2018-04-12 12:36:54****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PROVIDE THE INSTALLATION INSTRUCTIONS FOR THE MARVIN
 DOOR FL4809.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. PROVIDE A DOOR/WINDOW SCHEDULE AND INCLUDE LOCATION,
 SIZES AND PRESSURES.
  
 PROVIDE WIND DESIGN LOADS/DESIGN PRESSURES PURSUANT TO
 FBC-R301.2.
  
 3. LABEL ROOMS AND MAKE NOTE THAT IF THERE ARE OPENING
 SIZE CHANGES IN THE BEDROOMS THEY SHALL COMPLY WITH THE
 FOLLOWING.
  
 FBC-R310.1 EMERGENCY ESCAPE - WINDOWS
  
 EMERGENCY ESCAPE AND RESCUE REQUIRED IN BEDROOM 2 AS
 FOLLOWS: WHERE EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROVIDED THEY SHALL HAVE A SILL HEIGHT OF NOT MORE THAN
 44 INCHES (1118 MM) MEASURED FROM THE FINISHED FLOOR TO
 THE BOTTOM OF THE CLEAR OPENING. R310.1.1 MINIMUM
 OPENING AREA GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET
  
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
  
 R310.1.3 MINIMUM OPENING WIDTH. THE MINIMUM NET CLEAR
 OPENING WIDTH SHALL BE 20 INCHES
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-04-11 Cont ID  
Sent By destabro Date 2018-04-11 Time 10:30 Rev Time 0.00
Received By destabro Date 2018-04-11 Time 10:30 Sent To B
Notes
2018-04-11 10:34:384/11/2018 - PROPOSED WINDOW AND DOOR REPLACEMENT
 PRODUCTS MEET DESIGN GUIDELINES OF HISTORIC DISTRICT
 AND HPB APPROVAL 17-85. HOWEVER, PLANS REFLECT THE
 CLOSING OF A SECOND FLOOR WINDOW AND THE SHORTENING OF
 THE EAST-FACING SUNROOM WINDOW AT THE SE CORNER, WHICH
 WERE NOT PREVIOUSLY APPROVED CHANGES. PLEASE REVISE
 PLANS TO THOSE SUBMITTED FOR THE JANUARY 23 (2018)
 MEETING, NOW INCLUDED WITH PERMIT. QUESTIONS MAY BE
 DIRECTED TO DESIREE ESTABROOK, HISTORIC PRESERVATION
 PLANNER AT [email protected] OR 561-822.1428.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-12 Cont ID  
Sent By aclange Date 2018-04-12 Time 12:37 Rev Time 0.00
Received By aclange Date 2018-04-06 Time 11:21 Sent To  
Notes
2018-04-10 11:21:57ROUTED TO HISTORIC INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved