Plan Review Details - Permit 18031344
Plan Review Stops For Permit 18031344
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-20 Cont ID  
Sent By fgiaquin Date 2018-04-20 Time 07:17 Rev Time 0.00
Received By fgiaquin Date 2018-04-20 Time 06:58 Sent To  
Notes
2018-04-20 07:17:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-13 Cont ID  
Sent By fgiaquin Date 2018-04-13 Time 06:28 Rev Time 0.00
Received By fgiaquin Date 2018-04-13 Time 06:19 Sent To M
Notes
2018-04-13 06:28:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PLAN IS REQUIRED TO BE SIGNED AND SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.003(2)(H); 471.025; FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN
 REVIEW COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO
 THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 6TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 6TH
 EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 6TH EDITION, PART
 VIII ELECTRICAL
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 [email protected]
 561-657-1653

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-04-03 Cont ID  
Sent By pleduc Date 2018-04-03 Time   Rev Time 0.00
Received By pleduc Date 2018-04-02 Time 12:14 Sent To E
Notes
2018-04-03 12:40:21THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) IN AN EFFORT TO REDUCE FALSE ALARMS AND COMPLY WITH
 NFPA - IS THE SYSTEM PROGRAMABLE TO HAVE THE DUCT
 DETECTORS SEND A SUPERVISORY SIGNAL INSTEAD OF A FULL
 ALARM?
  
 IF SO, PLEASE EXECUTE AND TEST PER NFPA 72.
  
 NFPA 72
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE
 MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT
 DETECTOR ACTIVATION SIGNAL SHALL MEET THE REQUIREMENTS
 OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A CONSTANTLY
 ATTENDED
 LOCATION OR SUPERVISING STATION SHALL BE PERMITTED TO
 INITIATE AN
 ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL
 WHERE
 REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-20 Cont ID  
Sent By jleahy Date 2018-04-20 Time 16:11 Rev Time 0.00
Received By jleahy Date 2018-04-18 Time 16:06 Sent To  
Notes
2018-04-18 16:07:11RESUB ROUTED TO FGIAQUIN VIA JLEAHY'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-17 Cont ID  
Sent By hmoser Date 2018-04-17 Time 08:51 Rev Time 0.00
Received By hmoser Date 2018-03-29 Time 10:57 Sent To  
Notes
2018-03-30 10:58:05ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-04-17 Cont ID  
Sent By hmoser Date 2018-04-17 Time 08:51 Rev Time 0.00
Received By hmoser Date 2018-04-17 Time 08:42 Sent To I
Notes
***NONE***