Plan Review Details - Permit 18040024
Plan Review Stops For Permit 18040024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-06-05 Cont ID  
Sent By cthroop Date 2018-06-05 Time 15:52 Rev Time 0.00
Received By cthroop Date 2018-06-05 Time 14:56 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-10 Cont ID  
Sent By cthroop Date 2018-04-10 Time 10:44 Rev Time 0.00
Received By cthroop Date 2018-04-09 Time 17:30 Sent To  
Notes
2018-04-10 10:48:00BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL OF MECHANICAL DEVICE USED TO OPERATE
 LOUVERS,
 2. PROVIDE DETAIL OF MECHANICAL/ELECTRICAL DEVICE USED
 TO OPEN LOUVERS AT 45MPH.
 3. IF DEVICE IS ELECTRICALLY ACTUATED, PROVIDE
 ELECTRICAL PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-20 Cont ID  
Sent By jleahy Date 2018-06-20 Time 13:03 Rev Time 0.00
Received By jleahy Date 2018-06-20 Time 13:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-06-07 Cont ID  
Sent By jleahy Date 2018-06-07 Time 07:54 Rev Time 0.00
Received By jleahy Date 2018-06-07 Time 07:54 Sent To  
Notes
2018-06-07 07:57:24FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 400.8 USES NOT PERMITTED
  
 UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS
 AND CABLES
 SHALL NOT BE USED FOR THE FOLLOWING:
  
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A
 STRUCTURE.
  
 SUBMIT CUT SHEETS ON THE ELECTRICAL EQUIPMENT SHOWING
 THE LISTING. 110.3

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By fmittner Date 2018-06-04 Time 14:16 Rev Time 0.00
Received By fmittner Date 2018-06-04 Time 14:16 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By fmittner Date 2018-04-06 Time 15:15 Rev Time 0.00
Received By fmittner Date 2018-04-06 Time 15:15 Sent To B
Notes
2018-04-06 15:16:04IN HISTORIC DISTRICT REQUIRES COA. FHM SPOKE TO
 DESIGNER, WILL SUBMIT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-20 Cont ID  
Sent By jleahy Date 2018-06-20 Time 13:03 Rev Time 0.00
Received By jleahy Date 2018-06-19 Time 11:43 Sent To  
Notes
2018-06-20 11:44:05GIVEN TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-07 Cont ID  
Sent By jleahy Date 2018-06-07 Time 07:57 Rev Time 0.00
Received By jleahy Date 2018-05-22 Time 13:30 Sent To  
Notes
2018-05-23 13:30:53RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-10 Cont ID  
Sent By cthroop Date 2018-04-10 Time 10:48 Rev Time 0.00
Received By cthroop Date 2018-04-02 Time 09:45 Sent To I
Notes
2018-04-03 09:46:12ROUTED TO HISTORIC INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-04 Cont ID  
Sent By fmittner Date 2018-06-04 Time 14:16 Rev Time 0.00
Received By fmittner Date 2018-06-04 Time 14:16 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By fmittner Date 2018-04-06 Time 15:16 Rev Time 0.00
Received By fmittner Date 2018-04-06 Time 15:16 Sent To  
Notes
2018-04-06 15:17:26BUILDINGS CANNOT BE CONNECTED WITH SOLID ROOF AS IS
 ACHEIVED WHEN LOUVERS ARE IN CLOSED POSITION.