Plan Review Details - Permit 18040095
Plan Review Stops For Permit 18040095
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By cthroop Date 2018-06-29 Time 16:16 Rev Time 0.00
Received By cthroop Date 2018-06-29 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 10:01 Rev Time 0.00
Received By cthroop Date 2018-05-16 Time 08:24 Sent To  
Notes
2018-05-23 10:10:07BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PROJECT IS FOR SELECTIVE DEMOLITION, ADDITION AND
 INTERIOR BUILDOUT OF AN EXISTING BUILDING.
 TYPE OF CONSTRUCTION IS II B
 OCCUPANCY CLSSIFICATION IS B -BUSINESS
  
 1. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED FOR
 THE 562 SQ. FT. ADDITION.
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
 2. ROOFING PERMIT REQUIRED.
 PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING SYSTEM
 COMPONENTS OR DESIGNER MAY CHOOSE TO DEFER THESE
 SUBMITTALS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3. PROVIDE ABOVE CEILING IDENTIFICATION FOR THE 2 HR
 FIRE WALL C1 PER FBC 703.7.
 703.7 MARKING AND IDENTIFICATION.
 WHERE THERE IS AN ACCESSIBLE CONCEALED FLOOR,
 FLOOR-CEILING OR ATTIC SPACE, FIRE WALLS, FIRE
 BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
 PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED
 OPENINGS OR PENETRATIONS SHALL BE EFFECTIVELY AND
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING IN THE
 CONCEALED SPACE. SUCH IDENTIFICATION SHALL:
 1.BE LOCATED WITHIN 15 FEET (4572 MM) OF THE END OF
 EACH WALL AND AT INTERVALS NOT EXCEEDING 30 FEET (9144
 MM) MEASURED HORIZONTALLY ALONG THE WALL OR PARTITION.
 2. INCLUDE LETTERING NOT LESS THAN 3 INCHES (76 MM) IN
 HEIGHT WITH A MINIMUM 3/8-INCH (9.5 MM) STROKE IN A
 CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING,
 ?FIRE AND/OR SMOKE BARRIER?PROTECT ALL OPENINGS,? OR
 OTHER WORDING.
  
 4. PROVIDE SOILS REPORT FOR ADDITION PER FBC 1803.
 1803.1 GENERAL.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTION 1803.2 AND REPORTED IN
 ACCORDANCE WITH SECTION 1803.6. WHERE REQUIRED BY THE
 BUILDING OFFICIAL OR WHERE GEOTECHNICAL INVESTIGATIONS
 INVOLVE IN-SITU TESTING, LABORATORY TESTING OR
 ENGINEERING CALCULATIONS, SUCH INVESTIGATIONS SHALL BE
 CONDUCTED BY A REGISTERED DESIGN PROFESSIONAL.
 1803.2 INVESTIGATIONS REQUIRED.
 GEOTECHNICAL INVESTIGATIONS SHALL BE CONDUCTED IN
 ACCORDANCE WITH SECTIONS 1803.3 THROUGH 1803.5.
  
