| Notes |
| 2018-07-12 17:15:36 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. OCCUPANCY CLASSIFICATION IS R-2. CORRECT PLAN PAGES | | | CS AND S-3. | | | | | | 2. PROVIDE LIFE SAFETY PLAN. SHOW PATH OF TRAVEL TO | | | PUBLIC WAY. PROVIDE EXIT AND EMERGENCY LIGHTING. | | | | | | 3. STATE INSULATION R VALUES FROM ENERGY SUBMITTAL ON | | | PLANS. | | | | | | 4. PROVIDE SOILS REPORT. | | | FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE | | | CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND | | | REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE | | | REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL | | | INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY | | | TESTING OR ENGINEERING CALCULATIONS, SUCH | | | INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED | | | DESIGN PROFESSIONAL. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-05-01 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-04-25 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2018-05-01 11:33:27 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DESIGN IS FOR A FULLY SPRINKLERED BUILDING. PROVIDE | | | SPRINKLER SYSTEM DESIGN. | | | 2. VALUE WAS ADJUSTED FROM $363479 APPLIED TO $383274 | | | CALCULATED PER ICC BUILDING VALUEATION TABLE. | | | 3. PROJECT SHALL COMPLY WITH THE FAIR HOUSING ACT. FAIR | | | HOUSING GUIDELINES. 2017 FLORIDA ACCESSIBILITY CODE/ | | | FAIR HOUSING ACCESSIBILITY GUIDELINES. SECTION 3. FAIR | | | HOUSING ACT DESIGN AND CONSTRUCTION REQUIREMENTS. FOR | | | PURPOSES OF THIS SECTION, A COVERED MULTIFAMILY | | | DWELLING SHALL BE DEEMED TO BE DESIGNED AND CONSTRUCTED | | | FOR FIRST OCCUPANCY ON OR BEFORE MARCH 13, 1991, IF | | | THEY ARE OCCUPIED BY THAT DATE OR IF THE LAST BUILDING | | | PERMIT OR RENEWAL THEREOF FOR THE COVERED MULTIFAMILY | | | DWELLINGS IS ISSUED BY A STATE, COUNTY OR LOCAL | | | GOVERNMENT ON OR BEFORE JANUARY 13, 1990. | | | 3A. ACCESSIBLE PARKING - IF PROVIDED AT THE SITE, | | | DESIGNATED ACCESSIBLE PARKING AT THE DWELLING UNIT ON | | | REQUEST OF RESIDENTS WITH HANDICAPS ON THE SAME TERMS | | | AND WITH THE FULL RANGE OF CHOICES (E.G., SURFACE | | | PARKING OR GARAGE) THAT ARE PROVIDED FOR OTHER | | | RESIDENTS OF THE PROJECT WITH ACCESSIBLE PARKING ON A | | | ROUTE ACCESSIBLE TO WHEELCHAIRS FOR AT LEAST 2% OF THE | | | COVERED DWELLING UNITS: ACCESSIBLE VISITOR PARKING | | | SUFFICIENT TO PROVIDE ACCESS TO GRADE LEVEL ENTRANCES | | | OF COVERED MULTIFAMILY DWELLINGS; AND ACCESSIBLE | | | PARKING AT FACILITIES (E.G., SWIMMING POOLS) THAT SERVE | | | ACCESSIBLE BUILDINGS. | | | 3B. 406 CURB RAMPS | | | 406.1 GENERAL. | | | CURB RAMPS ON ACCESSIBLE ROUTES SHALL COMPLY WITH 406, | | | 405.2 THROUGH 405.5, AND 405.10. | | | 406.2 COUNTER SLOPE. | | | COUNTER SLOPES OF ADJOINING GUTTERS AND ROAD SURFACES | | | IMMEDIATELY ADJACENT TO THE CURB RAMP SHALL NOT BE | | | STEEPER THAN 1:20. THE ADJACENT SURFACES AT TRANSITIONS | | | AT CURB RAMPS TO WALKS, GUTTERS, AND STREETS SHALL BE | | | AT THE SAME LEVEL. | | | 3C. ACCESSIBLE ENTRANCE - REQUIREMENT 1. ACCESSIBLE | | | BUILDING ENTRANCE ON AN ACCESSIBLE ROUTE. | | | UNDER SECTION 100.205(A), COVERED MULTIFAMILY DWELLINGS | | | SHALL BE DESIGNED AND CONSTRUCTED TO HAVE AT LEAST ONE | | | BUILDING ENTRANCE ON AN ACCESSIBLE ROUTE, UNLESS IT IS | | | IMPRACTICAL TO DO SO BECAUSE OF TERRAIN OR UNUSUAL | | | CHARACTERISTICS OF THE SITE. | | | 3D. ACCESSIBLE ROUTE - IT APPEARS THE ACCESSIBLE ROUTE | | | TERMINATES AT THE FRONT ENTRANCE STEPS. PLEASE CLARIFY | | | THE ACCESSIBLE ROUTE INTO THE BUILDING. | | | 4. IDENTIFY WHICH UNIT WILL BE HANDICAPPED ADAPTABLE | | | PER 24 CFR 100.205. | | | 5. THE FOLLOWING PRODUCT APPROVALS IDENTIFIED IN THE | | | WINDOW AND DOOR SCHEDULE ARE NOT INCLUDED IN THIS | | | SUBMITTAL - | | | 5A. DOORS - OPENING 01 - NOA 17-1114.01 | | | 5B. WINDOWS - OPENINGS 05, 07, 10, 20 & 25 - NOA | | | 17-0630.08. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-10-25 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-10-25 |
Time |
06:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2018-07-08 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-07-08 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-07-08 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2018-07-08 13:07:01 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 (NOT PROVIDED) | | | 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. | | | NEC 110.3, 110.9 (NOT PROVIDED) | | | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, | | | 110.24(NOT PROVIDED) | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. SHOW LOCATION OF SERVICE EQUIPMENT ON PLAN. FBC | | | 107.2.1 (NOT PROVIDED) | | | 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER | | | CODE. NEC 210.64 (NOT PROVIDED) | | | 9. ONLY RECEPTACLE OUTLETS ARE SHOWN AS AFCI PROTECTED | | | ON PLAN. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY | | | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS | | | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, | | | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, | | | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, | | | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI | | | PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE | | | E3902.16 (NOT CORRECTED) | | | 10. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM | | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | | (NOT PROVIDED CORRECTLY. THE CALCULATION PROVIDED WAS | | | FOR A SINGLE DWELLING UNIT AND SHOULD NOT BE USED FOR | | | MULTI FAMILY. PROVIDE CORRECTION. NEC 220.84) | | | 11. PROVIDE ADDRESS OF PROJECT ON PLAN. WPB FBC 107.2.1 | | | (NOT PROVIDED) | | | | | | NEW COMMENT: | | | | | | 12. PLEASE BE ADVISED THAT SOME COMMENTS HAVE NOT BEEN | | | ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD REVIEW, IF | | | IT IS NECESSARY TO REJECT THE SUBMITTED PLAN A THIRD | | | TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW IS | | | REQUIRED. FLORIDA STATUTES STATE: ?WITH RESPECT TO | | | EVALUATION OF DESIGN PROFESSIONALS? DOCUMENTS, IF A | | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)? | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-05-01 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-05-01 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2018-05-01 10:56:21 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | 2. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANELS. | | | NEC 110.3, 110.9 | | | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF | | | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND | | | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 | | | 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE. | | | FBC EC C405.1, R404.1 | | | 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE | | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE | | | CORRECTION. NEC 210.11(C)(3) | | | 6. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT | | | SERVICE. SHOW ON PLAN. NEC 250.94 | | | 7. SHOW LOCATION OF SERVICE EQUIPMENT ON PLAN. FBC | | | 107.2.1 | | | 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER | | | CODE. NEC 210.64 | | | 9. ONLY RECEPTACLE OUTLETS ARE SHOWN AS AFCI PROTECTED | | | ON PLAN. PER CODE, ALL BRANCH CIRCUITS THAT SUPPLY | | | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS | | | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, | | | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, | | | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, | | | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI | | | PROTECTED. PROVIDE CORRECTION. NEC 210.12; FBC RE | | | E3902.16 | | | 10. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM | | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | | 11. PROVIDE ADDRESS OF PROJECT ON PLAN. WPB FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2018-10-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2018-10-25 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-10-25 10:42:31 | UNDER FORMAL ENGINEERING REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-12 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-12 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2018-07-12 09:06:41 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2018-04-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-04-21 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-04-21 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2018-04-21 11:14:56 | CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT | | | APPLICATION IF REQUIRED | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE | | | | | | MAIN PHONE: (561) 822-1200 | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-10-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-10-24 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2018-06-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-06-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-06-25 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2018-06-25 16:24:17 | 2ND REVIEW COMMENTS | | | | | | | | | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) COMPLIED | | | | | | | | | | | | 2) SHEET A 1 - THE DOOR INDICATED AT THE COVERED ENTRY | | | , # 10, IS AN EGRESS DOOR AND SHALL COMPLY WITH NFPA | | | 101, CHAPTER 7, MEANS OF EGRESS, AND SHALL HAVE | | | COMPLIANT EGRESS LOCKS AND/OR HARDWARE. | | | | | | PER NFPA 101 | | | | | | 7.2 MEANS OF EGRESS COMPONENTS. | | | 7.2.1 DOOR OPENINGS. | | | 7.2.1.1 GENERAL. | | | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL | | | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND | | | TO THE SPECIAL REQUIREMENTS OF 7.2.1. | | | 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL | | | ENTRANCE THAT IS REQUIRED TO SERVE AS AN EXIT SHALL BE | | | DESIGNED AND CONSTRUCTED SO THAT THE PATH OF EGRESS | | | TRAVEL IS OBVIOUS AND DIRECT. WINDOWS THAT, BECAUSE OF | | | THEIR PHYSICAL CONFIGURATION OR DESIGN AND THE | | | MATERIALS USED IN THEIR CONSTRUCTION, HAVE THE | | | POTENTIAL TO BE MISTAKEN FOR DOOR OPENINGS SHALL BE | | | MADE INACCESSIBLE TO THE OCCUPANTS BY BARRIERS OR | | | RAILINGS. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 3) SHEET A 1 - TWO UNIT B DOORS ARE INDICATING AS | | | OPENING INTO THE EGRESS TRAVEL PATH. | | | | | | PER NFPA 101 | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR | | | LEAF IS FULLY OPEN | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | | | | 4) THERE IS NO LIFE SAFETY PLAN INDICATING ALL PATHS OF | | | EGRESS LEADING TO A PUBLIC WAY, INCLUDING BUT NO | | | LIMITED TO, EGRESS TRAVEL PATHS, EXIT LIGHTING AND | | | EMERGENCY LIGHTING, ETC. | | | | | | PER NFPA 1 | | | | | | 1.7.11 PLANS AND SPECIFICATIONS. | | | | | | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN FOR THESE APARTMENTS. | | | | | | | | | | | | | | | 5) SHEET E 2 - THERE IS NO EXIT SIGN OR EXIT | | | ILLUMINATION AT THE FRONT COVERED ENTRY LEADING TO THE | | | DOOR # 10, THE LAUDRY ROOM OR OFFICE. | | | | | | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS | | | | | | 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. | | | | | | 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL | | | BUILDINGS REQUIRING MORE THAN ONE EXIT. | | | | | | 7.8 ILLUMINATION OF MEANS OF EGRESS. | | | 7.8.1 GENERAL. | | | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY | | | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 | | | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING | | | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT | | | PASSAGEWAYS LEADING TO A PUBLIC WAY. | | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF | | | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE | | | FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2. | | | | | | 7.10 MARKING OF MEANS OF EGRESS. | | | 7.10.1 GENERAL. | | | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE | | | MARKED IN ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED | | | IN CHAPTERS 11 THROUGH 43. | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, | | | SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY | | | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. | | | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH | | | WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED | | | EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION | | | OF THE EGRESS PATH IS NOT OBVIOUS. | | | 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE | | | SHALL BE PROVIDED TO MEET ALL OF THE FOLLOWING | | | CRITERIA, UNLESS OTHERWISE PROVIDED IN 7.10.1.4: | | | (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR | | | REQUIRING AN EXIT SIGN. | | | (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. | | | (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, | | | AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND USABLE | | | BUILDINGS AND FACILITIES | | | 7.10.1.5 EXIT ACCESS. | | | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, | | | READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR | | | WAY TO REACH THE EXIT IS NOT READILY APPARENT TO THE | | | OCCUPANTS. | | | 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO | | | POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE | | | RATED VIEWING DISTANCE OR 100 FT (30 M), WHICHEVER IS | | | LESS, FROM THE NEAREST SIGN. | | | | | | PLEASE REVIEW AND PROVIDE APPLICABLE SIGNAGE. | | | | | | | | | | | | 6) COMPLIED | | | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2018-04-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2018-04-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2018-04-09 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2018-04-10 13:50:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | | | | 1) SHEET CS - THERE IS INDICATIONS OF A FULLY | | | SPRINKLERED BUILDING; HOWEVER, THERE ARE NO FIRE | | | SPRINKLER DRAWINGS OR NARRATIVE IN COMPLIANCE WITH OF | | | FAC 61G FROM AN EOR. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | PER FL BLDG CODE | | | | | | 105.3.1.2 | | | NO PERMIT MAY BE ISSUED FOR ANY BUILDING CONSTRUCTION, | | | ERECTION, ALTERATION, MODIFICATION, REPAIR, OR ADDITION | | | UNLESS THE APPLICANT FOR SUCH PERMIT PROVIDES TO THE | | | ENFORCING AGENCY WHICH ISSUES THE PERMIT ANY OF THE | | | FOLLOWING DOCUMENTS WHICH APPLY TO THE CONSTRUCTION FOR | | | WHICH THE PERMIT IS TO BE ISSUED AND WHICH SHALL BE | | | PREPARED BY OR UNDER THE DIRECTION OF AN ENGINEER | | | REGISTERED UNDER CHAPTER 471, FLORIDA STATUTES: | | | | | | 2. FIRE SPRINKLER DOCUMENTS FOR ANY NEW BUILDING OR | | | ADDITION WHICH INCLUDES A FIRE SPRINKLER SYSTEM WHICH | | | CONTAINS 50 OR MORE SPRINKLER HEADS. PERSONNEL AS | | | AUTHORIZED BY CHAPTER 633 FLORIDA STATUTES, MAY DESIGN | | | A FIRE SPRINKLER SYSTEM OF 49 OR FEWER HEADS AND MAY | | | DESIGN THE ALTERATION OF AN EXISTING FIRE SPRINKLER | | | SYSTEM IF THE ALTERATION CONSISTS OF THE RELOCATION, | | | ADDITION OR DELETION OF NOT MORE THAN 49 HEADS, | | | NOTWITHSTANDING THE SIZE OF THE EXISTING FIRE SPRINKLER | | | SYSTEM. | | | | | | PLEASE REVIEW AND PROVIDE COMPLIANT DRAWINGS OR | | | NARRATIVE FROM AN EOR WITH THIS MASTER PERMIT. SHOP | | | DRAWINGS ARE NOT APPLICABLE TO THIS REQUIREMENT. | | | | | | | | | | | | 2) SHEET A 1 - THE DOOR INDICATED AT THE COVERED ENTRY | | | , # 10, IS AN EGRESS DOOR AND SHALL COMPLY WITH NFPA | | | 101, CHAPTER 7, MEANS OF EGRESS, AND SHALL HAVE | | | COMPLIANT EGRESS LOCKS AND/OR HARDWARE. | | | | | | PER NFPA 101 | | | | | | 7.2 MEANS OF EGRESS COMPONENTS. | | | 7.2.1 DOOR OPENINGS. | | | 7.2.1.1 GENERAL. | | | 7.2.1.1.1 A DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL | | | CONFORM TO THE GENERAL REQUIREMENTS OF SECTION 7.1 AND | | | TO THE SPECIAL REQUIREMENTS OF 7.2.1. | | | 7.2.1.1.2 EVERY DOOR OPENING AND EVERY PRINCIPAL | | | ENTRANCE THAT IS REQUIRED TO SERVE AS AN EXIT SHALL BE | | | DESIGNED AND CONSTRUCTED SO THAT THE PATH OF EGRESS | | | TRAVEL IS OBVIOUS AND DIRECT. WINDOWS THAT, BECAUSE OF | | | THEIR PHYSICAL CONFIGURATION OR DESIGN AND THE | | | MATERIALS USED IN THEIR CONSTRUCTION, HAVE THE | | | POTENTIAL TO BE MISTAKEN FOR DOOR OPENINGS SHALL BE | | | MADE INACCESSIBLE TO THE OCCUPANTS BY BARRIERS OR | | | RAILINGS. | | | | | | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. | | | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED | | | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS | | | OCCUPIED. | | | | | | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE | | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | | OPERATION FROM THE EGRESS SIDE. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 3) SHEET A 1 - TWO UNIT B DOORS ARE INDICATING AS | | | OPENING INTO THE EGRESS TRAVEL PATH. | | | | | | PER NFPA 101 | | | 7.2.1.4.3 DOOR LEAF ENCROACHMENT | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT | | | MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS | | | PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED | | | WIDTH OF THE STAIR LANDING WHEN THE DOOR | | | LEAF IS FULLY OPEN | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY. | | | | | | | | | | | | | | | 4) THERE IS NO LIFE SAFETY PLAN INDICATING ALL PATHS OF | | | EGRESS LEADING TO A PUBLIC WAY, INCLUDING BUT NO | | | LIMITED TO, EGRESS TRAVEL PATHS, EXIT LIGHTING AND | | | EMERGENCY LIGHTING, ETC. | | | | | | PER NFPA 1 | | | | | | 1.7.11 PLANS AND SPECIFICATIONS. | | | | | | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH | | | APPLICABLE CODES AND STANDARDS. | | | | | | | | | PLEASE PROVIDE A LIFE SAFETY PLAN FOR THESE APARTMENTS. | | | | | | | | | | | | | | | 5) SHEET E 2 - THERE IS NO EXIT SIGN OR EXIT | | | ILLUMINATION AT THE FRONT COVERED ENTRY LEADING TO THE | | | DOOR # 10, THE LAUDRY ROOM OR OFFICE. | | | | | | PER NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS | | | | | | 30.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. | | | | | | 30.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS | | | SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL | | | BUILDINGS REQUIRING MORE THAN ONE EXIT. | | | | | | 7.8 ILLUMINATION OF MEANS OF EGRESS. | | | 7.8.1 GENERAL. | | | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY | | | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 | | | THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING | | | TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT | | | DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, | | | CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT | | | PASSAGEWAYS LEADING TO A PUBLIC WAY. | | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF | | | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE | | | FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2. | | | | | | 7.10 MARKING OF MEANS OF EGRESS. | | | 7.10.1 GENERAL. | | | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE | | | MARKED IN ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED | | | IN CHAPTERS 11 THROUGH 43. | | | 7.10.1.2 EXITS. | | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | | THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, | | | SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY | | | VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. | | | 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH | | | WITHIN AN EXIT ENCLOSURE SHALL BE MARKED BY APPROVED | | | EXIT OR DIRECTIONAL EXIT SIGNS WHERE THE CONTINUATION | | | OF THE EGRESS PATH IS NOT OBVIOUS. | | | 7.10.1.3 EXIT DOOR TACTILE SIGNAGE. TACTILE SIGNAGE | | | SHALL BE PROVIDED TO MEET ALL OF THE FOLLOWING | | | CRITERIA, UNLESS OTHERWISE PROVIDED IN 7.10.1.4: | | | (1) TACTILE SIGNAGE SHALL BE LOCATED AT EACH EXIT DOOR | | | REQUIRING AN EXIT SIGN. | | | (2) TACTILE SIGNAGE SHALL READ AS FOLLOWS: EXIT. | | | (3) TACTILE SIGNAGE SHALL COMPLY WITH ICC/ANSI A117.1, | | | AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND USABLE | | | BUILDINGS AND FACILITIES | | | 7.10.1.5 EXIT ACCESS. | | | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, | | | READILY VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR | | | WAY TO REACH THE EXIT IS NOT READILY APPARENT TO THE | | | OCCUPANTS. | | | 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO | | | POINT IN AN EXIT ACCESS CORRIDOR IS IN EXCESS OF THE | | | RATED VIEWING DISTANCE OR 100 FT (30 M), WHICHEVER IS | | | LESS, FROM THE NEAREST SIGN. | | | | | | PLEASE REVIEW AND PROVIDE APPLICABLE SIGNAGE. | | | | | | | | | | | | 6) SHEET E 1 OR E 2 - THERE ARE NO INDICATIONS OR FIRE | | | ALARM WORK BEING SUBMITTED OR COMPLETED THROUGH | | | SEPARATE SHOP DRAWINGS BY CERTIFIED LIFE SAFETY | | | CONTRACTORS. | | | | | | PLEASE PROVIDE AN APPLICABLE NOTE. | | | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2019-03-01 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-03-01 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-02-28 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2019-03-01 14:31:56 | IMPACT FEES ROUTED TO CTHROOP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-25 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-16 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-07-20 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2018-07-20 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-06-21 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-05-01 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-04-05 |
Time |
13:30 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2019-03-01 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2019-03-01 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2019-03-01 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2019-03-01 16:50:06 | STAMP ON PLANS - OK | | | RECEIPT PROVIDED - OK | | | MU-2019-004740 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-05-01 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-04-25 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2018-05-01 11:15:53 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT | | | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. | | | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE | | | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN | | | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP | | | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE | | | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN | | | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY | | | IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2018-04-19 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2018-04-19 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2018-04-19 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-25 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-10-25 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-10-25 |
Time |
16:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-07-12 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-07-12 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2018-07-12 10:40:57 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED WITH. | | | | | | 1. THE BUILDING SHALL COMPLY WITH THE FAIR HOUSING ACT. | | | C) PROVIDE DETAILS THAT SHOW THE MOUNTING HEIGHTS FOR | | | THE GRAB BAR BACKING. PER FHA REQUIREMENT #6 THE GRAB | | | BAR BACKING FOR THE TOILET SHALL COMPLY WITH FIG. #3 IN | | | THE FHA GUIDELINES AND THE SHOWER FIG. #5 | | | | | | 2. PROVIDE A PLUMBING FLOOR PLAN WITH PIPING AND SITE | | | PLAN. PER WPB AMEND TO FBC 107.3.5.1.3 | | | | | | 3. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO | | | FBC 107.3.5.1.3(13) | | | | | | 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB | | | AMEND TO FBC 107.3.5.1.3(5) | | | | | | NEW COMMENTS: | | | | | | 1. SHT. A-6 THE BACKING FOR THE GRAB BARS IS NOT SHOWN | | | BEHIND THE TOILET ON THE DETAIL FOR TYPE B BATHEOOM. | | | PLEASE SHOW PER FHA REQUIREMENT #6 | | | | | | 2. SHT.S-3 ON THE SANITARY RISER FOR THE LAUNDRY, THE | | | LAUNDRY SINK WASTE ARM SHALL CONNECT TO THE WASTE STACK | | | SEPARATELY FROM THE WASHING MACHINE. PER FBC PL 901.2.1 | | | | | | 3. THIS 4 UNIT BUILDING IT IS A MULTI FAMILY AND FALLS | | | UNDER THE FBC NOT THE FBC RESIDENTIAL ON SHT. CS UNDER | | | CODE COMPLIANCE AND GENERAL ARCHITECTURAL NOTES AND | | | SHT. S-3 UNDER PLUMBING NOTES IT REFERENCES THR | | | RESIDENTIAL CODE PLEASE REMOVE ANY REFERENCES TO THE | | | RESIDENTIAL CODE. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-04-20 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-20 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-20 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2018-04-20 14:43:55 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE BUILDING SHALL COMPLY WITH THE FAIR HOUSING ACT. | | | | | | A) PLEASE INDICATE ON THE PLAN WHICH DESIGN DOCUMENT IS | | | BEING USED TO COMPLY WITH FHA GUIDELINES. | | | B) PLEASE LIST ON THE PLAN AND SHOW WHICH BATHROOMS ARE | | | DESIGNED TO MEET DESIGN SPEC A OR B PER FHA REQUIREMENT | | | #7 | | | C) PROVIDE DETAILS THAT SHOW THE MOUNTING HEIGHTS FOR | | | THE GRAB BAR BACKING. PER FHA REQUIREMENT #6 | | | D) PLEASE SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE | | | TOILET,LAVATORY, SHOWER AND KITCHEN. PER FHA | | | REQUIREMENT #7 | | | | | | 2. PROVIDE A PLUMBING FLOOR PLAN WITH PIPING AND SITE | | | PLAN. PER WPB AMEND TO FBC 107.3.5.1.3 | | | | | | 3. PROVIDE WATER ISOMETRIC DRAWING. PER WPB AMEND TO | | | FBC 107.3.5.1.3(13) | | | | | | 4. PROVIDE DETAIL FOR WATER HEATER PIPING. PER WPB | | | AMEND TO FBC 107.3.5.1.3(5) | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2018-07-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-07-12 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-07-09 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-05-01 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2018-05-01 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2018-05-01 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2018-05-01 11:17:23 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | CHRISTOPHER S. THROOP, C.B.O. | | | PLANS EXAMINER, PX3169 | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6726 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | 2. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM | | | COMPONENTS. | | | | | | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR | | | SUBMITTALS. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2018-10-24 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-10-24 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-10-23 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2018-10-24 09:44:10 | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING | | | TREES ON THE SITE, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED TO, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2018-07-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2018-07-20 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-07-18 |
Time |
15:30 |
Sent To |
PC |
|
| Notes |
| 2018-07-20 11:38:07 | PROVISO | | | | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY EXISTING | | | TREES ON THE SITE, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED TO, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT ? PLANNING DIVISION. | | | | | | 2. SEPARATE PERMIT REQUIRED FOR LANDSCAPING AND | | | IRRIGATION. | | | | | | 3. ALL FENCING SURROUNDING THE TRASH ENCLOSURES SHALL | | | BE SOLID/OPAQUE (CHAIN LINK WITH SLATS DOES NOT MEET | | | THIS REQUIREMENT). | | | | | | 4. ALL A/C CONDENSING UNITS SHALL BE A MINIMUM OF 11 | | | FEET FROM THE PROPERTY LINE. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | | PLANNER, AT [email protected] OR (561) 822-1448. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2018-04-27 |
|
|
Cont ID |
|
| Sent By |
JR |
Date |
2018-04-27 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2018-04-27 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2018-04-27 13:46:28 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 04.26.2018 | | | PERMIT NO.: 18040194 | | | ___________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT AN | | | APPLICATION FOR AN INFORMAL SITE PLAN REVIEW SHALL BE | | | APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT ? | | | PLANNING DIVISION. SUCH APPLICATION HAS ALREADY BEEN | | | SUBMITTED AND IS UNDER REVIEW. UPON APPROVAL OF THE | | | SITE PLAN REVIEW, ALL DRAWINGS SUBMITTED AS PART OF THE | | | BUILDING PERMIT SHALL MATCH THOSE WHICH WERE APPROVED. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
|