| 2018-04-16 18:14:30 | COMMERCIAL INTERIOR TENANT BUILDOUT, BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 6TH EDITION (2017). |
| | |
| | 1- ADDRESS OF PROPOSED WORK IS NOT CLEAR. PERMIT |
| | APPLICATION STATES 831 VILLAGE BLVD #109. ARCHITECTURAL |
| | PLANS STATES 931 VILLAGE BLVD #109 AND CITY RECORDS |
| | (BASED ON THE PARCEL ID #) IDENTIFIES THIS BUILDING AS |
| | 731 VILLAGE BLVD #109. PLEASE COORDINATE CORRECT |
| | ADDRESS TO AVOID CONFLICT/DELAYS. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | NOTE: COORDINATE CORRECT ADDRESS WITH MICHAEL P ORIO |
| | GIS SUPPORT SPECIALIST |
| | INFORMATION TECHNOLOGY |
| | GIS |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33401 |
| | PHONE: 494-1040 EXT: 1080 |
| | FAX: 494-1117 |
| | E-MAIL: [email protected] |
| | |
| | 2- BUILDING CODE INFORMATION ON SHEET A-0.10: |
| | A) ACCORDING TO PLANS SUBMITTED THE TENANT BUILDOUT IS |
| | NOT MERCANTILE. IT LOOKS MORE LIKE BUSINESS GROUP |
| | CLASSIFICATION. SEE SEC. 304.1 FBC. IT LOOKS LIKE ALL |
| | THE INFORMATION PROVIDED IN THIS TABLE IS BASED ON |
| | MERCANTILE OCCUPANCY (ALLOWABLE AREA, BUILDING HEIGHT, |
| | OCCUPANT LOAD, ETC). REVISE ALL THE INFORMATION TO |
| | REFLECT THE CORRECT USE AND OCCUPANCY. SEC. 301.1 FBC. |
| | NOTE: THIS IS A BUILDING WITH MULTIPLE TENANTS. SEE |
| | SEC. 508.1 FBC. CLARIFY WHY THE THE OCCUPANCY |
| | SEPARATION AND TENANT SEPARATION IS N/A? |
| | |
| | B) CLARIFY/REVISE THE REQUIRED AND PROVIDED DIMENSIONS |
| | SHOWN UNDER "OTHER EGRESS COMPONENTS (0.2" PER |
| | OCCUPANT)". IT LOOKS LIKE THE REQUIREMENTS FOR |
| | STAIRWAYS SEC. 1005.3.1 FBC AND THE REQUIREMENTS FOR |
| | OTHER EGRESS COMPONENTS SEC. 1005.3.2 ARE MISMATCHED. |
| | REVISE AS REQUIRED AND PROVIDE CORRECT INFORMATION. |
| | |
| | C) CLARIFY WHERE IN THE FLOOR PLAN IS THE 36" MINIMUM |
| | CLEAR OPENING SPECIFIED UNDER THE PROVIDED COLUMN. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | D) CLARIFY WHY THE MIN. CORRIDOR WIDTH IS N/A UNDER THE |
| | PROVIDED COLUMN?. TABLE 1020.2 FBC. |
| | |
| | 3- LIFE SAFETY PLAN ON SHEET A-0.10 IS MISSING THE |
| | EMERGENCY EXIT SIGN ABOVE THE DOOR BY THE DEMONSTRATION |
| | AREA AS REQUIRED BY SEC. 1025.2.6.1 FBC |
| | |
| | 4- EGRESS IS NOT ALLOWED THROUGH STORAGE ROOMS. REVISE |
| | PROPOSED FLOOR PLAN AND LIFE SAFETY PLAN AS REQUIRED. |
| | SEE SEC. 1016.2 FBC. |
| | |
| | 5- WINDOWS AND DOORS DESIGN PRESSURES SPECIFIED ON |
| | SHEET A-4.00. SPECIFY THE BUILDING MEAN ROOF HEIGHT, |
| | BUILDING EXPOSURE, OPENING LOCATION (INTERIOR OR END). |
| | NOTE: THE DESIGN PRESSURES NEED TO BE BASED ON THE |
| | TRIBUTARY AREA OF THE WINDOW/DOORS. REVISE DESIGN |
| | PRESSURES ACCORDINGLY. SEC. 1609.6.4.4.1 FBC |
| | |
| | 6- SHEET A-4.00: |
| | A) IT LOOKS LIKE THE DOOR ON THE RESTROOM DOESN'T |
| | COMPLY WITH THE 18" MINIMUM MANEUVERING CLEARANCE |
| | REQUIRED FOR A FRONT APPROACH. REVISE FLOOR PLANS AND |
| | DETAILS AS REQUIRED. SEE SEC. 404.2.4 FBC-ACCESSIBILITY |
| | |
| | B) REVISE THE CLEAR FLOOR SPACE DIMENSIONS SHOWN ON THE |
| | ENLARGED R.R PLAN. PLANS AND ELEVATIONS SHOW A FLOOR |
| | MOUNTED WATER CLOSET. ACCORDING TO SEC. 604.8.1.1 |
| | FBC-ACCESSIBILITY FLOOR MOUNTED WATER CLOSETS REQUIRE |
| | 60 INCHES WIDE MINIMUM AND 59 INCHES DEEP MINIMUM (NOT |
| | 56") CLEAR FLOOR SPACE. |
| | |
| | C) REVISE THE DIMENSION SHOWN FOR THE MIRROR ON DETAIL |
| | "A". THE DIMENSION IS TO THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE NOT TO THE BOTTOM EDGE OF THE MIRROR |
| | FRAME. SEE SEC. 603.3 FBC ACCESSIBILITY AND REVISE AS |
| | REQUIRED. |
| | |
| | D) REVISE THE DIMENSION SHOWN FOR THE HEIGHT OF THE |
| | GRAB BARS. ACCORDING TO SEC. 609.4 ACCESSIBILITY THE |
| | DIMENSION IS MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE NOT TO THE CENTER LINE OF THE GRAB BAR. REVISE |
| | AS REQUIRED. |
| | |
| | E) REVISE DIMENSION SHOWN FOR THE TOILET PAPER |
| | DISPENSER. ACCORDING TO SEC. 604.7 FBC-ACCESSIBILITY |
| | THE DIMENSION IS MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER NOT TO THE EDGES. REVISE AS REQUIRED, |
| | INCLUDING THE DIMENSIONS FROM THE EDGE OF THE WATER |
| | CLOSET AND FROM THE FINISH FLOOR. |
| | |
| | F) DETAIL "C" IS NOT DRAWN TO SCALE. THE ROOM DOESN'T |
| | MEASURE 6'-0". REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS. |
| | |
| | B) STOREFRONT WINDOWS AS SHOWN PLANS. NOTE: IDENTIFY |
| | GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |