Plan Review Details - Permit 18040370
Plan Review Stops For Permit 18040370
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-25 Cont ID  
Sent By aclange Date 2018-04-25 Time 13:18 Rev Time 0.00
Received By aclange Date 2018-04-25 Time 12:44 Sent To  
Notes
2018-04-25 13:18:25ACTION: BUILDING PROVISO
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
  
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
  
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2. PLYWOOD FLOORING UNDERLAYMENT SHALL BE FIRE
 RETARDANT TREATED WOOD AND SHALL COMPLY WITH FBC 603.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-25 Cont ID  
Sent By jleahy Date 2018-04-25 Time 15:37 Rev Time 0.00
Received By jleahy Date 2018-04-25 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-04 Cont ID  
Sent By rgathrig Date 2018-05-04 Time 12:12 Rev Time 0.00
Received By rgathrig Date 2018-05-04 Time 12:11 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-25 Cont ID  
Sent By jleahy Date 2018-04-25 Time 15:37 Rev Time 0.00
Received By jleahy Date 2018-04-09 Time 07:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-05-04 Cont ID  
Sent By rgathrig Date 2018-05-04 Time 12:11 Rev Time 0.00
Received By rgathrig Date 2018-05-04 Time 12:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-04-25 Cont ID  
Sent By aclange Date 2018-04-25 Time 13:25 Rev Time 0.00
Received By aclange Date 2018-04-25 Time 13:25 Sent To  
Notes
2018-04-25 13:26:34****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 PAGE 208.22 A6 ARE NOT DIGITALLY SEALED.
  
 NOTE: IF YOU ARE ABLE TO GET A PRINTED COPY WITH THE
 SEALS ON IT FOR THESE PAGES, YOU COULD SUBMIT THEM TO
 ME AND I COULD HAVE THEM SCANNED TO BE WITH THIS
 PERMIT.
  
 ALTERNATIVELY YOU COULD RESUBMIT THESE PAGES DIGITALLY
 AND I COULD RESTAMP THESE PAGES.
  
 DIGITALLY CREATED SEALS: A DIGITALLY CREATED SEAL IS
 ANY SEAL CREATED AS PART OF THE DOCUMENT AND NOT
 PHYSICALLY APPLIED THAT IS AN OPAQUE PERMANENT
 REPRESENTATION THAT COMPLIES WITH SUBSECTION
 61G15-23.002(2), F.A.C.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved