Plan Review Details - Permit 18040194
Plan Review Stops For Permit 18040194
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By cthroop Date 2018-10-25 Time 13:24 Rev Time 0.00
Received By cthroop Date 2018-10-25 Time 08:17 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-12 Cont ID  
Sent By cthroop Date 2018-07-12 Time 17:07 Rev Time 0.00
Received By cthroop Date 2018-07-09 Time 12:05 Sent To  
Notes
2018-07-12 17:15:36BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OCCUPANCY CLASSIFICATION IS R-2. CORRECT PLAN PAGES
 CS AND S-3.
  
 2. PROVIDE LIFE SAFETY PLAN. SHOW PATH OF TRAVEL TO
 PUBLIC WAY. PROVIDE EXIT AND EMERGENCY LIGHTING.
  
 3. STATE INSULATION R VALUES FROM ENERGY SUBMITTAL ON
 PLANS.
  
 4. PROVIDE SOILS REPORT.
 FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE
 CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE
 REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL
 INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY
 TESTING OR ENGINEERING CALCULATIONS, SUCH
 INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED
 DESIGN PROFESSIONAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 11:25 Rev Time 0.00
Received By cthroop Date 2018-04-25 Time 07:32 Sent To  
Notes
2018-05-01 11:33:27BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. DESIGN IS FOR A FULLY SPRINKLERED BUILDING. PROVIDE
 SPRINKLER SYSTEM DESIGN.
 2. VALUE WAS ADJUSTED FROM $363479 APPLIED TO $383274
 CALCULATED PER ICC BUILDING VALUEATION TABLE.
 3. PROJECT SHALL COMPLY WITH THE FAIR HOUSING ACT. FAIR
 HOUSING GUIDELINES. 2017 FLORIDA ACCESSIBILITY CODE/
 FAIR HOUSING ACCESSIBILITY GUIDELINES. SECTION 3. FAIR
 HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS. FOR
 PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY
 DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED
 FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF
 THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING
 PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY
 DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL
 GOVERNMENT ON OR BEFORE JANUARY 13, 1990.
 3A. ACCESSIBLE PARKING - IF PROVIDED AT THE SITE,
 DESIGNATED ACCESSIBLE PARKING AT THE DWELLING UNIT ON
 REQUEST OF RESIDENTS WITH HANDICAPS ON THE SAME TERMS
 AND WITH THE FULL RANGE OF CHOICES (E.G., SURFACE
 PARKING OR GARAGE) THAT ARE PROVIDED FOR OTHER
 RESIDENTS OF THE PROJECT WITH ACCESSIBLE PARKING ON A
 ROUTE ACCESSIBLE TO WHEELCHAIRS FOR AT LEAST 2% OF THE
 COVERED DWELLING UNITS: ACCESSIBLE VISITOR PARKING
 SUFFICIENT TO PROVIDE ACCESS TO GRADE LEVEL ENTRANCES
 OF COVERED MULTIFAMILY DWELLINGS; AND ACCESSIBLE
 PARKING AT FACILITIES (E.G., SWIMMING POOLS) THAT SERVE
 ACCESSIBLE BUILDINGS.
 3B. 406 CURB RAMPS
 406.1 GENERAL.
 CURB RAMPS ON ACCESSIBLE ROUTES SHALL COMPLY WITH 406,
 405.2 THROUGH 405.5, AND 405.10.
 406.2 COUNTER SLOPE.
 COUNTER SLOPES OF ADJOINING GUTTERS AND ROAD SURFACES
 IMMEDIATELY ADJACENT TO THE CURB RAMP SHALL NOT BE
 STEEPER THAN 1:20. THE ADJACENT SURFACES AT TRANSITIONS
 AT CURB RAMPS TO WALKS, GUTTERS, AND STREETS SHALL BE
 AT THE SAME LEVEL.
 3C. ACCESSIBLE ENTRANCE - REQUIREMENT 1. ACCESSIBLE
 BUILDING ENTRANCE ON AN ACCESSIBLE ROUTE.
 UNDER SECTION 100.205(A), COVERED MULTIFAMILY DWELLINGS
 SHALL BE DESIGNED AND CONSTRUCTED TO HAVE AT LEAST ONE
 BUILDING ENTRANCE ON AN ACCESSIBLE ROUTE, UNLESS IT IS
 IMPRACTICAL TO DO SO BECAUSE OF TERRAIN OR UNUSUAL
 CHARACTERISTICS OF THE SITE.
 3D. ACCESSIBLE ROUTE - IT APPEARS THE ACCESSIBLE ROUTE
 TERMINATES AT THE FRONT ENTRANCE STEPS. PLEASE CLARIFY
 THE ACCESSIBLE ROUTE INTO THE BUILDING.
 4. IDENTIFY WHICH UNIT WILL BE HANDICAPPED ADAPTABLE
 PER 24 CFR 100.205.
 5. THE FOLLOWING PRODUCT APPROVALS IDENTIFIED IN THE
 WINDOW AND DOOR SCHEDULE ARE NOT INCLUDED IN THIS
 SUBMITTAL -
 5A. DOORS - OPENING 01 - NOA 17-1114.01
 5B. WINDOWS - OPENINGS 05, 07, 10, 20 & 25 - NOA
 17-0630.08.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By jpearson Date 2018-10-25 Time 07:51 Rev Time 0.00
Received By jpearson Date 2018-10-25 Time 06:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-07-08 Cont ID  
Sent By jpearson Date 2018-07-08 Time 13:11 Rev Time 0.00
Received By jpearson Date 2018-07-08 Time 10:20 Sent To  
Notes
2018-07-08 13:07:01CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED)
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9 (NOT PROVIDED)
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16,
 110.24(NOT PROVIDED)
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. SHOW LOCATION OF SERVICE EQUIPMENT ON PLAN. FBC
 107.2.1 (NOT PROVIDED)
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64 (NOT PROVIDED)
 9. ONLY RECEPTACLE OUTLETS ARE SHOWN AS AFCI PROTECTED
 ON PLAN. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16 (NOT CORRECTED)
 10. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 (NOT PROVIDED CORRECTLY. THE CALCULATION PROVIDED WAS
 FOR A SINGLE DWELLING UNIT AND SHOULD NOT BE USED FOR
 MULTI FAMILY. PROVIDE CORRECTION. NEC 220.84)
 11. PROVIDE ADDRESS OF PROJECT ON PLAN. WPB FBC 107.2.1
 (NOT PROVIDED)
  
 NEW COMMENT:
  
 12. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN
 ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF
 IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD
 TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS
 REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)?
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By jpearson Date 2018-05-01 Time 10:55 Rev Time 0.00
Received By jpearson Date 2018-05-01 Time 09:19 Sent To  
Notes
2018-05-01 10:56:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS.
 NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE
 CORRECTION. NEC 210.11(C)(3)
 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 7. SHOW LOCATION OF SERVICE EQUIPMENT ON PLAN. FBC
 107.2.1
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. ONLY RECEPTACLE OUTLETS ARE SHOWN AS AFCI PROTECTED
 ON PLAN. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE
 E3902.16
 10. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM
 CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 11. PROVIDE ADDRESS OF PROJECT ON PLAN. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2018-10-25 Cont ID  
Sent By rrossano Date 2018-10-25 Time   Rev Time 0.00
Received By rrossano Date 2018-10-25 Time   Sent To I
Notes
2018-10-25 10:42:31UNDER FORMAL ENGINEERING REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-07-12 Cont ID  
Sent By shill Date 2018-07-12 Time 09:06 Rev Time 0.00
Received By shill Date 2018-07-12 Time 09:06 Sent To  
Notes
2018-07-12 09:06:41CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-04-21 Cont ID  
Sent By shill Date 2018-04-21 Time 11:14 Rev Time 0.00
Received By shill Date 2018-04-21 Time 11:14 Sent To  
Notes
2018-04-21 11:14:56CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time   Rev Time 0.00
Received By pleduc Date 2018-10-24 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-06-25 Cont ID  
Sent By pleduc Date 2018-06-25 Time   Rev Time 0.00
Received By pleduc Date 2018-06-25 Time 12:58 Sent To  
Notes
2018-06-25 16:24:172ND REVIEW COMMENTS
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) COMPLIED
  
  
  
 2) SHEET A 1 - THE DOOR INDICATED AT THE COVERED ENTRY
 , # 10, IS AN EGRESS DOOR AND SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS, AND SHALL HAVE
 COMPLIANT EGRESS LOCKS AND/OR HARDWARE.
  
 PER NFPA 101
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE SPECIAL REQUIREMENTS OF 7.2.1.
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS REQUIRED TO SERVE AS AN EXIT SHALL BE
 DESIGNED AND CONSTRUCTED SO THAT THE PATH OF EGRESS
 TRAVEL IS OBVIOUS AND DIRECT. WINDOWS THAT, BECAUSE OF
 THEIR PHYSICAL CONFIGURATION OR DESIGN AND THE
 MATERIALS USED IN THEIR CONSTRUCTION, HAVE THE
 POTENTIAL TO BE MISTAKEN FOR DOOR OPENINGS SHALL BE
 MADE INACCESSIBLE TO THE OCCUPANTS BY BARRIERS OR
 RAILINGS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET A 1 - TWO UNIT B DOORS ARE INDICATING AS
 OPENING INTO THE EGRESS TRAVEL PATH.
  