 5. PROVIDE PHYSICIST REPORT FOR THE INSTALLATION OF
 LEAD LINED WALLS AND GLAZING.
  
 6. EGRESS SEE PLAN PAGE A120 GENERAL NOTES FOR THE
 FOLLOWING-
 6A. COMMON PATH OF TRAVEL SHALL BE PER FBC CHPT. 10
 SEC. 1006 TABLE 1006.2.1 UNSPRINKLED.
 6B. EXIT ACCESS TRAVEL DISTANCE SHALL BE PER FBC CHPT.
 10 SEC. 1017 TABLE 1017.2 UNSPRINKLED.
 6C. TRAVEL DISTANCE AND COMMON PATH OF TRAVEL DISTANCES
 ARE NOT IDENTIFIED ON EXIT PATHS. SEE NOTES 6A AND 6B
 ABOVE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-28 Cont ID  
Sent By jpearson Date 2018-06-28 Time 10:35 Rev Time 0.00
Received By jpearson Date 2018-06-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-06 Cont ID  
Sent By jpearson Date 2018-05-06 Time 13:10 Rev Time 0.00
Received By jpearson Date 2018-05-06 Time 13:09 Sent To  
Notes
2018-05-06 13:09:54CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. IN PANEL SCHEDULE FOR MDPB THERE IS A LOAD SHOWN FOR
 CTB. PANEL SCHEDULE FOR CTB SHOWS NO LOADS. PROVIDE
 CLARIFICATION AND/OR CORRECTION. FBC 107.2.1
 2. IN THE TRANSFORMER SCHEDULE, TCTB AND TXR SHOW A
 SECONDARY BREAKER AT 150 AMP WITH A FEEDER OF SIZE # 1.
 THIS WIRE SIZE IS NOT RATED FOR 150 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16)
 3. DESIGNATE ON PLAN WHICH AREAS ARE PATIENT CARE
 SPACES THAT WILL HAVE WIRING INSTALLED PER NEC 517.13.
 4. PANELS SHOWN WITH AN ISOLATED GROUND DO NOT SHOW THE
 ISOLATED GROUNDING CONDUCTOR INCLUDED IN THE CONDUIT.
 PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 250.96(B)
 5. ISOLATED GROUND RECEPTACLES ARE SHOWN IN
 MAMMOGRAPHY, BONE DENSITY, AND ULTRASOUND AREAS.
 SECTION 517.16 OF THE NEC STATES THAT ISOLATED GROUND
 RECEPTACLES SHALL NOT BE INSTALLED WITHIN A PATIENT
 CARE VICINITY. PROVIDE CORRECTION. NEC 517.16
 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C
 EQUIPMENT PER CODE IN CHILLER AREA. NEC 210.63
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. ARE THERE ANY WINDOW DISPLAYS THAT WOULD REQUIRE A
 SHOW WINDOW OUTLET? NEC 210.62
 10. PANEL SCHEDULE FOR PANEL F IS MISSING INFORMATION.
 PROVIDE COMPLETE PANEL SCHEDULE. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-06-28 Cont ID  
Sent By jpearson Date 2018-06-28 Time 10:36 Rev Time 0.00
Received By jpearson Date 2018-06-28 Time 10:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By scaldero Date 2018-06-07 Time 10:40 Rev Time 0.00
Received By scaldero Date 2018-06-07 Time 10:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-16 Cont ID  
Sent By scaldero Date 2018-04-16 Time 13:34 Rev Time 0.00
Received By scaldero Date 2018-04-16 Time 13:19 Sent To  
Notes
2018-04-16 13:33:58PERMIT # 18040095
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-29 Cont ID  
Sent By cthroop Date 2018-06-29 Time 16:17 Rev Time 0.00
Received By cthroop Date 2018-06-04 Time 16:23 Sent To I
Notes
2018-06-06 16:23:50C29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 10:54 Rev Time 0.00
Received By cthroop Date 2018-04-03 Time 10:57 Sent To I
Notes
2018-04-05 10:57:26C29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By shill Date 2018-07-03 Time 10:31 Rev Time 0.00
Received By shill Date 2018-07-03 Time 10:31 Sent To  
Notes
2018-07-03 10:31:5318-23373
 $4714.37 PAID
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 10:32 Rev Time 0.00
Received By cthroop Date 2018-05-16 Time 08:24 Sent To  
Notes
2018-05-23 10:33:29BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-05-07 Cont ID  
Sent By hmoser Date 2018-05-07 Time 13:04 Rev Time 0.00
Received By hmoser Date 2018-05-03 Time 14:29 Sent To  
Notes
2018-05-07 13:04:31PASS PROVISO
 1) REFER TO SECTION C403.2.4.3 SHUTOFF DAMPERS
 AUTOMATIC DAMPERS REQUIRED FOR FRESH AIR.
 2017 FLORIDA ENERGY CODE
 2) REFER TO SECTION 301.15 2017 FBC (M)
 WIND RESISTANCE. PROVIDE ENGINEER DETAIL
 ON CURB TIEDOWN TO ROOF AND RTU TIEDOWN
 TO CURB. DETAIL PROVIDED WITH THE PLAN ARE
 NOT COMPLETE.
 3) REFER TO SECTION 606.3 INSTALLATION. DUCT DETECTORS
 2017 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-808-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 11:13 Rev Time 0.00
Received By gjohnson Date 2018-06-29 Time 11:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-17 Cont ID  
Sent By gjohnson Date 2018-05-17 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2018-05-17 Time 08:48 Sent To  
Notes
2018-05-17 11:15:021ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WALLS AROUND THE MOP SINK IN JANITORS ROOM SHALL
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE
 FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE THAT IS
 NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2. SHT. A602 PLEASE PROVIDE DIMENSIONS FOR THE
 EMERGENCY SCUPPER IT SHALL COMPLY WITH FBC 1503.4.2.1
 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF DRAINAGE OF
 OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL
 BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES
 NOR MORE THAN 4 INCHES ABOVE THE FINISHED ROOF COVERING
 AND SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 3. SHT. A202 DETAIL #1 THE LOBBY COFFEE BAR SHALL
 COMPLY WITH FBC ACC 606.2 AND 606.3 HEIGHT. LAVATORIES
 AND SINKS SHALL BE INSTALLED WITH THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 4. P2.1 THE HD IN CHILLER ENCLOSURE SHALL BE COVERED TO
 PREVENT STORM WATER FROM DISCHARGING TO THE SANITARY
 SYSTEM AND CONDENSATE SHALL NOT DISCHARGE INTO THE
 SANITARY. PER CITY OF WEST PALM BEACH CODE OF
 ORDINANCES SEC. 90-126(5)
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-06-29 Cont ID  
Sent By cthroop Date 2018-06-29 Time 16:16 Rev Time 0.00
Received By cthroop Date 2018-06-29 Time 14:46 Sent To  
Notes
2018-06-29 16:17:34PROVISO - ROOFING SUBMITTALS TO BE DEFERRED. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-23 Cont ID  
Sent By cthroop Date 2018-05-23 Time 10:33 Rev Time 0.00
Received By cthroop Date 2018-05-22 Time 12:19 Sent To  
Notes
2018-05-23 10:35:43BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOFING
 SYSTEM OR DESIGNER MAY CHOOSE TO DEFER THESE SUBMITTAL.
  
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-22 Cont ID  
Sent By jroach Date 2018-06-22 Time 15:30 Rev Time 0.00
Received By jroach Date 2018-06-22 Time 15:30 Sent To  
Notes
2018-06-22 15:31:07ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.22.2018
 PERMIT NO.: 18040095
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE PROPOSED CHILLER ENCLOSURE SHALL BE SET BACK AT
 LEAST TWO (2) FEET (TO THE SOUTH) FROM THE FRONT FA?ADE
 OF THE PROPOSED BUILDING ADDITION.
  
 2. CONTINGENT UPON APPROVAL FROM THE ADJACENT PROPERTY
 OWNER (TO THE EAST), THE DRIVEWAY CONNECTION BETWEEN
 THE TWO PROPERTIES SHALL BE REMOVED AND THE CURBING
 SHALL BE EXTENDED, AS IDENTIFIED IN THE ?ALTERNATE
 DRIVEWAY EXHIBIT? PROVIDED ON SHEET C1.00 (SITE PLAN).
  
 3. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY/COMPLETION OF THE PROPOSED ADDITION, BIKE
 RACKS SHALL BE INSTALLED ON THE SITE (IF NONE CURRENTLY
 EXIST). THE LOCATION AND STYLE OF THE BIKE RACKS SHALL
 BE REVIEWED AND APPROVED BY THE CITY?S PLANNING
 DIVISION AND INCORPORATED INTO ANY APPLICABLE BUILDING
 PERMITS.
  
 4. PRIOR TO THE REMOVAL OF ANY EXISTING TREES, A TREE
 ALTERATION PERMIT APPLICATION SHALL BE SUBMITTED TO,
 AND APPROVED BY, THE CITY?S DEVELOPMENT SERVICES
 DEPARTMENT ? PLANNING DIVISION.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-27 Cont ID  
Sent By JR Date 2018-04-27 Time 13:42 Rev Time 0.00
Received By jroach Date 2018-04-27 Time 13:42 Sent To  
Notes
2018-04-27 13:42:33ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.27.2018
 PERMIT NO.: 18040095
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT A MINOR
 AMENDMENT TO THE HOME DEPOT COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT ? PLANNING DIVISION. SUCH
 APPLICATION HAS ALREADY BEEN SUBMITTED AND IS UNDER
 REVIEW. UPON APPROVAL OF THE SITE PLAN REVIEW, ALL
 DRAWINGS SUBMITTED AS PART OF THE BUILDING PERMIT SHALL
 MATCH THOSE WHICH WERE APPROVED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved