Plan Review Details - Permit 18031395
Plan Review Stops For Permit 18031395
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2019-12-04 Cont ID  
Sent By jgomez Date 2019-12-04 Time 11:18 Rev Time 0.00
Received By jgomez Date 2019-12-04 Time 11:18 Sent To  
Notes
2019-12-04 11:21:10 
 REVISED 12/04/19 AND RESPONDED E-MAIL TO PAUL HALL
 (CONTRACTOR) PROVIDING CLARIFICATIONS. JG.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
  
 CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE. THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 2- OK
  
 ORIGINAL COMMENT.
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 RESPONSE:
 THE REVISED PLANS SPECIFY 2 HOUR WALL FOR THE SOUTH AND
 EAST EXTERIOR WALLS ONLY. THIS IS INCORRECT. IF THE
 CONSTRUCTION TYPE IS III-B, THEN ALL 4 EXTERIOR BEARING
 WALLS OF THIS BUILDING NEED TO BE 2 HOUR. REVISE PLANS
 AS REQUIRED.
 ALSO, PROVIDE COMPLETE WALL DETAIL OF THE SPECIFIED 2
 HOUR WALL ASSEMBLY U905. NO DETAIL WAS PROVIDED AS
 REQUESTED ON PREVIOUS CHECKLISTS.
  
  
 4- OK.
 5- FBC-ACCESSIBILITY.
 A) OK
 B) OK
 C)OK
  
 ORIGINAL COMMENT:
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 RESPONSE (REVISED 12/04/19 FOR CLARIFICATION):
 SECOND FLOOR CEILING WAS REPLACED WITH 2' X 4'
 ACOUSTICAL CEILING. NEED TO REVISE DETAILS W2 AND W3 ON
 SHEET LS-1 TO MATCH NEW CEILING SPECIFICATIONS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- OK.
 8- OK
 9- OK.
 10- OK
  
 11- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER STATES THAT
 A SIGNATURE WAS PROVIDED. THERE ARE NO SIGNATURES OF
 THE ARCHITECT ON THE ENERGY FORMS SUBMITTED.
 ALSO, ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE THE
 ARCHITECT IS DESIGNING THE BUILDING, ELECTRICAL AND
 PLUMBING SYSTEMS. PROVIDE SIGNATURE AND LICENSE NUMBERS
 ON EACH TRADE THE ARCHITECT IS RESPONSIBLE FOR THE
 DESIGN.
 NOTE: AT THE BOTTOM OF THE CERTIFICATIONS PAGE THERE IS
 A FOOTNOTE STATING THAT THE NAMES AND REGISTRATION
 NUMBERS MAY BE USED WHERE ALL THE INFORMATION IS
 CONTAINED IN THE SIGNED AND SEALED PLANS. THIS MAY BE
 DONE ALSO. BUT MAKE SURE EACH TRADE IS SHOWING THE
 DESIGNER OF RECORD.
  
 NEW COMMENT BASED ON CERTIFICATION PAGE SUBMITTED AT
 THIS TIME:
 THE OWNER SIGNED ON THE OWNER/AGENT SPACE LAST TIME.
 THIS TIME THIS SPACE WAS SIGNED BY SOMEONE ELSE. ONLY
 THE OWNER, THE OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNED BY THE OWNER CAN SIGN THE FORM.
 OWNER NEEDS TO SIGN THE FORM OR SINCE THE PERSON
 SIGNING ON THIS SPACE IS NOT THE ARCHITECT, THEN
 PROVIDE PROOF THAT THE PERSON SIGNING THE FORM IS THE
 OWNER'S LEGALLY DESIGNATED AGENT AS REQUIRED BY SEC.
 C103.2 FBC-ENERGY CONSERVATION.
  
  
 B) OK.
 C) OK
 D) OK
  
 ORIGINAL COMMENT:
 E)PLANS WERE REVISED. LOCATION OF WINDOWS CHANGED.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED. NOW THERE IS NOT INFORMATION FOR THE
 WINDOWS. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 12- OK.
 13- OK.
 14- OK.
  
 ORIGINAL COMMENT:
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 15(1)- PROVIDE ICC EVALUATION REPORT FOR ICYNENE SPRAY
 INSULATION SPECIFIED ON PLANS. AND ARCHITECT OF RECORD
 TO REVIEW/APPROVE PRIOR T SUBMITTAL. SEC. 2603 FBC.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
  
 16- OK.
 17- OK.
  
 18- TRUSS PACKAGE (REVISED 12/04/19):
 IT IS MY UNDERSTANDING THAT TRUSS TO TRUSS CONNECTIONS
 ARE THE RESPONSIBILITY OF THE TRUSS ENGINEER (ANSI/TPI
 1). NOTE #9 OF HIP GIRDER A10 AND NOTE # 6 OF FLOOR
 GIRDER FG1 SPECIFY THAT THE SELECTION OF CONNECTORS IS
 THE RESPONSIBILITY OF OTHERS. THESE ARE TRUSS TO TRUSS
 CONNECTIONS, THEREFORE THE TRUSS ENGINEER NEEDS TO
 SPECIFY THE CONNECTORS AND PROPERLY SIGN AND SEAL THE
 SHEETS WERE CONNECTOR IS SPECIFIED.
 ARCHITECT RESPONSE LETTER STATES THAT "SEE DETAIL
 1/LS-1 FOR DETAIL, AND ATTACHED TRUSS PACKAGE". THIS
 DETAIL IS INCORRECT. THE HANGERS ARE NOT BY THE TRUSS
 COMPANY. THEY ARE THE RESPONSIBILITY OF THE TRUSS
 ENGINEER.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ONCE TRUSS PACKAGE ITEMS ARE
 CORRECTED.
  
 20- OK.
  
 21- WELDED OR BOLTED CONNECTIONS (FYI)
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-11-27 Cont ID  
Sent By jgomez Date 2019-11-27 Time 09:05 Rev Time 0.00
Received By jgomez Date 2019-11-26 Time 13:08 Sent To  
Notes
2019-11-27 09:06:05CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE. THIRD
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES -
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  
 2- OK
  
 ORIGINAL COMMENT.
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 RESPONSE:
 THE REVISED PLANS SPECIFY 2 HOUR WALL FOR THE SOUTH AND
 EAST EXTERIOR WALLS ONLY. THIS IS INCORRECT. IF THE
 CONSTRUCTION TYPE IS III-B, THEN ALL 4 EXTERIOR BEARING
 WALLS OF THIS BUILDING NEED TO BE 2 HOUR. REVISE PLANS
 AS REQUIRED.
 ALSO, PROVIDE COMPLETE WALL DETAIL OF THE SPECIFIED 2
 HOUR WALL ASSEMBLY U905. NO DETAIL WAS PROVIDED AS
 REQUESTED ON PREVIOUS CHECKLISTS.
  