 PER NFPA 101
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) THERE IS NO LIFE SAFETY PLAN INDICATING ALL PATHS OF
 EGRESS LEADING TO A PUBLIC WAY, INCLUDING BUT NO
 LIMITED TO, EGRESS TRAVEL PATHS, EXIT LIGHTING AND
 EMERGENCY LIGHTING, ETC.
  
 PER NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE PROVIDE A LIFE SAFETY PLAN FOR THESE APARTMENTS.
  
  
  
  
 5) SHEET E 2 - THERE IS NO EXIT SIGN OR EXIT
 ILLUMINATION AT THE FRONT COVERED ENTRY LEADING TO THE
 DOOR # 10, THE LAUDRY ROOM OR OFFICE.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS
  
 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL
 BUILDINGS REQUIRING MORE THAN ONE EXIT.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2.
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED
 EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION
 OF THE EGRESS PATH IS NOT OBVIOUS.
 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE
 SHALL BE PROVIDED TO MEET ALL OF THE FOLLOWING
 CRITERIA, UNLESS OTHERWISE PROVIDED IN 7.10.1.4:
 (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR
 REQUIRING AN EXIT SIGN.
 (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT.
 (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1,
 AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND USABLE
 BUILDINGS AND FACILITIES
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR
 WAY TO REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE
 RATED VIEWING DISTANCE OR 100 FT (30 M), WHICHEVER IS
 LESS, FROM THE NEAREST SIGN.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE SIGNAGE.
  
  
  
 6) COMPLIED
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-10 Cont ID  
Sent By pleduc Date 2018-04-10 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 16:17 Sent To  
Notes
2018-04-10 13:50:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET CS - THERE IS INDICATIONS OF A FULLY
 SPRINKLERED BUILDING; HOWEVER, THERE ARE NO FIRE
 SPRINKLER DRAWINGS OR NARRATIVE IN COMPLIANCE WITH OF
 FAC 61G FROM AN EOR.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PER FL BLDG CODE
  
 105.3.1.2
 NO PERMIT MAY BE ISSUED FOR ANY BUILDING CONSTRUCTION,
 ERECTION, ALTERATION, MODIFICATION, REPAIR, OR ADDITION
 UNLESS THE APPLICANT FOR SUCH PERMIT PROVIDES TO THE
 ENFORCING AGENCY WHICH ISSUES THE PERMIT ANY OF THE
 FOLLOWING DOCUMENTS WHICH APPLY TO THE CONSTRUCTION FOR
 WHICH THE PERMIT IS TO BE ISSUED AND WHICH SHALL BE
 PREPARED BY OR UNDER THE DIRECTION OF AN ENGINEER
 REGISTERED UNDER CHAPTER 471, FLORIDA STATUTES:
  
 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR
 ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH
 CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS
 AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN
 A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY
 DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER
 SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION,
 ADDITION OR DELETION OF NOT MORE THAN 49 HEADS,
 NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER
 SYSTEM.
  
 PLEASE REVIEW AND PROVIDE COMPLIANT DRAWINGS OR
 NARRATIVE FROM AN EOR WITH THIS MASTER PERMIT. SHOP
 DRAWINGS ARE NOT APPLICABLE TO THIS REQUIREMENT.
  
  
  
 2) SHEET A 1 - THE DOOR INDICATED AT THE COVERED ENTRY
 , # 10, IS AN EGRESS DOOR AND SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS, AND SHALL HAVE
 COMPLIANT EGRESS LOCKS AND/OR HARDWARE.
  
 PER NFPA 101
  
 7.2 MEANS OF EGRESS COMPONENTS.
 7.2.1 DOOR OPENINGS.
 7.2.1.1 GENERAL.
 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL
 CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND
 TO THE SPECIAL REQUIREMENTS OF 7.2.1.
 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL
 ENTRANCE THAT IS REQUIRED TO SERVE AS AN EXIT SHALL BE
 DESIGNED AND CONSTRUCTED SO THAT THE PATH OF EGRESS
 TRAVEL IS OBVIOUS AND DIRECT. WINDOWS THAT, BECAUSE OF
 THEIR PHYSICAL CONFIGURATION OR DESIGN AND THE
 MATERIALS USED IN THEIR CONSTRUCTION, HAVE THE
 POTENTIAL TO BE MISTAKEN FOR DOOR OPENINGS SHALL BE
 MADE INACCESSIBLE TO THE OCCUPANTS BY BARRIERS OR
 RAILINGS.
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS
 OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET A 1 - TWO UNIT B DOORS ARE INDICATING AS
 OPENING INTO THE EGRESS TRAVEL PATH.
  
