| 2018-05-23 10:10:07 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | PROJECT IS FOR SELECTIVE DEMOLITION, ADDITION AND |
| | INTERIOR BUILDOUT OF AN EXISTING BUILDING. |
| | TYPE OF CONSTRUCTION IS II B |
| | OCCUPANCY CLSSIFICATION IS B -BUSINESS |
| | |
| | 1. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED FOR |
| | THE 562 SQ. FT. ADDITION. |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. |
| | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE |
| | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN |
| | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP |
| | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE |
| | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY |
| | IMPACT FEES AT (561) 233-5025. |
| | |
| | 2. ROOFING PERMIT REQUIRED. |
| | PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING SYSTEM |
| | COMPONENTS OR DESIGNER MAY CHOOSE TO DEFER THESE |
| | SUBMITTALS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING SUBMITTALS. |
| | |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON |
| | THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING |
| | OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 3. PROVIDE ABOVE CEILING IDENTIFICATION FOR THE 2 HR |
| | FIRE WALL C1 PER FBC 703.7. |
| | 703.7 MARKING AND IDENTIFICATION. |
| | WHERE THERE IS AN ACCESSIBLE CONCEALED FLOOR, |
| | FLOOR-CEILING OR ATTIC SPACE, FIRE WALLS, FIRE |
| | BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE |
| | PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED |
| | OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN THE |
| | CONCEALED SPACE. SUCH IDENTIFICATION SHALL: |
| | 1.BE LOCATED WITHIN 15 FEET (4572 MM) OF THE END OF |
| | EACH WALL AND AT INTERVALS NOT EXCEEDING 30 FEET (9144 |
| | MM) MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION. |
| | 2. INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM) IN |
| | HEIGHT WITH A MINIMUM 3/8-INCH (9.5 MM) STROKE IN A |
| | CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING, |
| | ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL OPENINGS,? OR |
| | OTHER WORDING. |
| | |
| | 4. PROVIDE SOILS REPORT FOR ADDITION PER FBC 1803. |
| | 1803.1 GENERAL. |
| | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN |
| | ACCORDANCE WITH SECTION 1803.2 AND REPORTED IN |
| | ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE |
| | BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS |
| | INVOLVE IN-SITU TESTING, LABORATORY TESTING OR |
| | ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE |
| | CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL. |
| | 1803.2 INVESTIGATIONS REQUIRED. |
| | GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN |
| | ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5. |
| | |
| | 5. PROVIDE PHYSICIST REPORT FOR THE INSTALLATION OF |
| | LEAD LINED WALLS AND GLAZING. |
| | |
| | 6. EGRESS SEE PLAN PAGE A120 GENERAL NOTES FOR THE |
| | FOLLOWING- |
| | 6A. COMMON PATH OF TRAVEL SHALL BE PER FBC CHPT. 10 |
| | SEC. 1006 TABLE 1006.2.1 UNSPRINKLED. |
| | 6B. EXIT ACCESS TRAVEL DISTANCE SHALL BE PER FBC CHPT. |
| | 10 SEC. 1017 TABLE 1017.2 UNSPRINKLED. |
| | 6C. TRAVEL DISTANCE AND COMMON PATH OF TRAVEL DISTANCES |
| | ARE NOT IDENTIFIED ON EXIT PATHS. SEE NOTES 6A AND 6B |
| | ABOVE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |