Plan Review Details - Permit 18040368
Plan Review Stops For Permit 18040368
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 15:07 Rev Time 0.00
Received By shill Date 2018-05-27 Time 15:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By jgomez Date 2018-04-17 Time 13:12 Rev Time 0.00
Received By jgomez Date 2018-04-16 Time 18:09 Sent To  
Notes
2018-04-16 18:14:30COMMERCIAL INTERIOR TENANT BUILDOUT, BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- ADDRESS OF PROPOSED WORK IS NOT CLEAR. PERMIT
 APPLICATION STATES 831 VILLAGE BLVD #109. ARCHITECTURAL
 PLANS STATES 931 VILLAGE BLVD #109 AND CITY RECORDS
 (BASED ON THE PARCEL ID #) IDENTIFIES THIS BUILDING AS
 731 VILLAGE BLVD #109. PLEASE COORDINATE CORRECT
 ADDRESS TO AVOID CONFLICT/DELAYS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 NOTE: COORDINATE CORRECT ADDRESS WITH MICHAEL P ORIO
 GIS SUPPORT SPECIALIST
 INFORMATION TECHNOLOGY
 GIS
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1080
 FAX: 494-1117
 E-MAIL: [email protected]
  
 2- BUILDING CODE INFORMATION ON SHEET A-0.10:
 A) ACCORDING TO PLANS SUBMITTED THE TENANT BUILDOUT IS
 NOT MERCANTILE. IT LOOKS MORE LIKE BUSINESS GROUP
 CLASSIFICATION. SEE SEC. 304.1 FBC. IT LOOKS LIKE ALL
 THE INFORMATION PROVIDED IN THIS TABLE IS BASED ON
 MERCANTILE OCCUPANCY (ALLOWABLE AREA, BUILDING HEIGHT,
 OCCUPANT LOAD, ETC). REVISE ALL THE INFORMATION TO
 REFLECT THE CORRECT USE AND OCCUPANCY. SEC. 301.1 FBC.
 NOTE: THIS IS A BUILDING WITH MULTIPLE TENANTS. SEE
 SEC. 508.1 FBC. CLARIFY WHY THE THE OCCUPANCY
 SEPARATION AND TENANT SEPARATION IS N/A?
  
 B) CLARIFY/REVISE THE REQUIRED AND PROVIDED DIMENSIONS
 SHOWN UNDER "OTHER EGRESS COMPONENTS (0.2" PER
 OCCUPANT)". IT LOOKS LIKE THE REQUIREMENTS FOR
 STAIRWAYS SEC. 1005.3.1 FBC AND THE REQUIREMENTS FOR
 OTHER EGRESS COMPONENTS SEC. 1005.3.2 ARE MISMATCHED.
 REVISE AS REQUIRED AND PROVIDE CORRECT INFORMATION.
  
 C) CLARIFY WHERE IN THE FLOOR PLAN IS THE 36" MINIMUM
 CLEAR OPENING SPECIFIED UNDER THE PROVIDED COLUMN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 D) CLARIFY WHY THE MIN. CORRIDOR WIDTH IS N/A UNDER THE
 PROVIDED COLUMN?. TABLE 1020.2 FBC.
  
 3- LIFE SAFETY PLAN ON SHEET A-0.10 IS MISSING THE
 EMERGENCY EXIT SIGN ABOVE THE DOOR BY THE DEMONSTRATION
 AREA AS REQUIRED BY SEC. 1025.2.6.1 FBC
  
 4- EGRESS IS NOT ALLOWED THROUGH STORAGE ROOMS. REVISE
 PROPOSED FLOOR PLAN AND LIFE SAFETY PLAN AS REQUIRED.
 SEE SEC. 1016.2 FBC.
  
 5- WINDOWS AND DOORS DESIGN PRESSURES SPECIFIED ON
 SHEET A-4.00. SPECIFY THE BUILDING MEAN ROOF HEIGHT,
 BUILDING EXPOSURE, OPENING LOCATION (INTERIOR OR END).
 NOTE: THE DESIGN PRESSURES NEED TO BE BASED ON THE
 TRIBUTARY AREA OF THE WINDOW/DOORS. REVISE DESIGN
 PRESSURES ACCORDINGLY. SEC. 1609.6.4.4.1 FBC
  
 6- SHEET A-4.00:
 A) IT LOOKS LIKE THE DOOR ON THE RESTROOM DOESN'T
 COMPLY WITH THE 18" MINIMUM MANEUVERING CLEARANCE
 REQUIRED FOR A FRONT APPROACH. REVISE FLOOR PLANS AND
 DETAILS AS REQUIRED. SEE SEC. 404.2.4 FBC-ACCESSIBILITY
  
 B) REVISE THE CLEAR FLOOR SPACE DIMENSIONS SHOWN ON THE
 ENLARGED R.R PLAN. PLANS AND ELEVATIONS SHOW A FLOOR
 MOUNTED WATER CLOSET. ACCORDING TO SEC. 604.8.1.1
 FBC-ACCESSIBILITY FLOOR MOUNTED WATER CLOSETS REQUIRE
 60 INCHES WIDE MINIMUM AND 59 INCHES DEEP MINIMUM (NOT
 56") CLEAR FLOOR SPACE.
  
 C) REVISE THE DIMENSION SHOWN FOR THE MIRROR ON DETAIL
 "A". THE DIMENSION IS TO THE BOTTOM EDGE OF THE
 REFLECTING SURFACE NOT TO THE BOTTOM EDGE OF THE MIRROR
 FRAME. SEE SEC. 603.3 FBC ACCESSIBILITY AND REVISE AS
 REQUIRED.
  
 D) REVISE THE DIMENSION SHOWN FOR THE HEIGHT OF THE
 GRAB BARS. ACCORDING TO SEC. 609.4 ACCESSIBILITY THE
 DIMENSION IS MEASURED TO THE TOP OF THE GRIPPING
 SURFACE NOT TO THE CENTER LINE OF THE GRAB BAR. REVISE
 AS REQUIRED.
  
 E) REVISE DIMENSION SHOWN FOR THE TOILET PAPER
 DISPENSER. ACCORDING TO SEC. 604.7 FBC-ACCESSIBILITY
 THE DIMENSION IS MEASURED TO THE CENTERLINE OF THE
 DISPENSER NOT TO THE EDGES. REVISE AS REQUIRED,
 INCLUDING THE DIMENSIONS FROM THE EDGE OF THE WATER
 CLOSET AND FROM THE FINISH FLOOR.
  
 F) DETAIL "C" IS NOT DRAWN TO SCALE. THE ROOM DOESN'T
 MEASURE 6'-0". REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) STOREFRONT WINDOWS AS SHOWN PLANS. NOTE: IDENTIFY
 GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2017
 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL
 BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURERS
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By ppetty Date 2018-05-21 Time 09:45 Rev Time 0.00
Received By ppetty Date 2018-05-21 Time 09:54 Sent To  
Notes
2018-05-21 09:53:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW OK, SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 PPETTY@WPB
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By jpearson Date 2018-04-24 Time 08:19 Rev Time 0.00
Received By jpearson Date 2018-04-24 Time 07:10 Sent To I
Notes
2018-05-21 09:50:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW OK, SEE COMMENTS BELOW.
  
 1. CORRECTED
 2. CORRECTED
 3. CORRECTED
 4. CORRECTED
 5. CORRECTED
 6. CORRECTED
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER ,CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  
2018-04-24 08:19:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND DATA
 SPECIFICATION SHEET SUBMITTALS FOR ANY OF THESE SYSTEMS
 PRESENT. WPB FBC 105.1, 107.2.1
 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS. NEC 210.62
 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. SOME AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 6. PLAN INDICATES THERE IS AN EMERGENCY LIGHT CIRCUIT.
 EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED FROM
 THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-18 Cont ID  
Sent By pleduc Date 2018-05-18 Time   Rev Time 0.00
Received By pleduc Date 2018-05-16 Time 17:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-12 Cont ID  
Sent By pleduc Date 2018-04-12 Time   Rev Time 0.00
Received By pleduc Date 2018-04-12 Time 12:50 Sent To  
Notes
2018-04-12 13:08:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-27 Cont ID  
Sent By shill Date 2018-05-27 Time 15:07 Rev Time 0.00
Received By shill Date 2018-05-10 Time 13:24 Sent To  
Notes
2018-05-14 13:24:26B34

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-09 Time 13:21 Sent To  
Notes
2018-04-10 13:22:01B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-04-18 Cont ID  
Sent By jgomez Date 2018-04-18 Time 11:25 Rev Time 0.00
Received By jgomez Date 2018-04-17 Time 07:48 Sent To  
Notes
2018-04-18 11:27:1204/18/18 TALKED TO MICHELE BONANNI. NO IMPACT FEES
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 12:44 Rev Time 0.00
Received By ccole Date 2018-05-15 Time 12:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-16 Cont ID  
Sent By ccole Date 2018-04-16 Time 11:20 Rev Time 0.00
Received By ccole Date 2018-04-16 Time 11:20 Sent To  
Notes
2018-04-16 11:23:361ST REVIEW FBC-2017 MECHANICAL , EXISTING BUILDING CODE
 PERMIT #18040368
 4/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 809.2: REFER TO SECTION 809.2 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3.1
 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES
 THE REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET M-2: PLEASE ADD THE TEXT FOR KEYED NOTE #5
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-25 Cont ID  
Sent By gjohnson Date 2018-05-25 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2018-05-25 Time 06:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-19 Cont ID  
Sent By gjohnson Date 2018-04-19 Time 15:55 Rev Time 0.00
Received By gjohnson Date 2018-04-19 Time 11:57 Sent To  
Notes
2018-04-19 15:59:011ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. TEMPERED WATER IS REQUIRED FOR THE LAVATORY. PER FBC
 PL
 607.1 WHERE REQUIRED.IN RESIDENTIAL OCCUPANCIES, HOT
 WATER SHALL BE SUPPLIED TO PLUMBING FIXTURES AND
 EQUIPMENT UTILIZED FOR BATHING, WASHING, CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE.
 IN NONRESIDENTIAL OCCUPANCIES, HOT WATER SHALL BE
 SUPPLIED FOR CULINARY PURPOSES, CLEANSING, LAUNDRY OR
 BUILDING MAINTENANCE PURPOSES. IN NONRESIDENTIAL
 OCCUPANCIES, HOT WATER OR TEMPERED WATER SHALL BE
 SUPPLIED FOR BATHING AND WASHING PURPOSES.
  
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-15 Cont ID  
Sent By eschneid Date 2018-05-15 Time 09:54 Rev Time 0.25
Received By eschneid Date 2018-05-15 Time 09:54 Sent To  
Notes
***NONE***