Plan Review Details - Permit 18040245
Plan Review Stops For Permit 18040245
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-03-26 Cont ID  
Sent By jduprey Date 2019-03-26 Time 15:33 Rev Time 0.00
Received By jduprey Date 2019-03-26 Time 15:06 Sent To  
Notes
2019-03-26 15:43:36BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY E.I., BN, PX
 BUILDING PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. SEE COMMENTS FROM PREVIOUS LIST. A DETAIL SHOWING
 HEIGHT OF THE AWNING WAS PROVIDED. HOWEVER THE AWNING
 EXTEND MORE THAN 5 FEET OVER PUBLIC PROPERTY. PROVIDE
 DEPTH AND HEIGHT MEASUREMENTS. FBC 3105.3.1.4 MOVABLE
 FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY EXTEND OVER
 PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE THAN 5 FEET
 (1524 MM), PROVIDED SUCH AWNINGS OR ANY PART THEREOF
 MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438 MM) ABOVE THE
 SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL BE SUPPORTED
 ON METAL FRAMES ATTACHED TO THE BUILDING.
  
 2. 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA. FBC
 3105.3.4.1 FABRIC USED FOR AWNINGS OR FABRIC-COVERED
 FRAMES SHALL MEET THE FLAME PROPAGATION PERFORMANCE
 CRITERIA OF NFPA 701 OR HAVE A FLAME SPREAD INDEX NOT
 GREATER THAN 25 WHEN TESTED IN ACCORDANCE WITH ASTM E84
 OR UL 723.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 12:14 Rev Time 0.00
Received By shill Date 2018-09-02 Time 12:14 Sent To  
Notes
2018-09-02 12:14:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 SEE COMMENTS FROM PREVIOUS LIST. A SITE PLAN SHOWING
 LOCATION OF THE AWNING RELATIVE TO THE SIDEWALK AND
 PROPERTY LINE WAS NOT PROVIDED. A DETAIL SHOWING HEIGHT
 OF THE AWNING WAS NOT PROVIDED. NOT ENOUGH INFORMATION
 PROVIDED TO DETERMINE CODE COMPLIANCE.
  
  
 1. RETRACTABLE AWNING.
  
 FBC 3105.3 DESIGN AND CONSTRUCTION.
  
 AWNINGS AND CANOPIES SHALL BE DESIGNED AND CONSTRUCTED
 TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS
 AS REQUIRED BY CHAPTER 16 AND IN ACCORDANCE WITH
 SECTION 3105.4 OF THIS CODE WITH DUE ALLOWANCE FOR
 SHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT
 RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS
 SHALL BE PROTECTED TO PREVENT DETERIORATION. AWNINGS
 SHALL HAVE FRAMES OF NONCOMBUSTIBLE MATERIAL,
 FIRE-RETARDANT-TREATED WOOD, WOOD OF TYPE IV SIZE, OR
 1-HOUR CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE
 COVERS AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING
 OR COLLAPSIBLE.
  
 2. AWNING HEIGHT
  
 PROVIDE DEPTH AND HEIGHT MEASUREMENTS.
 FBC 3105.3.1.4
  
 MOVABLE FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY
 EXTEND OVER PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE
 THAN 5 FEET (1524 MM), PROVIDED SUCH AWNINGS OR ANY
 PART THEREOF MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438
 MM) ABOVE THE SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL
 BE SUPPORTED ON METAL FRAMES ATTACHED TO THE BUILDING.
  
 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA.
 FBC 3105.3.4.1
  
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25
 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-06-27 Cont ID  
Sent By shill Date 2018-06-27 Time 18:15 Rev Time 0.00
Received By shill Date 2018-06-27 Time 18:09 Sent To  
Notes
2018-06-27 18:15:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 SEE COMMENTS FROM PREVIOUS LIST. A SITE PLAN SHOWING
 LOCATION OF THE AWNING RELATIVE TO THE SIDEWALK AND
 PROPERTY LINE WAS NOT PROVIDED. A DETAIL SHOWING HEIGHT
 OF THE AWNING WAS NOT PROVIDED. NOT ENOUGH INFORMATION
 PROVIDED TO DETERMINE CODE COMPLIANCE.
  
  
 1. RETRACTABLE AWNING.
  
 FBC 3105.3 DESIGN AND CONSTRUCTION.
  
 AWNINGS AND CANOPIES SHALL BE DESIGNED AND CONSTRUCTED
 TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS
 AS REQUIRED BY CHAPTER 16 AND IN ACCORDANCE WITH
 SECTION 3105.4 OF THIS CODE WITH DUE ALLOWANCE FOR
 SHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT
 RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS
 SHALL BE PROTECTED TO PREVENT DETERIORATION. AWNINGS
 SHALL HAVE FRAMES OF NONCOMBUSTIBLE MATERIAL,
 FIRE-RETARDANT-TREATED WOOD, WOOD OF TYPE IV SIZE, OR
 1-HOUR CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE
 COVERS AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING
 OR COLLAPSIBLE.
  
