| 2018-04-17 17:17:18 | 04/17/2018 1ST PLUMBING REVISION**DENIED** |
| | |
| | 1) THE REVISED PLAN IS NO LONGER SHOWING THE STOVE AS |
| | FUTURE. ALSO THE BTU'S ARE NOW SHOWING TO BE 120,000BTU |
| | INSTEAD OF THE 90,000BTU ON THE APPROVED PLAN. YOU HAVE |
| | ALSO REMOVE THE COMBUSTION AIR CALCULATIONS.FBC-R G |
| | 2407.5 SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED |
| | GAS APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE |
| | BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM |
| | SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN |
| | ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL |
| | GAS SEC.304.9.3 OR FBCR G2407.9.3. |
| | |
| | 2) THE LOCATION OF THE TANKLESS IS NOW SHOWING AS |
| | EXTERIOR. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 3) SHOW DISCHARGE PIPING FROM STEM UNIT AS REQUIRED IN |
| | FBC-R P2804.6. SHOW DISCHARGE INTO SAME ROOM AND PAN |
| | DRAIN LINE TO EXTERIOR. FBC-R P 2801.6, 2804.6.1 |
| | |
| | 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | |