Plan Review Details - Permit 18040248
Plan Review Stops For Permit 18040248
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-06-30 Cont ID  
Sent By cthroop Date 2018-06-30 Time 11:32 Rev Time 0.00
Received By cthroop Date 2018-06-30 Time 11:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-09 Cont ID  
Sent By cthroop Date 2018-06-09 Time 11:23 Rev Time 0.00
Received By cthroop Date 2018-06-09 Time 11:13 Sent To E
Notes
2018-06-09 11:42:16BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DOCUMENTS WITH ENGINEER'S SIGNATURE AND SEAL MUST BE
 ORIGINAL. PAPER PLANS MAY NOT BE DIGITALY SIGNED AND
 SEALED.
 PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE,
 DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE
 61G15-23.001.
  
 2. PROVIDE SITE PLAN. IDENTIFY LOCATION OF PROPOSED BBG
 GRILL.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
  
 3. PROVIDE STRUCTURAL PLANS. INCLUDE FOUNDATION PLAN
 AND WALL SECTION PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4. PROVIDE COMPLETE OWNERS MANUAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-13 Cont ID  
Sent By aclange Date 2018-04-13 Time 12:41 Rev Time 0.00
Received By aclange Date 2018-04-13 Time 12:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2018-06-28 Cont ID  
Sent By jleahy Date 2018-06-28 Time 08:17 Rev Time 0.00
Received By jleahy Date 2018-06-28 Time 08:17 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-06-13 Cont ID  
Sent By jleahy Date 2018-06-13 Time 14:32 Rev Time 0.00
Received By jleahy Date 2018-06-13 Time 14:32 Sent To I
Notes
2018-06-13 14:34:11NO ELECTRIC SHOWN JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2018-04-13 Cont ID  
Sent By aclange Date 2018-04-13 Time 12:41 Rev Time 0.00
Received By aclange Date 2018-04-13 Time 12:41 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-06-29 Cont ID  
Sent By thunt Date 2018-06-29 Time 15:02 Rev Time 0.00
Received By thunt Date 2018-06-29 Time 15:02 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-06-04 Cont ID  
Sent By thunt Date 2018-06-04 Time 15:46 Rev Time 0.00
Received By thunt Date 2018-06-04 Time 15:46 Sent To  
Notes
2018-06-04 15:54:3806/03/2018 3RD GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLAN REVIEW IS SUBJECT TO A 4XFEE IF PLANS REVIEW IS
 DENIED FOR THE SAME COMMENTS AFTER THE 3RD REVIEW PER
 FL ST. STAUTE 553.80 (2B)
  
 I HAVE PERFORMED A SITE INSPECTION. THERE IS NO
 PER-EXISTING GAS LINE FOR THE BBQ AS YOU HAVE TOLD ME
 AND AS IN PLAN. THERE IS ALMOST 1 MILLION BTU'S OF GAS
 ON THIS HOME AND YOU WILL NEED TO ADDRESS IN FULL ALL
 OF THE COMMENT'S. IF YOU REQUIRED ASSISTANCE I WOULD BE
 WILLING TO MEET YOU ON-SITE TO HELP SIZE AND LIST
 EVERYTHING.
  
  
 1) PLANS ARE REQUIRED TO HAVE A WET SIGNATURE BY
 ENGINEER. DIGITALLY SIGNED PLANS ARE ONLY PERMITTED ON
 PLANS THAT HAVE BEEN SUBMITTED DIGITALLY. FLORIDA ADMIN
 CODE 61G15-23.001. THE PLAN IS STILL STAMPED DIGITALLY.
  
 2) ANSWERED
  
 3) THE VALUE OF THIS JOB SEEMS LOW. PROVIDE A BONA FIDE
 SIGN CONTRACT TO VERIFY THE TOTAL VALVE, WPB AMEND TO
 THE FBC 109.3. YOU MUST WRITE THE TOTAL DIFFERENCE IN
 VALUE THAT THE CONTRACT YOU PROVIDED SHOWS.
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21). THIS IS NOT THE ONLY
 GAS ON THIS SYSTEM. THERE IS ALMOST 1 MILLION BTU'S
 EXISTING ON THIS HOUSE. THE SPEC'S PROVIDE FOR THIS
 REVIEW LIST THE BBQ AS 60K BUT THE GAS ISOMETRIC ONLY
 LIST IT AS 40K
  
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THIS GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. WHAT
 YOU PROVIDED DOES NOT LIST ANY APPROVALS
  
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3. YOU SUBMITTED 2 DIFFERENT
 SIZING CHART. WHAT PRESSURE DROP ARE YOU USING AND LIST
 WHAT CODE BOOK THIS IS FROM. ALSO YOU WILL NEED TO
 INCLUDE THE 2 PSI SIZING CHARTS FOR THE DIFFERENT PIPIE
 MATERIAL BEING USED.
  
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 10) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 13) ANSWERED
  
 14) ANSWERED
  
 .
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-25 Cont ID  
Sent By thunt Date 2018-05-25 Time 14:02 Rev Time 0.00
Received By thunt Date 2018-05-25 Time 14:02 Sent To  
Notes
2018-05-25 14:04:1804/12/2018 2ND GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLAN REVIEW IS SUBJECT TO A 4XFEE IF PLANS REVIEW IS
 DENIED FOR THE SAME COMMENTS AFTER THE 3RD REVIEW PER
 FL ST. STAUTE 553.80 (2B)
  
  
 1) PLANS ARE REQUIRED TO HAVE A WET SIGNATURE BY
 ENGINEER. DIGITALLY SIGNED PLANS ARE ONLY PERMITTED ON
 PLANS THAT HAVE BEEN SUBMITTED DIGITALLY. FLORIDA ADMIN
 CODE 61G15-23.001
  
 2) ANSWERED
  
 3) THE VALUE OF THIS JOB SEEMS LOW. PROVIDE A BONA FIDE
 SIGN CONTRACT TO VERIFY THE TOTAL VALVE, WPB AMEND TO
 THE FBC 109.3
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THIS GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3
  
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 10) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 11) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 13) YOU HAVE NOT INCLUDED THE HOOD VENT DOCUMENTATION
 IN THIS PACKET. SUBMIT DRAWNINGS AND MANUFACTURE SPEC
 FOR THE HOOD VENT SYSTEM AS REQUIRED IN FBC- FUEL AND
 GAS 623.5
  
 14) TO THE LEFT OF THE BBQ IS WHAT LOOKS TO BE A
 SMOKER. WILL THIS ALSO BE CONNECTED INTO THE NATURAL
 GAS SYSTEM? WHAT FUEL IS TO BE USED? FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-04-12 Cont ID  
Sent By thunt Date 2018-04-12 Time 17:46 Rev Time 0.00
Received By thunt Date 2018-04-12 Time 17:46 Sent To  
Notes
2018-04-12 18:22:3504/12/2018 1ST GAS REVIEW **DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1) PLANS ARE REQUIRED TO HAVE A WET SIGNATURE BY
 ENGINEER. DIGITALLY SIGNED PLANS ARE ONLY PERMITTED ON
 PLANS THAT HAVE BEEN SUBMITTED DIGITALLY. FLORIDA ADMIN
 CODE 61G15-23.001
  
 2) YOU WILL NEED A SUB GAS PERMIT APPLICATION SUBMITTED
 BY A LICENSE CONTRACTOR THAT GAS FALLS WITH IN THEIR
 SCOPE OF WORK. FBC 105.1
  
 3) THE VALUE OF THIS JOB SEEMS LOW. PROVIDE A BONA FIDE
 SIGN CONTRACT TO VERIFY THE TOTAL VALVE, WPB AMEND TO
 THE FBC 109.3
  
 4) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
  
 5) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1
  
 6) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 7) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR THIS GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1
  
 8) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3
  
 9) SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2017 FBC-FUEL GAS
 SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4.
  
 10) ) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3.
  
 11) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 12) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE
 APPLIANCE. COMPLY WITH 2017 FBC-FUEL GAS SEC. 402.4.1
 OR 2017 FBC-RES. SEC. G2413.4.1, G2413.4.2 FOR THE
 PROPER PIPE SIZE AND BTU LOAD.
  
 13) YOU HAVE NOT INCLUDED THE HOOD VENT DOCUMENTATION
 IN THIS PACKET. SUBMIT DRAWNINGS AND MANUFACTURE SPEC
 FOR THE HOOD VENT SYSTEM AS REQUIRED IN FBC- FUEL AND
 GAS 623.5
  
 14) TO THE LEFT OF THE BBQ IS WHAT LOOKS TO BE A
 SMOKER. WILL THIS ALSO BE CONNECTED INTO THE NATURAL
 GAS SYSTEM? WHAT FUEL IS TO BE USED? FBC 107.2.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 561-805-6695
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 09:16 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 09:16 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-04-10 Cont ID  
Sent By fmittner Date 2018-04-10 Time 10:52 Rev Time 0.00
Received By fmittner Date 2018-04-10 Time 10:52 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-06-30 Cont ID  
Sent By cthroop Date 2018-06-30 Time 11:32 Rev Time 0.00
Received By cthroop Date 2018-06-19 Time 14:09 Sent To I
Notes
2018-06-20 14:10:07RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-13 Cont ID  
Sent By jleahy Date 2018-06-13 Time 14:34 Rev Time 0.00
Received By jleahy Date 2018-05-31 Time 13:00 Sent To  
Notes
2018-06-01 13:01:05RESUB ROUTED TO THUNT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-25 Cont ID  
Sent By thunt Date 2018-05-25 Time 14:09 Rev Time 0.00
Received By thunt Date 2018-05-14 Time 13:19 Sent To I
Notes
2018-05-15 13:19:21RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-13 Cont ID  
Sent By aclange Date 2018-04-13 Time 12:41 Rev Time 0.00
Received By aclange Date 2018-04-05 Time 12:37 Sent To  
Notes
2018-04-06 12:37:44ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-23 Cont ID  
Sent By fmittner Date 2018-05-23 Time 09:16 Rev Time 0.00
Received By fmittner Date 2018-05-23 Time 09:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-10 Cont ID  
Sent By fmittner Date 2018-04-10 Time 10:52 Rev Time 0.00
Received By fmittner Date 2018-04-10 Time 10:52 Sent To  
Notes
***NONE***