  
 4- OK.
 5- FBC-ACCESSIBILITY.
 A) OK
 B) OK
 C)OK
  
 ORIGINAL COMMENT:
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 RESPONSE (REVISED 12/04/19 FOR CLARIFICATION):
 SECOND FLOOR CEILING WAS REPLACED WITH 2' X 4'
 ACOUSTICAL CEILING. NEED TO REVISE DETAILS W2 AND W3 ON
 SHEET LS-1 TO MATCH NEW CEILING SPECIFICATIONS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 7- OK.
 8- OK
 9- OK.
 10- OK
  
 11- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. ARCHITECT'S RESPONSE LETTER STATES THAT
 A SIGNATURE WAS PROVIDED. THERE ARE NO SIGNATURES OF
 THE ARCHITECT ON THE ENERGY FORMS SUBMITTED.
 ALSO, ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE THE
 ARCHITECT IS DESIGNING THE BUILDING, ELECTRICAL AND
 PLUMBING SYSTEMS. PROVIDE SIGNATURE AND LICENSE NUMBERS
 ON EACH TRADE THE ARCHITECT IS RESPONSIBLE FOR THE
 DESIGN.
 NOTE: AT THE BOTTOM OF THE CERTIFICATIONS PAGE THERE IS
 A FOOTNOTE STATING THAT THE NAMES AND REGISTRATION
 NUMBERS MAY BE USED WHERE ALL THE INFORMATION IS
 CONTAINED IN THE SIGNED AND SEALED PLANS. THIS MAY BE
 DONE ALSO. BUT MAKE SURE EACH TRADE IS SHOWING THE
 DESIGNER OF RECORD.
  
 NEW COMMENT BASED ON CERTIFICATION PAGE SUBMITTED AT
 THIS TIME:
 THE OWNER SIGNED ON THE OWNER/AGENT SPACE LAST TIME.
 THIS TIME THIS SPACE WAS SIGNED BY SOMEONE ELSE. ONLY
 THE OWNER, THE OWNER'S ARCHITECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNED BY THE OWNER CAN SIGN THE FORM.
 OWNER NEEDS TO SIGN THE FORM OR SINCE THE PERSON
 SIGNING ON THIS SPACE IS NOT THE ARCHITECT, THEN
 PROVIDE PROOF THAT THE PERSON SIGNING THE FORM IS THE
 OWNER'S LEGALLY DESIGNATED AGENT AS REQUIRED BY SEC.
 C103.2 FBC-ENERGY CONSERVATION.
  
  
 B) OK.
 C) OK
 D) OK
  
 ORIGINAL COMMENT:
 E)PLANS WERE REVISED. LOCATION OF WINDOWS CHANGED.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED. NOW THERE IS NOT INFORMATION FOR THE
 WINDOWS. PROVIDE COMPLETE INFORMATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 12- OK.
 13- OK.
 14- OK.
  
 ORIGINAL COMMENT:
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 15(1)- PROVIDE ICC EVALUATION REPORT FOR ICYNENE SPRAY
 INSULATION SPECIFIED ON PLANS. AND ARCHITECT OF RECORD
 TO REVIEW/APPROVE PRIOR T SUBMITTAL. SEC. 2603 FBC.
  
 RESPONSE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
  
 16- OK.
 17- OK.
  
 18- TRUSS PACKAGE (REVISED 12/04/19):
 IT IS MY UNDERSTANDING THAT TRUSS TO TRUSS CONNECTIONS
 ARE THE RESPONSIBILITY OF THE TRUSS ENGINEER (ANSI/TPI
 1). NOTE #9 OF HIP GIRDER A10 AND NOTE # 6 OF FLOOR
 GIRDER FG1 SPECIFY THAT THE SELECTION OF CONNECTORS IS
 THE RESPONSIBILITY OF OTHERS. THESE ARE TRUSS TO TRUSS
 CONNECTIONS, THEREFORE THE TRUSS ENGINEER NEEDS TO
 SPECIFY THE CONNECTORS AND PROPERLY SIGN AND SEAL THE
 SHEETS WERE CONNECTOR IS SPECIFIED.
 ARCHITECT RESPONSE LETTER STATES THAT "SEE DETAIL
 1/LS-1 FOR DETAIL, AND ATTACHED TRUSS PACKAGE". THIS
 DETAIL IS INCORRECT. THE HANGERS ARE NOT BY THE TRUSS
 COMPANY. THEY ARE THE RESPONSIBILITY OF THE TRUSS
 ENGINEER.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ONCE TRUSS PACKAGE ITEMS ARE
 CORRECTED.
  
 20- OK.
  
 21- WELDED OR BOLTED CONNECTIONS (FYI)
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-03-18 Cont ID  
Sent By jgomez Date 2019-03-15 Time 19:05 Rev Time 0.00
Received By jgomez Date 2019-03-15 Time 09:25 Sent To  
Notes
2019-03-14 18:17:21 
 CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE. SECOND
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
  
 1- IMPACT FEES - PAPER SUBMITTALS
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 ORIGINAL COMMENT:
 2- PROVIDE SITE GRADING PLAN (INCLUDING PROPOSED LOT
 DRAINAGE) SHOWING COMPLIANCE WITH SEC. 1804.4
 FBC-BUILDING AND SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: DRAWINGS REFERENCED ON GENERAL SITE NOTE #5 ON
 SHEET SP-1 WERE NOT SUBMITTED. ALSO, COORDINATED
 DRAWINGS WITH PROPOSED RETAINING WALLS TO AVOID
 CONFLICTS/DELAYS. SEE SHEET SP-1.
  
 RESPONSE:
 A) ONLY ON SET OF CIVIL DRAWINGS WAS SUBMITTED. NEED
 TWO COPIES. SEC. 107.1 CITY AMENDMENTS.
  
 B) IT LOOKS LIKE THREE IS A CONFLICT BETWEEN THE CIVIL
 DRAWINGS AND ARCHITECTURAL DRAWINGS REGARDING THE
 RETENTION WALLS. THERE ARE TWO DIFFERENT TYPE OF
 RETENTION WALLS. CLARIFY/REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT.
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "TYPE III-B
 CONSTRUCTION AS NOTED WILL ALLOW THE 2-STRY OFFICE.
 EXTERIOR WALL SHALL BE 2HR. PROTECTED". THIS DOESN'T
 ADDRESS THE REQUIRED 2 HOUR WALL FOR TYPE III
 CONSTRUCTION. PLANS DON'T SHOW ANY DETAILS AND
 SPECIFICATIONS FOR TWO HOUR CONCRETE BLOCK WALLS. NOT
 ALL CONCRETE BLOCK IS TWO HOUR RATED.
  
 ORIGINAL COMMENT:
 B) SQUARE FEET OF ALLOWED OPENINGS SPECIFIED IN THE
 DESIGN CRITERIA DON'T MATCH PLANS. REVISE AS REQUIRED
 TO MATCH. SEC. 705.8 FBC-BUILDING.
  
 RESPONSE:
 OPENINGS LOCATION WERE REVISED. IT LOOKS LIKE
 INFORMATION GIVEN IS FOR THE WEST WALL. IF SO, IS
 MISSING THE DOOR OPENING ON THE FIRST FLOOR. REVISE AS
 REQUIRED.
  
 C) OK.
  
 ORIGINAL COMMENT:
 D) REVISE THE GENERAL BUILDING LIMITATIONS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. TABLE 503 IS INCORRECT.
 THIS BUILDING HAS A MIXED OCCUPANCY. NEED TO PROVIDE
 INFORMATION FOR EACH OCCUPANCY. USE TABLE 504.3, TABLE
 504.4 AND TABLE 506.2 FBC 2017 FOR CORRECT AND CURRENT
 CODE INFORMATION AND REVISE AS REQUIRED.
  
 RESPONSE:
 THIS WILL BE REVIEWED BASED ON THE CLARIFICATION
 REQUIRED BY ITEM #3(A) ABOVE REGARDING CONSTRUCTION
 TYPE.
  
 E) OK.
  
 F) OK.
  
 G) OK.
  
 4- OK.
  
 5- FBC-ACCESSIBILITY.
 A) OK
 B) OK
 C)OK
  
 ORIGINAL COMMENT:
 A) PROVIDE COMPLIANCE WITH THE VERTICAL ACCESSIBILITY
 REQUIREMENTS FOR THE SECOND STORY OFFICE AS REQUIRED BY
 SEC. 201.1.1 FBC-ACCESSIBILITY. OR SHOW IN PLANS
 COMPLIANCE WITH ANY EXCEPTION.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "201.1.1(3) OCCUPANT
 LOAD LESS THAN 5 PERSONS: SO NOTED ON THE PLAN". PLANS
 DON'T SHOW COMPLIANCE WITH THIS EXCEPTION. THERE ARE
 TWO REQUIREMENTS TO MEET THIS EXCEPTION. FIRST OF ALL,
 IT NEEDS TO BE CLEAR THAT THE OFFICE IS NOT OPEN TO THE
 PUBLIC. THE SECOND REQUIREMENTS IS THAT IT CAN NO HOUSE
 MORE THAN 5 PERSONS. ONLY THE SECOND REQUIREMENT WAS
 MET BY THE SIZE OF THE OFFICE. IN ORDER TO APPLY THIS
 EXCEPTION IT MUST BE CLEARLY NOTED ON PLANS BY THE
 OFFICE AREA THAT THE OFFICE CAN NOT OPEN TO THE PUBLIC.
 REVISE PLANS AS REQUIRED.
  
 ORIGINAL COMMENT:
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE ROUTE SHOWING COMPLIANCE WITH SEC.
 206-FBC-ACCESSIBILITY.
 ACCESSIBLE ROUTE FROM PARKING TO THE BUILDING ENTRANCE
 (SEC. 402 AND SEC. 404 FBC-ACCESSIBILITY).
  
 RESPONSE:
 THE BUILDING MAIN ENTRANCE DOESN'T SEEM TO COMPLY. SHOW
 COMPLIANCE WITH THE CHANGE OF LEVEL AT THE ENTRANCE.
 SHOW MANEUVERING CLEARANCES (INCLUDING TURNING
 CLEARANCES) AT THE VESTIBULE AREA LEADING TO THE
 WAREHOUSE AREA.
  
 ORIGINAL COMMENT:
 C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 504-FBC-ACCESSIBILITY.
 INCLUDE THE NOSING SPECIFICATIONS.
  
 RESPONSE:
 REVISE NOSING DETAIL ON SHEET A-2. THE UNDERSIDE OF
 NOSING NEEDS TO COMPLY WITH SEC. 504.5
 FBC-ACCESSIBILITY.
  
 ORIGINAL COMMENT:
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 RESPONSE:
 ATTIC ACCESS WAS REMOVED. ATTIC ACCESS IS REQUIRED BY
 SEC. 1209.2 FBC.
  
 7- SHEET A-1:
 A) OK.
  
 B) OK.
  
 8- OK.
  
 9- OK.
  
 10- SOIL TEST REPORT:
 A) OK.
  
 B) OK.
  
 C) OK.
  
 D) OK.
  
 11- ENERGY CALCULATIONS:
 ORIGINAL COMMENT:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 ARCHITECT'S RESPONSE LETTER STATES "CERTIFICATION WITH
 NAME AND LICENSE NUMBER SHOWN". ENERGY CALCULATIONS
 SUBMITTED DON'T HAVE THE SIGNATURE AND LICENSE NUMBER
 OF THE ARCHITECT. ACCORDING TO PLANS SUBMITTED, IT
 LOOKS LIKE THE ARCHITECT IS DESIGNING THE BUILDING,
 ELECTRICAL AND PLUMBING SYSTEMS. PROVIDE SIGNATURE AND
 LICENSE NUMBERS ON EACH TRADE AS REQUIRED.
  
 B) OK.
  
 ORIGINAL COMMENT:
 C) REVISE BUILDING ORIENTATION SHOWN ON PAGE 17 OF 22
 TO MATCH PLANS. NOTE: PLANS ARE DRAWN WITH NORTH ARROW
 POINTING SOUTH.
  
 RESPONSE:
 WHY ARE THERE TWO EAST WALLS?
  
 ORIGINAL COMMENT:
 D) REVISE WALL TYPES AND INSULATION INFORMATION SHOWN
 ON PAGE 17 OF 22 TO MATCH PLANS. ALSO, NEED TO PROVIDE
 INFORMATION FOR RAISED FLOOR ABOVE THE FIRST FLOOR
 UNCONDITIONED WAREHOUSE AREA. NOTE: COORDINATE WITH
 ARCHITECT.
  
