 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 15:37 Rev Time 0.00
Received By shill Date 2018-04-10 Time 14:02 Sent To  
Notes
2018-04-30 15:26:514/30 TO C.MONTELLO DESK
  
2018-04-11 14:02:16R25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By cmontell Date 2018-04-30 Time 12:46 Rev Time 0.00
Received By cmontell Date 2018-04-30 Time 15:33 Sent To  
Notes
2018-04-30 15:34:31PER PLANS NO MECHANICAL WORK BEING DONE
 CHRIS MONTELLO
 561-805-6733

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-22 Cont ID  
Sent By lcrespo Date 2018-05-22 Time 15:19 Rev Time 0.00
Received By lcrespo Date 2018-05-22 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-27 Cont ID  
Sent By lcrespo Date 2018-04-27 Time 16:43 Rev Time 0.00
Received By lcrespo Date 2018-04-27 Time 16:43 Sent To  
Notes
2018-04-27 17:14:4204/27/18 DENIED BY PLUMBING
  
 1. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE)
 ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO
 THE FBC SEC. 107.1 GENERAL.
  
 2. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND
 SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS
 FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC
 107.2.1, 107.3.5
  
 3.THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING
 PERMITS VALUATIONS. IF IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE
 APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR
 BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO
 MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR
 PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS
 SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  