Plan Review Details - Permit 18040277
Plan Review Stops For Permit 18040277
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 13:36 Rev Time 0.00
Received By cthroop Date 2018-04-24 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 08:44 Rev Time 0.00
Received By jpearson Date 2018-05-05 Time 08:44 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-23 Cont ID  
Sent By jpearson Date 2018-04-23 Time 12:47 Rev Time 0.00
Received By jpearson Date 2018-04-20 Time 08:42 Sent To B
Notes
2018-04-23 12:46:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DETAIL OF COMPLIANCE WITH NEC 240.87
 2. PROVIDE MANUFACTURERS SPEC SHEET FOR MSB-1 AND MSB-2
 AND THE GENERATOR TAP BOXES. NEC 110.3; FBC 107.2.1
 3. DUE TO THE FACT THAT THERE WERE NOT ANY SPEC SHEETS
 SUBMITTED FOR THE ELECTRICAL EQUIPMENT PROPOSED, IT IS
 NOT POSSIBLE TO DETERMINE IF REAR ACCESS FOR MSB-1 AND
 MSB-2 IS REQUIRED. IF IT IS NECESSARY TO ACCESS THE
 REAR OF THE EQUIPMENT, IT APPEARS THAT MSB-2 DOES NOT
 SHOW THE CLEARANCE REQUIRED. DEPENDING ON THE DIRECTION
 THAT MSB-1 FACES, IT MAY NOT HAVE THE REQUIRED
 CLEARANCES. PROVIDE CLARIFICATION AND/OR CORRECTION.
 NEC 110.26
 4. PARTIAL ONE LINE DIAGRAM PROVIDED IS CONFUSING AND
 HAS DISCREPANCIES. FOR MSB-1, THE FEED FROM THE
 TRANSFORMER IS SHOWN FEEDING THE BUS AHEAD OF THE MAIN
 BREAKER, WHILE FOR MSB-2, IT IS SHOWN FEEDING THE BUS
 DOWNSTREAM OF THE MAIN BREAKER. NO DETAILS ARE PROVIDED
 FOR THE FEED FROM THE TAP BOXES TO THE GENERATOR
 BREAKER. PROVIDE CLARIFICATION AND/OR CORRECTION. FBC
 107.2.1; NEC 230.70
 5. MAIN BONDING JUMPERS SHALL BE SIZED AT 12.5% OF THE
 TOTAL AREA OF SERVICE CONDUCTORS. PROVIDE CORRECTION.
 NEC 250.28(D)
 6. PROVIDE EQUIPMENT GROUNDING CONDUCTORS FOR THE
 CONDUITS FROM THE NEW MSB?S TO THE EXISTING MDP?S. NEC
 250.110, 250.118, 250.120, 250.122
 7. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 8. PROVIDE DETAILS OF HOW THE TEMPORARY POWER MENTIONED
 ON PLAN WILL BE ACCOMPLISHED. FBC 107.2.1
 9. WILL PERMANENT GENERATOR BE INSTALLED UNDER SEPARATE
 PERMIT, OR WILL A TEMPORARY GENERATOR BE USED? PROVIDE
 CLARIFICATION ON PLAN. FBC 107.2.1
 10. PLAN STATES THAT MSB?S HAVE AUTOMATIC TRANSFER
 CAPABILITY. PROVIDE DETAILS OF HOW THIS AUTOMATIC
 TRANSFER WILL BE ACCOMPLISHED. FBC 107.2.1
 11. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE AND TO CONFIRM WHAT CAPACITY IS REQUIRED
 FOR GENERATOR. NEC 215.2, 220, 408.30, 702.4(B)
 12. PROVIDE COMPLIANCE WITH NEC 702.7(C), INDICATE
 WHICH TYPE OF SYSTEM WILL BE USED IF THIS IS A PORTABLE
 GENERATOR TYPE OF INSTALLATION. NEC 702.7; FBC 107.2.1
 13. WHY IS THE GENERATOR BREAKER IN MSB-2 SIZED AT 3000
 AMPS INSTEAD OF 4000? PROVIDE CLARIFICATION. FBC
 107.2.1; NEC 230.79, 230.90
 14. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-05 Cont ID  
Sent By jpearson Date 2018-05-05 Time 08:44 Rev Time 0.00
Received By jpearson Date 2018-05-03 Time 10:09 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-24 Cont ID  
Sent By cthroop Date 2018-04-24 Time 13:36 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 11:16 Sent To I
Notes
2018-04-09 11:16:55ROUTED TO ELECTRICAL INBOX