 RESPONSE:
 WHY ARE THERE TWO EAST WALLS?.
 PAGE 19 OF 22 DOESN'T SHOW ANY INFORMATION FOR THE
 RAISED FLOOR ABOVE WAREHOUSE.
  
 NEW COMMENT:
 E)PLANS WERE REVISED. LOCATION OF WINDOWS CHANGED.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
  
 12- OK.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) OK.
  
 B) OK.
  
 14- OK.
  
 ORIGINAL COMMENT:
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 APPROVED ASSEMBLY WAS NOT MARKED/IDENTIFIED. APPROVED
 ASSEMBLIES ARE ON PAGE 5 OF 8 TO PAGE 7 OF 8. NOTE: ALL
 THESE ASSEMBLIES ARE FOR ASSEMBLIES WITH INSULATION.
 PLANS DON'T SHOW ANY FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION. THE INSULATION SHOWN ON PLANS IS FOR
 ICYNENE INSULATION SPRAYED AT THE BOTTOM OF ROOD DECK.
 IF USING A FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION , THEN ARCHITECTURAL PLANS NEED TO BE
 REVISED SHOWING THE ADDITIONAL INSULATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENT ( I APOLOGIZE . I FORGOT TO ASK FOR IT ON
 THE PREVIOUS REVIEW):
 15(1)- PROVIDE ICC EVALUATION REPORT FOR ICYNENE SPRAY
 INSULATION SPECIFIED ON PLANS. AND ARCHITECT OF RECORD
 TO REVIEW/APPROVE PRIOR T SUBMITTAL. SEC. 2603 FBC.
  
 16- OK.
  
 17- OK.
  
 18- TRUSS PACKAGE:
 A)OK.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C) TRUSS PACKAGE COVER LETTER NEEDS TO PROVIDE THE
 INFORMATION OF THE PROFESSIONAL DESIGNER OF RECORD AS
 REQUIRED BY FAC 61G15-23.003.
  
 RESPONSE.
 NOT RESPONSE. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) TRUSS LAYOUT SHOW THE TRUSS TO TRUSS STRUCTURAL
 CONNECTORS. TRUSS ENGINEER TO SIGN AND SEAL TRUSS
 LAYOUT AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 RESPONSE:
 NOT ADDRESSED. TRUSS LAYOUT SHOW THE FLOOR TRUSS
 CONNECTORS RESTING ON THE FLOOR GIRDER. AND THERE ARE
 NOT CONNECTORS SPECIFIED ON THE INDIVIDUAL TRUSSES
 RESTING ON THE HIP GIRDER AND DIAGONAL HIP GIRDER. NOTE
 #9 OF INDIVIDUAL TRUSSES STATES THAT "HE
 DESIGN/SELECTION OF SUCH CONNECTION DEVICE(S) IS THE
 RESPONSIBILITY OF OTHERS". WHY? ISN'T THE TRUSS TO
 TRUSS CONNECTIONS THE RESPONSIBILITY OF THE TRUSS
 ENGINEER OF RECORD?. ALL STRUCTURAL CONNECTORS
 SPECIFIED NEED TO HAVE THE SEAL AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 E)OK.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: THIS APPLIES ONCE TRUSS PACKAGE ITEMS ARE
 CORRECTED.
  
 ORIGINAL COMMENT:
 20- VALUE DECLARED I THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED. SEC. 109.3 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. VALUATION TO INCLUDE ALL
 LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND
 DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $155,360. THE
 PERMIT FEE BALANCE IS $3250.30.
  
 21- WELDED OR BOLTED CONNECTIONS (FYI)
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
 22-PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 NOTE: ENTER BUILDING INFORMATION ON FRONT SCREEN FIELDS
 WHEN PLANS ARE REVISED SHOWING CORRECT CONSTRUCTIOIN
 TYPE AND RESUBMITTED. JG.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jgomez Date 2018-05-09 Time 17:37 Rev Time 0.00
Received By jgomez Date 2018-05-09 Time 07:50 Sent To  
Notes
2018-05-10 18:06:15CONSTRUCTION OF NEW OFFICE/WAREHOUSE STRUCTURE.
 BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
 2- PROVIDE SITE GRADING PLAN (INCLUDING PROPOSED LOT
 DRAINAGE) SHOWING COMPLIANCE WITH SEC. 1804.4
 FBC-BUILDING AND SEC. 107.2.5 CITY AMENDMENTS.
 NOTE: DRAWINGS REFERENCED ON GENERAL SITE NOTE #5 ON
 SHEET SP-1 WERE NOT SUBMITTED. ALSO, COORDINATED
 DRAWINGS WITH PROPOSED RETAINING WALLS TO AVOID
 CONFLICTS/DELAYS. SEE SHEET SP-1.
  
 3- SHEET LS-1:
 A) TYPE III-B CONSTRUCTION TYPE SPECIFIED IN THE DESIGN
 CRITERIA REQUIRES 2 HR FIRE RESISTANCE RATING FOR THE
 EXTERIOR WALLS. SEE BY TABLE 601 FBC-BUILDING. PROVIDE
 COMPLETE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE WITH
 THE 2 HR FIRE RATED ASSEMBLY.
  
 B) SQUARE FEET OF ALLOWED OPENINGS SPECIFIED IN THE
 DESIGN CRITERIA DON'T MATCH PLANS. REVISE AS REQUIRED
 TO MATCH.
 SEC. 705.8 FBC-BUILDING.
  
 C) TABLE 1004.1.2 OCCUPANT LOAD FOR WAREHOUSES IS 500
 GROSS. PROVIDE JUSTIFICATION WHY IN THE DESIGN CRITERIA
 IS USING AN OCCUPANT LOAD OF 300. REVISE AS REQUIRED.
  
 D) REVISE THE GENERAL BUILDING LIMITATIONS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. TABLE 503 IS INCORRECT.
 THIS BUILDING HAS A MIXED OCCUPANCY. NEED TO PROVIDE
 INFORMATION FOR EACH OCCUPANCY. USE TABLE 504.3, TABLE
 504.4 AND TABLE 506.2 FBC 2017 FOR CORRECT AND CURRENT
 CODE INFORMATION AND REVISE AS REQUIRED.
  
 E) REVISE ARRANGEMENTS AND NUMBER OF EXITS INFORMATION
 SHOWN IN THE DESIGN CRITERIA. SINGLE EXITS ARE ALLOWED.
 SEE SEC. 1006.3.2.1 AND TABLE 1006.3.2(2) FOR MIXED
 OCCUPANCIES AND REVISE NUMBER OF EXITS AND TRAVEL
 DISTANCE AS REQUIRED.
  
 F) REVISE TRAVEL DISTANCES LINES SHOWN ON THE LIFE
 SAFETY PLAN.
 (1) THE PATH IS MEASURED FROM THE MOST REMOTE POINT TO
 THE ENTRANCE TO THE EXIT. SEC. 1017.3 FBC. A DIAGONAL
 LINE IS NOT ACCEPTABLE. NEED TO CONSIDER PATH WHERE
 FURNITURE IS IN PLACE. TYPICALLY TRAVEL DISTANCE IS
 SHOWN GOING PARALLEL TO THE WALLS. PROVIDE FURNITURE
 LAYOUT AND REDRAW TRAVEL DISTANCES AS REQUIRED.
  
 (2) PROVIDE A SEPARATE TRAVEL DISTANCE FROM THE MOST
 REMOTE POINT OF THE WAREHOUSE TO THE EXIT. SEC. 1017.3
 FBC.
  
 G) FLOOR CEILING FIRE RATED ASSEMBLY DRAWING IS NOT
 LEGIBLE. PROVIDE LEGIBLE DRAWING. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- NEED 1 HR FIRE RESISTANCE RATED CONSTRUCTION AT THE
 COMBUSTIBLE ROOF PROJECTION EXTENDING TO WITHIN 5 FEET
 OF THE PROPERTY LINE AS REQUIRED BY SEC. 705.2.3
 FBC-BUILDING. PROVIDE DETAIL AND SPECIFICATIONS FOR
 EAVE OVERHANG FIRE RATED ASSEMBLY.
  
 5- FBC-ACCESSIBILITY.
 A) PROVIDE COMPLIANCE WITH THE VERTICAL ACCESSIBILITY
 REQUIREMENTS FOR THE SECOND STORY OFFICE AS REQUIRED BY
 SEC. 201.1.1 FBC-ACCESSIBILITY. OR SHOW IN PLANS
 COMPLIANCE WITH ANY EXCEPTION.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ACCESSIBLE ROUTE SHOWING COMPLIANCE WITH SEC.
 206-FBC-ACCESSIBILITY.
 ACCESSIBLE ROUTE FROM PARKING TO THE BUILDING ENTRANCE
 (SEC. 402 AND SEC. 404 FBC-ACCESSIBILITY)
  
 C)PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 504-FBC-ACCESSIBILITY.
 INCLUDE THE NOSING SPECIFICATIONS.
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 HANDRAILS SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS
 OF SEC. 505-FBC-ACCESSIBILITY.
 HANDRAILS REQUIRED ON EACH SIDE OF STAIRWAY (REQ'D BY
 FBC ALSO).
  
 E) OFFICE ENTRANCE DOOR DOESN'T COMPLY WITH THE
 MANEUVERING REQUIREMENTS OF SEC. 404.2.4
 FBC-ACCESSIBILITY.
  
 F) PROVIDE COMPLETE DETAILS AND SPECIFICATION FOR
 ACCESSIBLE RESTROOMS SHOWING COMPLIANCE WITH ALL THE
 REQUIREMENTS OF CHAPTER 6- FBC-ACCESSIBILITY THAT
 APPLY.
 NOTE: 7'-0" MAY NOT COMPLY WITH THE OVERLAP ALLOWANCE
 OF SEC. 604.3.2 FBC-ACCESSIBILITY.
  
 6- LOCATION OF ATTIC ACCESS DOESN'T SEEM TO PROVIDE THE
 MIN. 30" CLEAR HEADROOM AS REQUIRED BY SEC. 1209.2 FBC.
 REVISE AS REQUIRED.
  
 7- SHEET A-1:
 A) WINDOWS AND DOORS DESIGN PRESSURES SHOWN ON
 WINDOW/DOORS SCHEDULES DON'T MATCH DESIGN PRESSURES
 SHOWN UNDER PRODUCT APPROVAL AFFIDAVIT ON SAME SHEET.
 ALSO, COORDINATE WITH DESIGN PRESSURES SHOWN ON SHEET
 S-2. REVISE AS REQUIRED TO MATCH. SEC. 1609.1 FBC.
  
 B) CLARIFY SIZE OF DOOR #2. SEE OPENING SIZE SHOWN ON
 FLOOR PLAN. SEC.107.2.1 CITY AMENDMENTS.
  
 8- RETAINING WALL DETAILS ON SHEET SP-1: CLARIFY
 VERTICAL REINFORCEMENT SIZE AND SPACING. SEC. 1609.1
 FBC.
  
 9- WINDER TREADS ARE NOT ALLOWED. SEC. 1011.5.3 FBC.
 REVISE STAIRS AS REQUIRED.
  
 10- SOIL TEST REPORT:
 A) NEED TO HAVE ENGINEER'S ORIGINAL SEAL AND SIGNATURE
 AS REQUIRED BY CHAPTER 471 F.S. WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. THIS IS NOT A DIGITAL
 SUBMITTAL.
  
 B) PROVIDE 2 COPIES. SEC. 107.1 CITY AMENDMENTS.
  
 C) THE PROPOSED CONSTRUCTION MATERIALS DON'T MATH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D) SOIL TEST FOOTING RECOMMENDATION AND PLANS DON'T
 MATCH. REVISE AS REQUIRED TO MATCH. IF FOOTING SIZE IS
 NOT REVISED, THEN DESIGNER OF RECORD TO PROVIDE
 JUSTIFICATION IN WRITING AS REQUIRED BY SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 11- ENERGY CALCULATIONS:
 A) ARCHITECT OF RECORD TO CERTIFY (SIGNATURE AND
 LICENSE NUMBER) ON ENERGY FORM AS REQUIRED BY SEC.
 C103.1.1.1.2 FBC-ENERGY CONSERVATION.
  
 B) SHOW COMPLIANCE WITH THE BUILDING ENVELOPE
 REQUIREMENT SEC. C402.3. THERE IS A LOW SLOPE ROOF IN
 THIS BUILDING. REVISE INFORMATION ON PAGE 9 OF 22 AS
 REQUIRED. THIS IS NOT N/A.
  
 C) REVISE BUILDING ORIENTATION SHOWN ON PAGE 17 OF 22
 TO MATCH PLANS. NOTE: PLANS ARE DRAWN WITH NORTH ARROW
 POINTING SOUTH.
  
 D) REVISE WALL TYPES AND INSULATION INFORMATION SHOWN
 ON PAGE 17 OF 22 TO MATCH PLANS. ALSO, NEED TO PROVIDE
 INFORMATION FOR RAISED FLOOR ABOVE THE FIRST FLOOR
 UNCONDITIONED WAREHOUSE AREA. NOTE: COORDINATE WITH
 ARCHITECT.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS WILL BE REQUIRED
 FOR INSPECTION.
  
  
 12- ARCHITECT TO COORDINATE INFORMATION ON PLANS WITH
 THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. SEC.
 C103.2 FBC-ENERGY CONSERVATION.
  
 13- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
 A) ENTRY DOORS. FLORIDA PRODUCT APPROVAL FL14237-R3
 SUBMITTED IS NOT APPROVED YET. IT' ONLY VALIDATED.
  
 B) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STAIRWAY CONSTRUCTION AS REQUIRED BY SEC. 1607.3 FBC.
  
 17- DESIGNER OF RECORD TO SPECIFY THE LIVE AND DEAD
 LOADS FOR SECOND FLOOR. SEC. 1606 AND SEC. 1607 FBC.
 NOTE: SEE SEC. 1607.11 FOR DISTRIBUTION OF FLOOR LOADS.
  
 18- TRUSS PACKAGE:
 A)TRUSS LAYOUT SHOWS A TOTAL FLOOR LOADING OF 70 PSF.
 THIS IS INCORRECT. IT DOESN'T ADD UP WITH ALL SPECIFIED
 LOADS. REVISE AS REQUIRED TO MATCH. SEC. 1606 AND 1607
 FBC.
  
 B) TRUSS ENGINEER TO PROVIDE ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. COPIES ARE NOT
 ALLOWED.
  
 C) TRUSS PACKAGE COVER LETTER NEEDS TO PROVIDE THE
 INFORMATION OF THE PROFESSIONAL DESIGNER OF RECORD AS
 REQUIRED BY FAC 61G15-23.003.
  
 D) TRUSS LAYOUT SHOW THE TRUSS TO TRUSS STRUCTURAL
 CONNECTORS. TRUSS ENGINEER TO SIGN AND SEAL TRUSS
 LAYOUT AND PROVIDE HIS INFORMATION AS REQUIRED BY FAC
 61G15-23.001. OR PROVIDE COMPLETE STRUCTURAL
 CONNECTIONS ON EACH INDIVIDUAL TRUSS DRAWING.
  
 E)TRUSS ENGINEER TO PROVIDE ALL HIS INFORMATION ON ALL
 TRUSS DRAWINGS AS REQUIRED BY FAC 61G15-31.003 WHEN
 USING A COVER SHEET.
  
 19- DESIGNER OF RECORD TO REVIEW REVISED TRUSS PACKAGE,
 INCLUDING INDIVIDUAL TRUSSES BEFORE SUBMITTAL TO THIS
 OFFICE. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 20- VALUE DECLARED I THE PERMIT APPLICATION IS TOO LOW.
 REVISE AS REQUIRED. SEC. 109.3 CITY AMENDMENTS.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 21- WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 NOTE: ENTER BUILDING INFORMATION ON FRONT SCREEN FIELDS
 WHEN PLANS ARE REVISED AND RESUBMITTED. JG.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-12-16 Cont ID  
Sent By jpearson Date 2019-12-16 Time 07:54 Rev Time 0.00
Received By jpearson Date 2019-12-16 Time 06:48 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-03-19 Cont ID  
Sent By jpearson Date 2019-03-19 Time 10:57 Rev Time 0.00
Received By jpearson Date 2019-03-19 Time 09:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By jpearson Date 2018-05-02 Time 13:55 Rev Time 0.00
Received By jpearson Date 2018-05-02 Time 13:06 Sent To  
Notes
2018-05-02 13:55:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE AIC RATING OF PANEL. NEC 110.3, 110.9
 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 4. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 5. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
 6. A CONFLICT EXIST ON THE RISER DIAGRAM THE GROUNDING
 ELECTRODE CONDUCTOR IS SHOWN AS #4 IN ONE LOCATION AND
 THE SAME WIRE IS SHOWS AS #8 IN ANOTHER LOCATION.
 GROUNDING ELECTRODE CONDUCTOR SHOULD BE SIZED PER NEC
 250.66. PROVIDE CORRECTION. FBC 107.2.1; NEC 250.66
 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. NEC
 422.52
 10. PROVIDE ACCURATE LOAD CALCULATION INCLUDING 125% OF
 CONTINUOUS LOADS AND 100% OF NON-CONTINUOUS LOADS. SOME
 LOADS SUCH AS WATER HEATER AND SPRINKLER PUMP ARE NOT
 SHOWN AS CONTINUOUS. SOME LOADS HAVE INCORRECT MATH FOR
 THE 125%. NEC 215.2, 220, 422.13
 11. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2019-12-13 Cont ID  
Sent By rrossano Date 2019-12-13 Time   Rev Time 0.00
Received By rrossano Date 2019-12-13 Time   Sent To  
Notes
2019-12-13 09:47:36UNDER FORMAL ENGINEERING SUBMITTAL REVIEW E18030033.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 13:52 Rev Time 0.00
Received By shill Date 2019-03-22 Time 13:52 Sent To  
Notes
2019-03-22 13:52:24CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-04-30 Cont ID  
Sent By shill Date 2018-04-30 Time 08:13 Rev Time 0.00
Received By shill Date 2018-04-30 Time 08:12 Sent To  
Notes
2018-04-30 08:13:10CONTACT ENGINEERING DEPARTMENT DIRECTLY AND SUBMIT
 APPLICATION IF REQUIRED
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 ENGINEERING APPROVAL REQUIRED PRIOR TO PERMIT ISSUANCE
  
 MAIN PHONE: (561) 822-1200
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-11-15 Cont ID  
Sent By pleduc Date 2019-11-15 Time   Rev Time 0.00
Received By pleduc Date 2019-11-15 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By scaldero Date 2019-02-26 Time 11:26 Rev Time 0.00
Received By scaldero Date 2019-02-26 Time 11:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-03 Cont ID  
Sent By scaldero Date 2018-04-03 Time 12:12 Rev Time 0.00
Received By scaldero Date 2018-04-03 Time 12:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-12-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-11-12 Time 16:34 Sent To  
Notes
2019-11-13 16:34:35C06

