Plan Review Details - Permit 18040360
Plan Review Stops For Permit 18040360
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-09-24 Cont ID  
Sent By dbattles Date 2018-09-24 Time 13:35 Rev Time 0.00
Received By dbattles Date 2018-09-24 Time 13:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-25 Cont ID  
Sent By dbattles Date 2018-07-25 Time 14:13 Rev Time 0.00
Received By dbattles Date 2018-07-25 Time 09:01 Sent To  
Notes
2018-07-25 14:13:54****CORRECTIONS****
 W.P.B. PERMIT: 18040360
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC EC = FBC ENERGY CONSERVATION
  
 1. OK.
  
 2. OK.
  
 3. AS WINDOW INSTALLATION IS A SIGNIFICANT PORTION OF
 PROPOSED WORK, PROVIDE PRODUCT APPROVALS. PRODUCT
 APPROVALS TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 INSTALLATION. (SINGLE HUNG, MULLION) FBC R 301.
 3A. ADDITIONAL TO COMMENT 3 FROM INITIAL REVIEW.
 THE PRODUCT APPROVAL FOR WINDOWS IS NOT IMPACT RATED.
 PLEASE PROVIDE PRODUCT APPROVAL FOR IMPACT WINDOW, OR
 PROVIDE SHUTTER TO BE USED FOR IMPACT PROTECTION WITH
 THE EASTERN SERIES 1000.
 ALSO, THE SERIES 1000 WINDOW WILL NOT MEET PRESSURES AT
 END ZONES. PLEASE INDICATE WHICH WINDOWS ARE IN END
 ZONES.
  
 3B. [FBC R301]COMPLETE THE "SCHEDULE FOR INSTALLATION
 OF OPENING PROTECTIVE DEVICES" OR PROVIDE ALL
 INFORMATION REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL
 SPREADSHEET):
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS?PAGE=2
  
 WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE
 PAGE 13 OF 20, FACTORS APPLY DEPENDING ON SUBSTRATE,
 EDGE DISTANCE AND FASTENER. FOR FASTENER, IF USING
 TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON
 W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR).
  
 3C. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 R402.1.2.
  
 4. OK.
  
 5. [FBC R311.3} FLOORS AND LANDINGS AT EXTERIOR DOORS.
 NEW WOOD STAIRS SHOW LANDING OUTSIDE OF DOOR, BUT THE
 ELEVATIONS DON'T SHOW A LANDING. A LANDING 36" MIN. IN
 THE DIRECTION IS REQUIRED, BUT IT CAN STEP DOWN UP TO 7
 3/4" FORM TOP OF THRESHOLD.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 09:59 Rev Time 0.00
Received By shill Date 2018-04-30 Time 09:58 Sent To  
Notes
2018-04-30 10:01:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PROVIDE A DETAIL FOR THE AWNINGS, FBC R 301. PLAN
 STATES THAT THEY WILL BE REPLACED. IT APPEARS THAT THEY
 ARE STRUCTURAL AWNINGS INCLUDING FRAMING AND ROOFING.
  
 2. VALUE APPEARS LOW; PROVIDE A COST BREAKDOWN FBC 109.
  
 3. AS WINDOW INSTALLATION IS A SIGNIFICANT PORTION OF
 PROPOSED WORK, PROVIDE PRODUCT APPROVALS. PRODUCT
 APPROVALS TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 INSTALLATION. (SINGLE HUNG, MULLION) FBC R 301.
  
 4. S1 WINDOW SCHEDULE IS INCOMPLETE; REVISE TO INCLUDE
 PROPOSED WINDOWS FOR OPENINGS L, M, N.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 16:25 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-23 Cont ID  
Sent By ppetty Date 2018-07-23 Time 14:50 Rev Time 0.00
Received By ppetty Date 2018-07-23 Time 14:49 Sent To  
Notes
2018-07-23 14:49:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 7. CONTRACT PROVIDED DOES NOT LIST ELECTRICAL IN TOTAL.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 PHIL PETTY
 ELECTRICAL PLANS EXAMINER, CHIEF ELECTRICAL INSPECTOR
 561-805-6742
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-27 Cont ID  
Sent By jpearson Date 2018-04-27 Time 15:49 Rev Time 0.00
Received By jpearson Date 2018-04-27 Time 15:21 Sent To  
Notes
2018-04-27 15:49:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE CURRENT CALCULATION PROVIDED DID NOT INCLUDE
 THE 3 VA PER SQUARE FOOT. NEC 220; FBC RE E3602.2
 2. RISER DIAGRAM SHOWS #1 WIRE TO INTERIOR PANEL. THIS
 WIRE IS NOT RATED FOR 200 AMPS. PROVIDE CORRECTION. NEC
 310.15(B)(16); FBC RE E3603.1, E3705.1
 3. CURRENT NOTE FOR AFCI PROTECTION IS NOT CODE
 COMPLIANT. PER CODE: ?ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED.? PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 4. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 5. PLAN DOES NOT CLARIFY WHAT TYPE OF LIGHT FIXTURES
 ARE USED ABOVE BATH SHOWER AS THE SYMBOL USED IS NOT IN
 LEGEND. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC
 410.10(D); FBC RE E4003.11
 6. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND
 NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING.
 PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7
 7. CONTRACT PROVIDED DOES NOT LIST ELECTRICAL IN TOTAL.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-08-08 Cont ID  
Sent By lcrespo Date 2018-08-08 Time 06:45 Rev Time 0.00
Received By lcrespo Date 2018-08-08 Time 06:45 Sent To  
Notes
2018-08-08 06:46:25GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN
 PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND PLANS
 WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE. AT
 THIS TIME. WPB AMENDMENTS TO FBC SEC. 107.2.1.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By destabro Date 2018-07-10 Time 10:47 Rev Time 0.00
Received By destabro Date 2018-07-10 Time 10:42 Sent To B
Notes
2018-07-10 10:46:557/10/2018 - SOME ERRORS ON NEW PLANS W/LABELING.
 CONDITIONS FROM FIRST APPROVAL STILL APPLY. ORIGINAL
 TWO WOOD WINDOWS ON FRONT ELEVATION WILL BE RETAINED
 AND REPAIRED. SIDE SHED AWNINGS WILL BE REPLICATED
 IN-KIND WITH PECKY CYPRESS WRAP AND CLAY TILE ROOFING
 MATERIAL. REPLACEMENT WINDOWS WILL BE WHITE FRAME
 ALUMINUM AND MATCH EXISTING LIGHT DIVISIONS OR REVERT
 TO 6/1-LIGHT WITH APPLIED GRIDS. DLE