 2. AWNING HEIGHT
  
 PROVIDE DEPTH AND HEIGHT MEASUREMENTS.
 FBC 3105.3.1.4
  
 MOVABLE FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY
 EXTEND OVER PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE
 THAN 5 FEET (1524 MM), PROVIDED SUCH AWNINGS OR ANY
 PART THEREOF MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438
 MM) ABOVE THE SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL
 BE SUPPORTED ON METAL FRAMES ATTACHED TO THE BUILDING.
  
 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA.
 FBC 3105.3.4.1
  
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25
 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-12 Cont ID  
Sent By aclange Date 2018-04-12 Time 10:46 Rev Time 0.00
Received By aclange Date 2018-04-12 Time 10:44 Sent To  
Notes
2018-04-12 10:46:21 
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. RETRACTABLE AWNING.
  
 FBC 3105.3 DESIGN AND CONSTRUCTION.
  
 AWNINGS AND CANOPIES SHALL BE DESIGNED AND CONSTRUCTED
 TO WITHSTAND WIND OR OTHER LATERAL LOADS AND LIVE LOADS
 AS REQUIRED BY CHAPTER 16 AND IN ACCORDANCE WITH
 SECTION 3105.4 OF THIS CODE WITH DUE ALLOWANCE FOR
 SHAPE, OPEN CONSTRUCTION AND SIMILAR FEATURES THAT
 RELIEVE THE PRESSURES OR LOADS. STRUCTURAL MEMBERS
 SHALL BE PROTECTED TO PREVENT DETERIORATION. AWNINGS
 SHALL HAVE FRAMES OF NONCOMBUSTIBLE MATERIAL,
 FIRE-RETARDANT-TREATED WOOD, WOOD OF TYPE IV SIZE, OR
 1-HOUR CONSTRUCTION WITH COMBUSTIBLE OR NONCOMBUSTIBLE
 COVERS AND SHALL BE EITHER FIXED, RETRACTABLE, FOLDING
 OR COLLAPSIBLE.
  
 2. AWNING HEIGHT
  
 PROVIDE DEPTH AND HEIGHT MEASUREMENTS.
 FBC 3105.3.1.4
  
 MOVABLE FABRIC AWNINGS OR FABRIC COVERED FRAMES MAY
 EXTEND OVER PUBLIC PROPERTY FOR A DISTANCE OF NOT MORE
 THAN 5 FEET (1524 MM), PROVIDED SUCH AWNINGS OR ANY
 PART THEREOF MAINTAIN A CLEAR HEIGHT OF 8 FEET (2438
 MM) ABOVE THE SIDEWALK. ALL SUCH MOVABLE AWNINGS SHALL
 BE SUPPORTED ON METAL FRAMES ATTACHED TO THE BUILDING.
  
 3. PROVIDE AWNINGS FABRIC FLAME SPREAD CRITERA.
 FBC 3105.3.4.1
  
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA
 701 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25
 WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-26 Cont ID  
Sent By jduprey Date 2019-03-26 Time 15:43 Rev Time 0.00
Received By jduprey Date 2019-02-11 Time 09:44 Sent To  
Notes
2019-02-12 09:44:31RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 12:14 Rev Time 0.00
Received By shill Date 2018-08-10 Time 14:11 Sent To  
Notes
2018-08-13 14:11:49RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-27 Cont ID  
Sent By shill Date 2018-06-27 Time 18:15 Rev Time 0.00
Received By shill Date 2018-06-11 Time 14:11 Sent To  
Notes
2018-06-27 12:09:396/27 TO SH DESK
  
2018-06-12 14:11:27RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-12 Cont ID  
Sent By aclange Date 2018-04-12 Time 10:46 Rev Time 0.00
Received By aclange Date 2018-04-05 Time 12:38 Sent To  
Notes
2018-04-06 12:38:48ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 4 Status F Date 2019-03-20 Cont ID  
Sent By eschneid Date 2019-03-20 Time 15:27 Rev Time 0.25
Received By eschneid Date 2019-03-20 Time 15:27 Sent To B
Notes
2019-03-20 15:27:26FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS SHALL PROVIDE A MINIMUM OF EIGHT
 (8) FEET OF CLEARANCE BETWEEN THE FLOOR AND THE LOWEST
 POINT OF THE AWNING. THE PERMIT DOES NOT INCLUDE THE
 CLEARANCE OF THE LOWEST POINT OF THE AWNING. THIS NEEDS
 TO BE SHOWN AT THE FULL EXTENSION OF 11 FEET SO THAT
 STAFF CAN VERIFY ADEQUATE CLEARANCE IN THE EVENT THAT
 THE AWING IS FULLY EXTENDED.
  
 2) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS ON THE STREET LEVEL SHALL PROJECT
 FOUR (4) FEET FROM THE BUILDING FACADE, UNLESS
 OTHERWISE APPROVED BY CITYPLACE RETAIL IN WRITING. THE
 AWNINGS ARE LISTED AS PROJECTING EITHER SIX (6) OR
 SEVEN (7) FEET FROM THE BUILDING FA?ADE, DEPENDING ON
 WHICH PLAN IS USED. NO WRITTEN APPROVAL FROM CITYPLACE
 RETAIL IS PROVIDED. THIS IS REQUIRED TO BE LETTER ON
 CITYPLACE LETTER HEAD.
  
 3) NEW COMMENT: THE NEW SURVEY PROVIDED WITH THE PERMIT
 SHOWS THE AWNINGS PROJECTING SIX (6) FEET FROM THE
 BUILDING FACADE. THE ENGINEERING PLANS SHOW THE AWNING
 PROJECTING UP TO SEVEN (7) FEET FROM THE BUILDING
 FACADE. ALL SUBMITTED PLANS, SURVEYS, ETC. MUST SHOW
 THE SAME CONDITIONS.
  
 4) NEW COMMENT: HOW WILL YOU ENSURE THAT THE AWNING
 WILL ONLY BE EXTENDED TO THE MAXIMUM RECOMMENDED
 PROJECTION OF SEVEN (7) FEET INSTEAD OF THE POSSIBLE
 MAXIMUM OF 11 FEET? THE SURVEY SHOWS THAT THE FULL
 PROJECTION WILL ENCROACH OVER THE PUBLIC SIDEWALK WITH
 NO APPROVAL TO DO SO.
  
 5) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT ALL AWNINGS ON STREET LEVEL MUST HAVE AN
 EIGHT (8) INCH VERTICAL VALANCE ALONG THE FRONT OF THE
 AWNING. THE VALANCE MUST BE PROVIDED WITH CONCEALED
 WEIGHT TO PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. NO
 INFORMATION IS PROVIDED REGARDING THE VALANCE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 2018-08-31 Cont ID  
Sent By eschneid Date 2018-08-31 Time 09:51 Rev Time 0.25
Received By eschneid Date 2018-08-31 Time 09:24 Sent To B
Notes
2018-08-31 09:34:57FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) REPEAT COMMENT: PROVIDE TWO COPIES OF A RECENT
 SURVEY SHOWING THE DIMENSIONS OF THE AWNING AND ITS
 PROJECTION IN RELATIONSHIP TO THE PROPERTY LINE. IF THE
 AWNING PROJECTS OVER THE RIGHT-OF-WAY, THEN PRIOR TO
 ZONING APPROVAL OF THIS PERMIT, YOU MUST HAVE APPROVAL
 FROM THE ENGINEERING SERVICES DIVISION PERMITTING THE
 ENCROACHMENT OVER THE RIGHT-OF-WAY. THE IRRIGATION PLAN
 FROM 1999 DOES NOT QUALIFY TO MEET THIS COMMENT.
  
 2) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS SHALL PROVIDE A MINIMUM OF EIGHT
 (8) FEET OF CLEARANCE BETWEEN THE FLOOR AND THE LOWEST
 POINT OF THE AWNING. THE PERMIT DOES NOT INCLUDE THE
 CLEARANCE OF THE LOWEST POINT OF THE AWNING.
  
 3) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS ON THE STREET LEVEL SHALL PROJECT
 FOUR (4) FEET FROM THE BUILDING FACADE, UNLESS
 OTHERWISE APPROVED BY CITYPLACE RETAIL IN WRITING. THE
 AWNINGS ARE LISTED AS PROJECTING 7 FEET FROM THE
 BUILDING FACADE. NO WRITTEN APPROVAL FROM CITYPLACE
 RETAIL IS PROVIDED. THIS IS REQUIRED TO BE LETTER ON
 CITYPLACE LETTER HEAD.
  
 4) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT ALL AWNINGS ON STREET LEVEL MUST HAVE AN
 EIGHT (8) INCH VERTICAL VALANCE ALONG THE FRONT OF THE
 AWNING. THE VALANCE MUST BE PROVIDED WITH CONCEALED
 WEIGHT TO PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. NO
 INFORMATION IS PROVIDED REGARDING THE VALANCE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-06-27 Cont ID  
Sent By eschneid Date 2018-06-27 Time 10:37 Rev Time 0.25
Received By eschneid Date 2018-06-27 Time 10:37 Sent To B
Notes
2018-06-27 11:00:42FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) REPEAT COMMENT: PROVIDE TWO COPIES OF A RECENT
 SURVEY SHOWING THE DIMENSIONS OF THE AWNING AND ITS
 PROJECTION IN RELATIONSHIP TO THE PROPERTY LINE. IF THE
 AWNING PROJECTS OVER THE RIGHT-OF-WAY, THEN PRIOR TO
 ZONING APPROVAL OF THIS PERMIT, YOU MUST HAVE APPROVAL
 FROM THE ENGINEERING SERVICES DIVISION PERMITTING THE
 ENCROACHMENT OVER THE RIGHT-OF-WAY.
  
 2) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT THE AWNING COLORS, COPY AND/OR LOGO SHALL
 BE APPROVED BY CITYPLACE RETAIL IN WRITING. NO WRITTEN
 APPROVAL FROM CITYPLACE RETAIL IS PROVIDED.
  
 3) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS SHALL PROVIDE A MINIMUM OF EIGHT
 (8) FEET OF CLEARANCE BETWEEN THE FLOOR AND THE LOWEST
 POINT OF THE AWNING. THE PERMIT DOES NOT INCLUDE THE
 CLEARANCE OF THE LOWEST POINT OF THE AWNING.
  
 4) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT AWNINGS ON THE STREET LEVEL SHALL PROJECT
 FOUR (4) FEET FROM THE BUILDING FACADE, UNLESS
 OTHERWISE APPROVED BY CITYPLACE RETAIL IN WRITING. THE
 AWNINGS ARE LISTED AS PROJECTING 7 FEET FROM THE
 BUILDING FACADE. NO WRITTEN APPROVAL FROM CITYPLACE
 RETAIL IS PROVIDED.
  
 5) REPEAT COMMENT: THE CITYPLACE MASTER SIGN PLAN
 REQUIRES THAT ALL AWNINGS ON STREET LEVEL MUST HAVE AN
 EIGHT (8) INCH VERTICAL VALANCE ALONG THE FRONT OF THE
 AWNING. THE VALANCE MUST BE PROVIDED WITH CONCEALED
 WEIGHT TO PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. NO
 INFORMATION IS PROVIDED REGARDING THE VALANCE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-11 Cont ID  
Sent By eschneid Date 2018-04-11 Time 11:45 Rev Time 0.50
Received By eschneid Date 2018-04-11 Time 11:45 Sent To B
Notes
2018-04-11 11:48:12FAILED
  
 PROVIDE RESPONSES IN WRITING.
  
 1) PROVIDE TWO COPIES OF A RECENT SURVEY SHOWING THE
 DIMENSIONS OF THE AWNING AND ITS PROJECTION IN
 RELATIONSHIP TO THE PROPERTY LINE. IF THE AWNING
 PROJECTS OVER THE RIGHT-OF-WAY, THEN PRIOR TO ZONING
 APPROVAL OF THIS PERMIT, YOU MUST HAVE APPROVAL FROM
 THE ENGINEERING SERVICES DIVISION PERMITTING THE
 ENCROACHMENT OVER THE RIGHT-OF-WAY.
  
 2) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE PLANS.
  
 3) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT THE
 AWNING COLORS, COPY AND/OR LOGO SHALL BE APPROVED BY
 CITYPLACE RETAIL IN WRITING.
  
 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 SHALL PROVIDE A MINIMUM OF EIGHT (8) FEET OF CLEARANCE
 BETWEEN THE FLOOR AND THE LOWEST POINT OF THE AWNING.
 THE PERMIT DID NOT INCLUDE THE CLEARANCE OF THE LOWEST
 POINT OF THE AWNING.
  
 5) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 ON THE STREET LEVEL SHALL PROJECT FOUR (4) FEET FROM
 THE BUILDING FACADE, UNLESS OTHERWISE APPROVED BY
 CITYPLACE RETAIL IN WRITING. THE AWNINGS ARE LISTED AS
 PROJECTING 11 FEET FROM THE BUILDING FACADE.
  
 6) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT ALL
 AWNINGS ON STREET LEVEL MUST HAVE AN EIGHT (8) INCH
 VERTICAL VALANCE ALONG THE FRONT OF THE AWNING. THE
 VALANCE MUST BE PROVIDED WITH CONCEALED WEIGHT TO
 PREVENT EXCESSIVE MOVEMENT IN HIGH WINDS. NO
 INFORMATION IS PROVIDED REGARDING THE VALANCE.
  
 8) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT AWNINGS
 SHALL BE A SUNBRELLA 100% SOLUTION DYED ACRYLIC OR
 SUNBRELLA FIRESIST 100% SOLUTION DYED MODACRYLIC
 MATERIAL (OR EQUIVALENT APPROVED BY CITYPLACE RETAIL IN
 WRITING). NO INFORMATION PROVIDED REGARDING THE AWNING
 MATERIAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  