 PER NFPA 101
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR
 LEAF IS FULLY OPEN
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) THERE IS NO LIFE SAFETY PLAN INDICATING ALL PATHS OF
 EGRESS LEADING TO A PUBLIC WAY, INCLUDING BUT NO
 LIMITED TO, EGRESS TRAVEL PATHS, EXIT LIGHTING AND
 EMERGENCY LIGHTING, ETC.
  
 PER NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE PROVIDE A LIFE SAFETY PLAN FOR THESE APARTMENTS.
  
  
  
  
 5) SHEET E 2 - THERE IS NO EXIT SIGN OR EXIT
 ILLUMINATION AT THE FRONT COVERED ENTRY LEADING TO THE
 DOOR # 10, THE LAUDRY ROOM OR OFFICE.
  
 PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS
  
 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
  
 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL
 BUILDINGS REQUIRING MORE THAN ONE EXIT.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2.
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS,
 SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY
 VISIBLE FROM ANY DIRECTION OF EXIT ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED
 EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION
 OF THE EGRESS PATH IS NOT OBVIOUS.
 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE
 SHALL BE PROVIDED TO MEET ALL OF THE FOLLOWING
 CRITERIA, UNLESS OTHERWISE PROVIDED IN 7.10.1.4:
 (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR
 REQUIRING AN EXIT SIGN.
 (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT.
 (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1,
 AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND USABLE
 BUILDINGS AND FACILITIES
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR
 WAY TO REACH THE EXIT IS NOT READILY APPARENT TO THE
 OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE
 RATED VIEWING DISTANCE OR 100 FT (30 M), WHICHEVER IS
 LESS, FROM THE NEAREST SIGN.
  
 PLEASE REVIEW AND PROVIDE APPLICABLE SIGNAGE.
  
  
  
 6) SHEET E 1 OR E 2 - THERE ARE NO INDICATIONS OR FIRE
 ALARM WORK BEING SUBMITTED OR COMPLETED THROUGH
 SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-03-01 Cont ID  
Sent By dbattles Date 2019-03-01 Time 16:49 Rev Time 0.00
Received By dbattles Date 2019-02-28 Time 14:31 Sent To  
Notes
2019-03-01 14:31:56IMPACT FEES ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 11:46 Sent To  
Notes
2018-10-18 11:46:36C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-20 Cont ID  
Sent By lmarchan Date 2018-07-20 Time 16:40 Rev Time 0.00
Received By lmarchan Date 2018-06-21 Time 15:42 Sent To  
Notes
2018-06-22 15:42:33C25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 12:03 Rev Time 0.00
Received By cthroop Date 2018-04-05 Time 13:30 Sent To I
Notes
2018-04-06 13:30:55C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-03-01 Cont ID  
Sent By dbattles Date 2019-03-01 Time 16:49 Rev Time 0.00
Received By dbattles Date 2019-03-01 Time 16:49 Sent To  
Notes
2019-03-01 16:50:06STAMP ON PLANS - OK
 RECEIPT PROVIDED - OK
 MU-2019-004740

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 11:15 Rev Time 0.00
Received By cthroop Date 2018-04-25 Time 07:32 Sent To  
Notes
2018-05-01 11:15:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-19 Cont ID  
Sent By cmontell Date 2018-04-19 Time 14:35 Rev Time 0.00
Received By cmontell Date 2018-04-19 Time 14:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 16:32 Rev Time 0.00
Received By gjohnson Date 2018-10-25 Time 16:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-07-12 Cont ID  
Sent By gjohnson Date 2018-07-12 Time 09:55 Rev Time 0.00
Received By gjohnson Date 2018-07-12 Time 09:11 Sent To  
Notes
2018-07-12 10:40:572ND REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH.
  
 1. THE BUILDING SHALL COMPLY WITH THE FAIR HOUSING ACT.
 C) PROVIDE DETAILS THAT SHOW THE MOUNTING HEIGHTS FOR
 THE GRAB BAR BACKING. PER FHA REQUIREMENT #6 THE GRAB
 BAR BACKING FOR THE TOILET SHALL COMPLY WITH FIG. #3 IN
 THE FHA GUIDELINES AND THE SHOWER FIG. #5
  
 2. PROVIDE A PLUMBING FLOOR PLAN WITH PIPING AND SITE
 PLAN. PER WPB AMEND TO FBC 107.3.5.1.3
  
 3. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB
 AMEND TO FBC 107.3.5.1.3(5)
  
 NEW COMMENTS:
  
 1. SHT. A-6 THE BACKING FOR THE GRAB BARS IS NOT SHOWN
 BEHIND THE TOILET ON THE DETAIL FOR TYPE B BATHEOOM.
 PLEASE SHOW PER FHA REQUIREMENT #6
  
 2. SHT.S-3 ON THE SANITARY RISER FOR THE LAUNDRY, THE
 LAUNDRY SINK WASTE ARM SHALL CONNECT TO THE WASTE STACK
 SEPARATELY FROM THE WASHING MACHINE. PER FBC PL 901.2.1
  
 3. THIS 4 UNIT BUILDING IT IS A MULTI FAMILY AND FALLS
 UNDER THE FBC NOT THE FBC RESIDENTIAL ON SHT. CS UNDER
 CODE COMPLIANCE AND GENERAL ARCHITECTURAL NOTES AND
 SHT. S-3 UNDER PLUMBING NOTES IT REFERENCES THR
 RESIDENTIAL CODE PLEASE REMOVE ANY REFERENCES TO THE
 RESIDENTIAL CODE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-20 Cont ID  
Sent By gjohnson Date 2018-04-20 Time 11:15 Rev Time 0.00
Received By gjohnson Date 2018-04-20 Time 11:02 Sent To  
Notes
2018-04-20 14:43:551ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE BUILDING SHALL COMPLY WITH THE FAIR HOUSING ACT.
  
 A) PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT IS
 BEING USED TO COMPLY WITH FHA GUIDELINES.
 B) PLEASE LIST ON THE PLAN AND SHOW WHICH BATHROOMS ARE
 DESIGNED TO MEET DESIGN SPEC A OR B PER FHA REQUIREMENT
 #7
 C) PROVIDE DETAILS THAT SHOW THE MOUNTING HEIGHTS FOR
 THE GRAB BAR BACKING. PER FHA REQUIREMENT #6
 D) PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE
 TOILET,LAVATORY, SHOWER AND KITCHEN. PER FHA
 REQUIREMENT #7
  
 2. PROVIDE A PLUMBING FLOOR PLAN WITH PIPING AND SITE
 PLAN. PER WPB AMEND TO FBC 107.3.5.1.3
  
 3. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB
 AMEND TO FBC 107.3.5.1.3(5)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-07-12 Cont ID  
Sent By cthroop Date 2018-07-12 Time 15:57 Rev Time 0.00
Received By cthroop Date 2018-07-09 Time 12:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-01 Cont ID  
Sent By cthroop Date 2018-05-01 Time 11:15 Rev Time 0.00
Received By cthroop Date 2018-05-01 Time 08:40 Sent To  
Notes
2018-05-01 11:17:23BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM
 COMPONENTS.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-24 Cont ID  
Sent By jroach Date 2018-10-24 Time 09:43 Rev Time 0.00
Received By jroach Date 2018-10-23 Time 10:52 Sent To  
Notes
2018-10-24 09:44:10REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING
 TREES ON THE SITE, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED TO, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT - PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-20 Cont ID  
Sent By jroach Date 2018-07-20 Time 11:37 Rev Time 0.00
Received By jroach Date 2018-07-18 Time 15:30 Sent To PC
Notes
2018-07-20 11:38:07PROVISO
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING
 TREES ON THE SITE, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED TO, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING DIVISION.
  
 2. SEPARATE PERMIT REQUIRED FOR LANDSCAPING AND
 IRRIGATION.
  
 3. ALL FENCING SURROUNDING THE TRASH ENCLOSURES SHALL
 BE SOLID/OPAQUE (CHAIN LINK WITH SLATS DOES NOT MEET
 THIS REQUIREMENT).
  
 4. ALL A/C CONDENSING UNITS SHALL BE A MINIMUM OF 11
 FEET FROM THE PROPERTY LINE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-27 Cont ID  
Sent By JR Date 2018-04-27 Time 13:46 Rev Time 0.00
Received By jroach Date 2018-04-27 Time 13:46 Sent To  
Notes
2018-04-27 13:46:28ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.26.2018
 PERMIT NO.: 18040194
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT AN
 APPLICATION FOR AN INFORMAL SITE PLAN REVIEW SHALL BE
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ?
 PLANNING DIVISION. SUCH APPLICATION HAS ALREADY BEEN
 SUBMITTED AND IS UNDER REVIEW. UPON APPROVAL OF THE
 SITE PLAN REVIEW, ALL DRAWINGS SUBMITTED AS PART OF THE
 BUILDING PERMIT SHALL MATCH THOSE WHICH WERE APPROVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved