Plan Review Details - Permit 18040016
Plan Review Stops For Permit 18040016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By jgomez Date 2018-05-17 Time 11:44 Rev Time 0.00
Received By jgomez Date 2018-05-17 Time 11:25 Sent To  
Notes
2018-05-17 11:32:08FLOORING UNDERLAYMENT.
 SUPER SAM 125 SOUND CONTROL MEMBRANE TEST REPORTS ARE
 IN CITY'S FILES (F DRIVE) UNDER FLOOR UNDERLAYMENT.
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- NEED SEPARATE FIRE SPRINKLER PERMIT FOR THE
 RELOCATION OF SPRINKLER HEADS AS SPECIFIED ON PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By jgomez Date 2018-04-06 Time 17:46 Rev Time 0.00
Received By jgomez Date 2018-04-06 Time 08:16 Sent To  
Notes
2018-04-06 14:43:24BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE TWO COPIES OF THE TEST DONE FOR: FLAME
 SPREAD INDEX, SMOKE DEVELOPED INDEX, SOUND TRANSMISSION
 CLASS (STC) AND IMPACT INSULATION CLASS (IIC) OF THE
 SUPER SAM 125 SOUND CONTROL MEMBRANE SUBMITTED.
 2- NEED SEPARATE FIRE SPRINKLER PERMIT FOR THE
 RELOCATION OF SPRINKLER HEADS AS SPECIFIED ON PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-11 Cont ID  
Sent By jpearson Date 2018-05-11 Time 15:45 Rev Time 0.00
Received By jpearson Date 2018-05-11 Time 15:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-23 Cont ID  
Sent By jpearson Date 2018-04-23 Time 14:26 Rev Time 0.00
Received By jpearson Date 2018-04-23 Time 13:39 Sent To I
Notes
2018-04-23 14:26:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (BOTH
 COPIES) IS REQUIRED TO BEAR THE NAME AND BE SIGNED AND
 SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN.
 PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
 2. THERE IS A BLOCK NOTE ABOVE THE DESIGN
 PROFESSIONAL?S NAME THAT STATES THE ELECTRICAL
 CONTRACTOR IS RESPONSIBLE FOR CONFORMANCE OF THIS PLAN
 TO THE 2014 FBC AND THE 2011 NEC, WHICH ARE NOT THE
 CURRENT CODES AND CONFLICT WITH STATEMENTS LOCATED
 ELSEWHERE ON PLAN. PROVIDE CORRECTION. FBC PREFACE
 (ALSO SEE CURRENT CODES ABOVE)
 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE
 CORRECTION, A NOTE WILL SUFFICE. NEC 210.12
 4. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 5. RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8
 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 7. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. THIS CIRCUIT IS
 NOT LISTED IN PANEL SCHEDULE. PROVIDE CORRECTION. NEC
 210.11(C)(3)
 8. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. THE
 MASTER BATH DOES NOT SHOW THE REQUIRED RECEPTACLE
 OUTLET. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-04-27 Cont ID  
Sent By pleduc Date 2018-04-27 Time   Rev Time 0.00
Received By pleduc Date 2018-04-27 Time 14:04 Sent To  
Notes
2018-04-27 15:09:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY WORK ON THE FIRE SPRINKLER AND/OR FIRE ALARM
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By pleduc Date 2018-04-09 Time   Rev Time 0.00
Received By pleduc Date 2018-04-09 Time 13:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-21 Cont ID  
Sent By tklarge Date 2018-05-21 Time 10:07 Rev Time 0.00
Received By tklarge Date 2018-04-25 Time 13:22 Sent To  
Notes
2018-04-26 13:23:02B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-04-02 Time 11:27 Sent To  
Notes
2018-04-03 11:27:43B05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cmontell Date 2018-05-09 Time 14:32 Sent To  
Notes
2018-05-09 14:38:04PER NOTE ON PLAN
  
 "HVAC CONTRACTOR TO PROVIDE LAYOUT W/MECHANICAL PERMIT
 APPLICATION"
  
 NEED SEPARATE PRIMARY MECHANICAL PERMIT.
  
 ****************NOT SUB PERMIT***************
  
 CHRIS MONTELLO
 561-805-6733

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-16 Cont ID  
Sent By ccole Date 2018-04-16 Time 11:39 Rev Time 0.00
Received By ccole Date 2018-04-16 Time 11:39 Sent To  
Notes
2018-04-16 11:41:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18040016
 4/16/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE MECHANICAL PLANS OR WRITE "NO MECHANICAL" ON
 THE PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By tklarge Date 2018-05-21 Time 10:07 Rev Time 0.00
Received By tklarge Date 2018-05-21 Time 09:41 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-17 Cont ID  
Sent By gjohnson Date 2018-04-17 Time 10:36 Rev Time 0.00
Received By gjohnson Date 2018-04-17 Time 09:05 Sent To  
Notes
2018-04-17 10:43:401ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. 01 NOTE ON TUB IN LAUNDRY ROOM STATES TUB TO BE
 REPLACED SHT02 SHOW A WASHER AND DRYER IN THAT LOCATION
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. THE SINK IN LAUNDRY ROOM IS SHOWN IN DEFERENT
 LOCATION FROM SHT 02 TO SHT E/P1 PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  