Plan Review Details - Permit 18040253
Plan Review Stops For Permit 18040253
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By skennedy Date 2018-06-19 Time 11:42 Rev Time 0.00
Received By skennedy Date 2018-06-19 Time 11:42 Sent To FIRE
Notes
2018-06-19 11:46:211ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
  
 EXEMPT PER FBC 102.2 TEMPORARY TRAILER & BUILDING,
 SHIPPING CONTAINER, USED EXCLUSIVELY FOR CONSTRUCTION
 PURPOSES LIMITED TO SIX MONTHS IN FROM PERMIT ISSUANCE
 DATE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-28 Cont ID  
Sent By shill Date 2018-04-28 Time 10:01 Rev Time 0.00
Received By shill Date 2018-04-28 Time 10:01 Sent To  
Notes
2018-04-28 10:27:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. NO PLANS WERE SUBMITTED, ONLY A SITE PLAN.
  
 THE APPLICATION IS FOR "OFFICE RENTAL TRAILER", SITE
 PLAN SHOWS "JOB TRAILER". PLEASE SEE CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE 2017
 102.2(D), EXEMPTION TO FLORIDA BUILDING CODE
 REQUIREMENTS ARE "TEMPORARY BUILDINGS OR SHEDS USED
 EXCLUSIVELY FOR CONSTRUCTION PURPOSES." EITHER REVISE
 THE PERMIT APPLICATION WORK DESCRIPTON (BOX 5) AND THE
 SITE PLAN ACCORDINGLY, OR PROVIDE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE.
  
 2. SCOPE NOT CLEAR. THE APPLICATION APPEARS TO BE FOR
 TWO TRAILERS. THE SITE PLAN APPEARS TO SHOW MORE THAN
 TWO TRAILERS. REVISE PLAN TO CLARIFY WHICH TRAILERS ARE
 COVERED UNDER THIS APPLICATION.
  
 3. PERMIT APPLICATION LACKS AN ADDRESS. A MASTER NUMBER
 WAS PROVIDED, BUT THE MASTER REFERENCED IS FOR A
 PROJECT ON A DIFFERENT PARCEL. PROVIDE AN APPLICATION
 WHICH INCLUDES THE CORRECT ADDRESS FOR PROPOSED
 TRAILER.
  
 4. THE PROPOSED TRAILERS ARE LOCATED IN A SPECIAL FLOOD
 HAZARD AREA. TWO DIFFERENT BASE FLOOD ELEVATIONS AFFECT
 THIS PARCEL. PLANS SUBMITTED ARE TO SHOW COMPLIANCE
 WITH CITY OF WEST PALM BEACH ORDINANCE 4729-17, CITY OF
 WEST PALM BEACH MUNICIPAL CODE 18-280(B) WHICH STATES
 THAT BUILDINGS OR STRUCTURES EXEMPT FROM FLORIDA
 BUILDING CODE SHALL COMPLY WITH THIS ORDINANCE/CODE,
 WHICH REQUIRES A 2' FREEBOARD (SEC 18-34B).
  
 THIS PARCEL HAS A 6' BFE PORTION AND A 7' BFE PORTION,
 SO INCLUDING FREEBOARD ELEVATION IS TO BE 8' OR 9'
 NAVD88. REVISE PLAN TO SHOW PROPOSED ELEVATION OF
 FINISHED FLOOR. IF 8' NAVD88 IS PROPOSED, REVISE PLAN
 TO INCLUDE LOCATION OF THE FLOOD ZONE LINE. ALSO NOTE
 THAT THE FLOOD INSURANCE STUDY MAY BE UTILIZED IN LIEU
 OF THE FLOOD INSURANCE RATE MAP.
  
 5. IF THE PROPOSED TRAILERS ARE ELEVATED WITH AN
 ELEVATED SUPPORTING STRUCTURE RATHER THAN FILL, PROVIDE
 A STRUCTURAL DETAIL SHOWING COMPLIANCE WITH FBC B 1622,
 RESISTANCE TO FLOOD LOADS.
  
 6. VALUE ON THE APPLICATION SHOULD INCLUDE A REASONABLE
 VALUE - THE RENTAL FEE, INSTALLATION FEE, OR ANOTHER
 **REASONABLE** VALUATION, FBC 109. VALUE CANNOT BE $0.
  
 7. APPLICANT INDICATED THAT HE WOULD LIKE TO HAVE THE
 PROPOSED TRAILERS POWERED BY GENERATOR RATHER THAN
 ELECTRICITY AS SHOWN ON THE PLAN. PLEASE CONTACT
 [email protected] (JAKE LEAHY) TO DISCUSS THE DOCUMENTS
 REQUIRED.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-06-19 Cont ID  
Sent By skennedy Date 2018-06-19 Time 11:46 Rev Time 0.00
Received By skennedy Date 2018-06-19 Time 11:46 Sent To  
Notes
2018-06-19 11:47:29ELECTRIC WILL BE BY SEPARATE SUBMITTAL AND PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By jpearson Date 2018-04-30 Time 08:28 Rev Time 0.00
Received By jpearson Date 2018-04-30 Time 07:59 Sent To  
Notes
2018-04-30 08:28:42CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. INCLUDE RISER DIAGRAM
 OF SERVICE AND FEED TO TRAILER. INCLUDE LOAD
 CALCULATION FOR TRAILER. FS 471.003(2)(H); 471.025; WPB
 FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-06-19 Cont ID  
Sent By pleduc Date 2018-06-19 Time   Rev Time 0.00
Received By pleduc Date 2018-06-19 Time 12:56 Sent To I
Notes
2018-06-19 13:26:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS COMMENTS SUBMITTED BY FIRE WERE NOT
 ADDRESSED.
  
 1) THERE IS INSUFFICIENT DETAIL TO DETERMINE COMPLIANCE
 WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, 2013 EDITION
  
  
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS; TABLE
 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
  
 PLEASE PROVIDE A DETAILED SITE PLAN WITH EXACT
 LOCATIONS WITH SEPARATION DISTANCES FROM ALL OTHER
 PROPOSED TEMPOERY BUILDINGS/TRAILERS AND NEW
 CONSTRUCTION BUILDINGS THAT MEET THE REQUIREMENTS OF
 THE ABOVE CODE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By pleduc Date 2018-04-30 Time   Rev Time 0.00
Received By pleduc Date 2018-04-30 Time 12:07 Sent To  
Notes
2018-04-30 16:59:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PLAN WAS UNCLEAR AS TO THE LOCATION(S) OF THE
 TRAILER(S) AND COMPLAINCE WITH NFPA 241 AS NOTED BELOW:
  
  
 CONSTRUCTION TRAILERS
 PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
  
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER.
 4.2.1* SEPARATION DISTANCES BETWEEN BUILDINGS UNDER
 CONSTRUCTION AND CONSTRUCTION-RELATED STRUCTURES, SUCH
 AS TEMPORARY OFFICES, TRAILERS, SHEDS, AND OTHER
 FACILITIES FOR THE STORAGE OF TOOLS AND MATERIALS
 HAVING COMBUSTIBLE CONSTRUCTION OR CONTENTS, SHALL BE
 IN ACCORDANCE WITH TABLE 4.2.1.
  
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 NOTES:
 (1) WHERE THE SEPARATION DISTANCE BETWEEN TEMPORARY
 STRUCTURES IS LESS THAN THE MINIMUM SEPARATION
 DISTANCE, THEN THE EXPOSING WALL LENGTH SHALL BE
 CONSIDERED TO BE THE SUM OF THE INDIVIDUAL EXPOSING
 WALL LENGTHS OF THE TEMPORARY STRUCTURES.
 (2) A 75 PERCENT REDUCTION IN SEPARATION DISTANCES
 SHALL BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 (3) THE SEPARATION DISTANCES APPLY TO SINGLE-LEVEL
 STRUCTURES ONLY. THIS TABLE DOES NOT APPLY TO
 MULTILEVEL, UNSPRINKLERED STRUCTURES. A LEVEL, WHERE
 APPLYING THIS TABLE, IS 3600 MM (144 IN.).
  
 4.2.2* DETACHMENT BETWEEN TEMPORARY STRUCTURES,
 ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND
 PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION.
  
  
 PLEASE PROVIDE CLEAR INDICATIONS OF ALL PROPOSED
 CONSTRUCTION TRAILERS FOR THIS PROJECT INCLUDING
 DIMENSIONS TO ALL OTHER TRAILERS, PROPERTY LINES,
 FUTURE BUILDING WALLS AND ENDURE THESE DIMENSION COMPLY
 WITH THE ABOVE CODE OR PROVIDE FIRE SPRINKLERS FOR A
 75% REDUCTION OF SEPARATION DISTANCE.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-20 Cont ID  
Sent By cpuell Date 2018-06-20 Time 11:06 Rev Time 0.00
Received By cpuell Date 2018-06-19 Time 11:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-25 Cont ID  
Sent By lmarchan Date 2018-05-25 Time 10:29 Rev Time 0.00
Received By lmarchan Date 2018-04-06 Time 12:48 Sent To  
Notes
2018-05-25 08:49:47TO L MARCHANT.
2018-04-09 12:48:36B12

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-06-22 Cont ID  
Sent By skennedy Date 2018-06-22 Time 09:20 Rev Time 0.00
Received By skennedy Date 2018-06-22 Time 09:20 Sent To  
Notes
2018-06-22 09:23:52PLEASE PROVIDE INSTALLATION DETAILS TO DEMONSTRATE
 COMPLIANCE WITH ELEVATION OF MINIMUM FINISH FLOOR AND
 FLOOD RESISTANCE OF THE FOUNDATION. FF TO MEET MINIMUM
 RELATIVE TO NAV88. THIS MAY NOT BE REQUIRED IF IT IS
 DETERMINE TO NOT APPLY, UNDR RESEARCH.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2018-06-19 Cont ID  
Sent By skennedy Date 2018-06-19 Time 11:47 Rev Time 0.00
Received By skennedy Date 2018-06-19 Time 11:47 Sent To  
Notes
2018-06-19 11:48:52BATHROOM NOT FUNCTIONAL, OCCUPANTS TO USE WATER
 DISPENSER AND PORT-O-LETS.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-05-25 Cont ID  
Sent By AA Date 2018-05-25 Time 08:49 Rev Time 0.00
Received By aaponte Date 2018-05-25 Time 08:49 Sent To  
Notes
2018-05-25 08:49:27PROVISO: TRAILER LOCATED INSIDE CONSTRUCTION ZONE.