Plan Review Details - Permit 18040448
| Plan Review Stops For Permit 18040448 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-05-22 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-05-22 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-30 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-30 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2018-04-30 15:04:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. THE NAME OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | | THE INFORMATION AND DESIGN IS ILLEGIBLE, PLEASE | | | PROVIDE, FBC 107. | | | | | | 2. WINDOW DESIGN PRESSURES HAVE BEEN SPECIFIED AS PSI, | | | REVISE TO PSF TO CORRELATE WITH BUILDING CODE | | | REQUIREMENTS AND WITH PRODUCT APPROVALS, FBC R 301. | | | | | | 3. THE DETAIL FOR THE NEW WINDOW OPENING IS | | | INSUFFICIENT; REVISE TO INCLUDE BAR SIZE, LENGTH, | | | MINIMUM EMBEDMENT INTO EXISTING, FBC R 301. | | | | | | 4. AS THE BUILDING ENVELOPE IS AFFECTED, REVISE PLAN TO | | | INCLUDE WIND DESIGN CRITERIA FBC R 301. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-22 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-22 |
Time |
15:10 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-30 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-30 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2018-04-30 13:32:59 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE COMPLETE ELECTRICAL PLAN FOR REVIEW, SIGNED | | | (AND SEALED, IF APPLICABLE) BY THE PERSON RESPONSIBLE | | | FOR THE DESIGN. INCLUDE ALL ELECTRICAL WORK. THE PLAN | | | PROVIDED DOES NOT SHOW ANY ELECTRICAL FOR THE KITCHEN | | | AREA THAT IS BEING RECONFIGURED. FS 471.003(2)(H); | | | 471.025, 481.229; WPB FBC 107.2.1, 107.3.5 | | | 2. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, | | | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN | | | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, | | | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, | | | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND | | | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE | | | COMPLIANCE, A NOTE WILL SUFFICE. NEC 210.12; FBC RE | | | E3902.16 | | | 3. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF | | | EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1 | | | 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | | FBC EC R404.1 | | | 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | 6. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC | | | 107.3.5; FBC RE E3706.2, E3902 | | | 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 | | | 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP | | | CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. | | | PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE | | | E3703.4, E3901.6 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-05-22 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-05-22 |
Time |
15:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-30 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-10 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2018-04-30 15:26:51 | 4/30 TO C.MONTELLO DESK | | | | | 2018-04-11 14:02:16 | R25 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-04-30 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-04-30 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-04-30 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2018-04-30 15:34:31 | PER PLANS NO MECHANICAL WORK BEING DONE | | | CHRIS MONTELLO | | | 561-805-6733 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-05-22 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-05-22 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-05-22 |
Time |
15:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-04-27 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-04-27 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-04-27 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2018-04-27 17:14:42 | 04/27/18 DENIED BY PLUMBING | | | | | | 1. SIGNATURE (OR SEAL, OR TITLE BLOCK, OR ALL THREE) | | | ARE NOT IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.001, FLORIDA STATUTE 471. WPB AMENDMENTS TO | | | THE FBC SEC. 107.1 GENERAL. | | | | | | 2. PLANS ARE REQUIRED TO BE DESIGNED AND SIGNED AND | | | SEALED BY A LICENSED ENGINEER OR ARCHITECT. PLANS | | | FURNISHED BY AN INTERIOR DESIGNER ARE NOT ACCEPTABLE. | | | PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; FBC | | | 107.2.1, 107.3.5 | | | | | | 3.THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, PLEASE PROVIDE A BONA FIDE SIGNED | | | CONTRACT. WPB AMENDMENTS TO THE FBC 109.3. BUILDING | | | PERMITS VALUATIONS. IF IN THE OPINION OF THE BUILDING | | | OFFICIAL, THE CLAIMED VALUATION OF BUILDING, | | | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR | | | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE | | | APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE | | | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR | | | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO | | | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR | | | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS | | | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|
|
|