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-04-13 Cont ID  
Sent By destabro Date 2018-04-13 Time 10:38 Rev Time 0.00
Received By destabro Date 2018-04-13 Time 10:38 Sent To B
Notes
2018-04-13 10:45:484/13/2018 - APPLICANT DISCUSSED RENOVATION PLAN WITH
 HISTORIC SECTION. EXISTING GABLED AWNINGS WILL BE
 REPLACED IN-KIND WITH PECKY CYPRESS WRAP TO OUTLOOKERS.
 FRONT LIVING ROOM WINDOWS WILL BE MAINTAINED AND
 RESTORED - REMAINING WINDOWS WILL BE WHITE FRAME
 ALUMINUM IMPACT WITH APPLIED COLONIAL GRIDS. DLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-24 Cont ID  
Sent By skennedy Date 2018-09-24 Time 15:55 Rev Time 0.00
Received By skennedy Date 2018-08-28 Time 15:00 Sent To  
Notes
2018-08-29 15:02:01R04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-08 Cont ID  
Sent By lcrespo Date 2018-08-08 Time 06:20 Rev Time 0.00
Received By lcrespo Date 2018-06-27 Time 15:22 Sent To  
Notes
2018-06-28 15:22:31R26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 10:01 Rev Time 0.00
Received By shill Date 2018-04-09 Time 11:38 Sent To  
Notes
2018-04-10 11:38:17R22

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-07-17 Cont ID  
Sent By cmontell Date 2018-07-17 Time 14:45 Rev Time 0.00
Received By cmontell Date 2018-07-17 Time 14:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-25 Cont ID  
Sent By cmontell Date 2018-04-25 Time 13:33 Rev Time 0.00
Received By cmontell Date 2018-04-25 Time 13:23 Sent To  
Notes
2018-04-25 13:32:31MECHANICAL PLAN REVIEW FAIL
  
 MECHANICAL PLAN NEEDED PER 2017 FLORIDA BUILDING CODE -
 BUILDING, SIXTH EDITION SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHERE APPROVED BY THE
 BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-09-24 Cont ID  
Sent By skennedy Date 2018-09-24 Time 15:55 Rev Time 0.00
Received By skennedy Date 2018-09-24 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-08 Cont ID  
Sent By lcrespo Date 2018-08-08 Time 06:40 Rev Time 0.00
Received By lcrespo Date 2018-08-08 Time 06:19 Sent To  
Notes
2018-08-08 06:41:3908/08/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By gjohnson Date 2018-04-24 Time 13:05 Rev Time 0.00
Received By gjohnson Date 2018-04-24 Time 08:33 Sent To  
Notes
2018-04-24 13:20:41 
 1ST REVIEW: FBC 2017 6TH EDITION
 PLUMBING COMMENTS:
  
 1. WASHING MACHING IS MISSING FROM SANITARY ISOMETRIC
 IT SHALL CONNECT DOWN STREAM OF BATHROOM GROUP. PER FBC
 PL 912.1
  
 2. SHOW THE VENTS ON TOP OF THESTACK FOR THE SINKS.
 EACH FIXTURE SHALL BE VENTED. PER FBC PL 901.2.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-09-24 Cont ID  
Sent By dbattles Date 2018-09-24 Time 13:32 Rev Time 0.00
Received By dbattles Date 2018-09-24 Time 13:32 Sent To  
Notes
2018-09-24 13:35:16ROOF TILE PRODUCT APPROVAL OK, BUT NEED TO RECEIVE TILE
 ATTACHMENT AND UNDERLAYMENT.
 OWNER/BUILDER
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-10 Cont ID  
Sent By destabro Date 2018-07-10 Time 10:47 Rev Time 0.00
Received By destabro Date 2018-07-10 Time 10:46 Sent To HIST
Notes
2018-07-10 10:47:527/10/2018 - PROPOSED LOCATION FOR A/C UNIT SHALL NOT
 ENCROACH MORE THAN 2' INTO SIDE SETBACK. DLE

Review Stop Z ZONING
Rev No 1 Status P Date 2018-07-23 Cont ID  
Sent By destabro Date 2018-07-23 Time 15:41 Rev Time 0.00
Received By destabro Date 2018-07-23 Time 15:41 Sent To HIST
Notes
***NONE***