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-03-22 Cont ID  
Sent By shill Date 2019-03-22 Time 13:56 Rev Time 0.00
Received By shill Date 2019-02-20 Time 13:42 Sent To  
Notes
2019-02-21 13:43:00C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 07:53 Rev Time 0.00
Received By gjohnson Date 2018-03-30 Time 14:04 Sent To  
Notes
2018-04-02 14:05:48C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2019-11-27 Cont ID  
Sent By jgomez Date 2019-11-27 Time 09:06 Rev Time 0.00
Received By jgomez Date 2019-11-27 Time 09:06 Sent To  
Notes
2019-11-27 09:07:05IMPACT FEES -
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-03-14 Cont ID  
Sent By jgomez Date 2019-03-14 Time 18:21 Rev Time 0.00
Received By jgomez Date 2019-03-14 Time 18:21 Sent To  
Notes
2019-03-14 18:21:41IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL OF PLANS, YOU MAY CHECK
 OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW.
 PLEASE RETURNED STAMPED AND WITH A COPY OF THE RECEIPT
 AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jgomez Date 2018-05-10 Time 18:08 Rev Time 0.00
Received By jgomez Date 2018-05-10 Time 18:08 Sent To  
Notes
2018-05-10 18:09:111- BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-12-06 Cont ID  
Sent By ccole Date 2019-12-06 Time 15:28 Rev Time 0.00
Received By ccole Date 2019-12-06 Time 14:31 Sent To  
Notes
2019-12-06 15:34:312ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 PERMIT #18031395
 12/6/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT APPEARS THE ORIGINAL AC CALCULATIONS HAVE BEEN
 VOIDED OUT, HOWEVER NO NEW AC CALCULATIONS HAVE BEEN
 SUBMITTED- SECTION C403.2.1 FBC EC.
  
 2) A REVISED ENERGYGAUGE COMPLIANCE REPORT HAS BEEN
 SUBMITTED, HOWEVER THERE ARE MSSING CERTIFICATIONS ON
 PAGE 4. PLEASE REFER TO BUILDING REVIEW COMMENT #11
 (12/4/2019) FOR COMPLIANCE REQUIRMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-03-21 Cont ID  
Sent By ccole Date 2019-03-21 Time 12:17 Rev Time 0.00
Received By ccole Date 2019-03-21 Time 12:09 Sent To  
Notes
2019-03-21 12:33:572ND REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 PERMIT #18031395
 3/21/19
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL PLANS SHALL BEAR THE SIGNATURE OF THE
 INSTALLING CONTRACTOR (KYZAR AIR CONDITIONING INC.) OR
 SHALL BE SIGNED AND SEALED BY A FL. LICENSED ENGINEER-
 SECTION 105.3.1.2 WPB AMENDMENTS TO THE FBC-17.
  
 2) SHEET M.1: IT APPEARS THE AIR HANDLER WILL BE
 INSTALLED IN THE ATTIC WHICH IS NOT ALLOWED IN A
 COMMERCIAL BUILDING- SECTION C403.2.9.6 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-02 Cont ID  
Sent By ccole Date 2018-05-02 Time 09:19 Rev Time 0.00
Received By ccole Date 2018-05-02 Time 09:19 Sent To  
Notes
2018-05-02 10:00:211ST REVIEW FBC-2017 MECHANICAL, ENERGY CONSERVATION
 PERMIT #18031395
 5/2/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-2: THERMAL ENVELOPE AND CONTINUOUS AIR BARRIER
 INCOMPLETE AT THE INTERSECTION OF THE FLOOR TRUSSES AND
 THE EXTERIOR WALL- SECTIONS C407.2, C402.5, AND
 C402.5.1. PLEASE NOTE THAT THE PLANS ARE SPECIFYING
 FOIL BACKED INSULATION ON THE EXTERIOR WALL AND THE
 ENERGY CALCULATIONS ARE INDICATING 3/4" ISO.
  
 2) THE ENERGY AND AC CALCULATIONS ARE SPECIFYIONG THE
 CONDITIONED AREA AT 709 SQ. FT. HOWEVER THE THERMAL
 ENVELOPE APPEARS TO BE INCOMPLETE BECAUSE NO SECOND
 FLOOR INSULATION IS SHOWN ON THE PLAN OR IN THE CALCS.
  
 3) AC-1: PROVIDE MINIMUM VENTILATION CALCULATIONS IN
 ACCORDANCE WITH TABLE 403.1.1. INDICATE THE REQUIRED
 AND PROVIDED CFMS OF OUTDOOR AIR.
  
 4) AC-1: EXHAUST VENTILATION IS REQUIRED FOR THE TOILET
 ROOMS- TABLE 403.1.1.
  
 5) AC-1: NATURAL OR MECHANICAL VENTILATION IS REEQUIRED
 FOR THE WAREHOUSE PER SECTION 401.2. PLEASE INDICATE
 WHICH METHOD IS TO BE USED AND PROVIDE A CALCULATION-
 SEE SECTION 402.2 AND TABLE 403.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-12-10 Cont ID  
Sent By jesmith Date 2019-12-10 Time 14:02 Rev Time 0.00
Received By jesmith Date 2019-12-05 Time 12:23 Sent To  
Notes
2019-12-05 12:23:29PLUMBING COMMENTS: APPROVED WITH PROVISO
 1. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, A CODE COMPLIANT SANITARY
 ISOMETRIC THAT SHOWS THE DRINKING FOUNTAIN AND THE MOP
 SINK DOWNSTREAM OF THE WET VENT IN ACCORDANCE WITH FBC
 PL 912.1. PROVIDE A VENT FOR THE DRINKING FOUNTAIN PER
 FBC PL 909.1 AND 909.2. THE DOCUMENTS SHALL BE
 SUBMITTED, APPROVED AND ON SITE PRIOR TO FIRST
 INSPECTION. PROCEED AT YOUR OWN RISK.
 2. PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE
 AS A DEFERRED SUBMITTAL, AN ENGINEERED DETAIL OF THE
 SUPPORT SYSTEM FOR THE WATER HEATER. THE DOCUMENTS
 SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR TO FINAL
 INSPECTION. PROCEED AT YOUR OWN RISK.
 3. WATER HAMMER ARRESTOR SHALL BE INSTALLED WHERE QUICK
 CLOSING VALVES ARE UTILIZED PER FBC PL 604.9
 4. FULL OPEN VALVES SHALL BE INSTALLED ON TOP OF EVERY
 WATER DOWNFEED PIPE PER FBC PL 604.9.

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-03-12 Cont ID  
Sent By thunt Date 2019-03-12 Time 13:48 Rev Time 0.00
Received By thunt Date 2019-03-12 Time 13:07 Sent To M
Notes
2019-03-12 13:39:14PLUMBING PROVISO:(1) PROVIDE A CODE COMPLIANT
 SANITARY ISOMETRIC DRAWING BY 1ST INSPECTION THAT
 SHOW THE MOP SINK DOWN STREAM OF THE WET VENT.
 FBC-P 107.3.5*FBC-P 912.1.(2) HAMMER ARRESTOR
 MUST BE INSTALLED WHERE QUICK CLOSING VALVES
 ARE UTILIZED. FBC-P 604.9 (3) FULL OPEN SHUT OFF
 VALVES SHALL BE INSTALLED ON-TOP OF EVERY WATER
 DOWN FEED PIPE. FBC-P 604.9
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-15 Cont ID  
Sent By gjohnson Date 2018-05-15 Time 07:02 Rev Time 0.00
Received By gjohnson Date 2018-05-14 Time 16:36 Sent To  
Notes
2018-05-15 07:53:151ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WATER COOLER SHALL COMPLY WITH FBC ACC 211.1 AND
 602
  
 2. THE LAVATORY'S SHALL COMPLY WITH FBC PL 416.5
 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
  
 3. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW ON
 THE WATER SERVICE NEXT TO METER PLEASE PLACE NOTE ON
 PLANS. PER WPB UTILITIES DEPT.
  
 4. THE UTILITY SINK SHALL CONNECT TO BUILDING DRAIN
 DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2019-11-26 Cont ID  
Sent By jgomez Date 2019-11-26 Time 18:52 Rev Time 0.00
Received By jgomez Date 2019-11-26 Time 18:51 Sent To  
Notes
2019-11-26 18:51:51NOTE:
 THIS WILL BE A PROVISO. THE INFORMATION WILL NEED TO BE
 PROVIDED FOR REVIEW PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS.
  
  
 1- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 APPROVED ASSEMBLY WAS NOT MARKED/IDENTIFIED. APPROVED
 ASSEMBLIES ARE ON PAGE 5 OF 8 TO PAGE 7 OF 8. NOTE: ALL
 THESE ASSEMBLIES ARE FOR ASSEMBLIES WITH INSULATION.
 PLANS DON'T SHOW ANY FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION. THE INSULATION SHOWN ON PLANS IS FOR
 ICYNENE INSULATION SPRAYED AT THE BOTTOM OF ROOD DECK.
 IF USING A FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION , THEN ARCHITECTURAL PLANS NEED TO BE
 REVISED SHOWING THE ADDITIONAL INSULATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 APPROVED:
 SHINGLES FL18355-R4.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2019-03-18 Cont ID  
Sent By jgomez Date 2019-03-18 Time 16:22 Rev Time 0.00
Received By jgomez Date 2019-03-18 Time 15:01 Sent To  
Notes
2019-03-18 16:21:55ORIGINAL COMMENT:
 1- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 APPROVED ASSEMBLY WAS NOT MARKED/IDENTIFIED. APPROVED
 ASSEMBLIES ARE ON PAGE 5 OF 8 TO PAGE 7 OF 8. NOTE: ALL
 THESE ASSEMBLIES ARE FOR ASSEMBLIES WITH INSULATION.
 PLANS DON'T SHOW ANY FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION. THE INSULATION SHOWN ON PLANS IS FOR
 ICYNENE INSULATION SPRAYED AT THE BOTTOM OF ROOD DECK.
 IF USING A FLAT ROOF ASSEMBLY WITH ADDITIONAL
 INSULATION , THEN ARCHITECTURAL PLANS NEED TO BE
 REVISED SHOWING THE ADDITIONAL INSULATION. SEC. 107.2.1
 CITY AMENDMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 APPROVED:
 SHINGLES FL18355-R4.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-05-10 Cont ID  
Sent By jgomez Date 2018-05-10 Time 18:07 Rev Time 0.00
Received By jgomez Date 2018-05-10 Time 18:07 Sent To  
Notes
2018-05-09 10:35:48ROOFING INFORMATION.
  
 1- FLAT ROOF NOA 14-0627.05 SUBMITTED: CLEARLY MARK
 WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 1609.1 FBC. NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED.
  
  
 APPROVED:
 SHINGLES FL18355-R4.

Review Stop Z ZONING
Rev No 3 Status F Date 2019-11-19 Cont ID  
Sent By llouie Date 2019-11-19 Time   Rev Time 0.00
Received By llouie Date 2019-11-19 Time   Sent To  
Notes
2019-11-19 16:01:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) DETAIL OF THE BICYCLE RACK IS MISSING. [4/6/18
 REPEAT COMMENT]
  
 2.) PROVIDE INFORMATION ON HOW TRASH WILL BE REMOVED
 FROM THE SITE. PLEASE NOTE THAT WRITTEN APPROVAL FROM
 SANITATION IS REQUIRED FOR THE METHOD OF TRASH REMOVAL.
 CONTACT MATT HEJAZI, INDUSTRIAL ENGINEER, WITH THE
 PUBLIC WORKS DEPARTMENT FOR SANITATION APPROVAL (561)
 822-2045 OR AT [email protected].
  
 3.) PARKING STALL DIMENSIONS AND STALL STRIPING DETAIL
 MISSING FROM THE PERMIT PLANS.
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: LANDSCAPING.
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * REFERENCE: ISPR 17-03
  
 * ZONE: I
  

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2019-03-05 Time   Rev Time 0.00
Received By pgreilic Date 2019-03-05 Time 14:31 Sent To  
Notes
2019-03-05 14:31:381.) ONE BICYCLE PARKING SPACE REQUIRED
 2.) PROVIDE BIKE RACK DETAIL AND PARKING STRIPING
 DETAIL
 3.) LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2018-04-06 Time   Rev Time 0.00
Received By pgreilic Date 2018-04-05 Time 14:40 Sent To  
Notes
2018-04-06 10:25:011.) ONE BICYCLE PARKING SPACE REQUIRED
 2.) PROVIDE BIKE RACK DETAIL AND PARKING STRIPING
 DETAIL
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]