Plan Review Details - Permit 18031260
Plan Review Stops For Permit 18031260
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 15:55 Rev Time 0.00
Received By shill Date 2018-05-22 Time 15:55 Sent To  
Notes
2018-05-22 15:56:40REVISION REQUIRED - ISSUED AT APPLICANT'S RISK
 PROVIDE RATED CEILING ASSEMBLY DETAIL
 PLEASE SUBMIT A PRELIMINARY REVIEW VIA EMAIL
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:46 Rev Time 0.00
Received By shill Date 2018-05-22 Time 06:43 Sent To  
Notes
2018-05-22 06:47:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
  
  
 1) FROM PREVIOUS LIST: 2014 FBC-B 1009.9.3 ENCLOSURES
 UNDER INTERIOR STAIRWAYS. THE WALLS AND SOFFITS WITHIN
 ENCLOSED USABLE SPACES UNDER ENCLOSED AND UNENCLOSED
 STAIRWAYS SHALL BE PROTECTED BY 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE
 SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE.
  
 2ND REVIEW: PLANS HAVE BEEN REVISED TO SPECIFY UL263.
 THIS ASSEMBLY IS FOR USE AS A WALL ONLY; REVISE PLAN TO
 SPECIFY CEILING.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By jwitmer Date 2018-03-30 Time 15:23 Rev Time 0.00
Received By jwitmer Date 2018-03-30 Time 13:57 Sent To  
Notes
2018-03-30 15:23:142014 FBC- BUILDING PLAN REVIEW
 W. P. B. REVISION: 18031260
 W. P. B. PERMIT: 17100783
 ADD: 480 HIBISCUS ST. SUITE: 115
 CONT: IBS CONSTRUCTION
 TEL: 305-527-8303
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MARCH 30/ 2018
 ACTION: DENIED
  
 1) SHEET A201 SHOWS (2) ROOMS BEING BUILT UNDERNEATH
 THE MEZZANINE STAIRS. ROOMS 103 AND ROOM 104. PLEASE
 SHOW COMPLIANCE WITH;
 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR
 ENCLOSURE.
  
 2) SHEET A202 AND A901 SHOW DETAILS OF THE USE FOR
 GLASS CEILINGS, GL9 & GL10. PLEASE PROVIDE HOW
 COMPLIANCE WILL BE ACHIEVED WITH EITHER SECTION:
 2014 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS. SLOPED GLAZING SHALL BE ANY OF THE
 FOLLOWING MATERIALS, SUBJECT TO THE LISTED LIMITATIONS.
 OR
 2014 FBC-B 2606.1. THE PROVISIONS OF THIS SECTION AND
 SECTIONS 2607 THROUGH 2611 SHALL GOVERN THE QUALITY AND
 METHODS OF APPLICATION OF LIGHT-TRANSMITTING PLASTICS
 FOR USE AS LIGHT-TRANSMITTING MATERIALS IN BUILDINGS
 AND STRUCTURES. FOAM PLASTICS SHALL COMPLY WITH SECTION
 2603. LIGHT-TRANSMITTING PLASTIC MATERIALS THAT MEET
 THE OTHER CODE REQUIREMENTS FOR WALLS AND ROOFS SHALL
 BE PERMITTED TO BE USED IN ACCORDANCE WITH THE OTHER
 APPLICABLE CHAPTERS OF THE CODE.
  
 3) SHEET A901 SHOWS GLASS PANEL SECTIONS GL 01 THRIUGH
 GL 08. THERE ARE NO DETAILS INDICATING THE TYPE OF
 GLAZING, THICKNESS OF GLAZING IN EITHER THE DOOR, AND
 OR SIDELIGHTS NEXT TO THE DOOR. PLEASE REVIEW SECTION
 2406.4OF THE FBC-B, HAZARDOUS LOCATIONS. THE LOCATIONS
 SPECIFIED IN SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL
 BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING
 SAFETY GLAZING MATERIALS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-21 Cont ID  
Sent By jpearson Date 2018-05-21 Time 13:19 Rev Time 0.00
Received By jpearson Date 2018-05-15 Time 12:14 Sent To  
Notes
2018-05-15 13:19:29NO NOTES

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By jpearson Date 2018-03-30 Time 08:39 Rev Time 0.00
Received By jpearson Date 2018-03-30 Time 08:36 Sent To  
Notes
2018-03-30 08:38:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE LOAD CALCULATION FOR SERVICE AT WIREWAY #3,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC 405.7.1
 3. A CONFLICT EXIST ON SHEET E3.1. TRANSFORMER GROUND
 NOTES STATE A # 6 GROUND SHOULD BE RUN TO BUILDING
 STEEL, WHILE THE FEEDER SIZE KEY NOTES STATES THAT A #
 2 SHOULD BE RUN. PROVIDE CORRECTION. FBC 107.2.1; NEC
 250.30
 4. VALUE STATED FOR THE INCREASE IN WORK APPEARS LOW.
 PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE OF
 WORK, TO INCLUDE ALL MATERIALS AND LABOR. FBC 109.3
 5. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-08 Cont ID  
Sent By pleduc Date 2018-05-08 Time   Rev Time 0.00
Received By pleduc Date 2018-05-07 Time 15:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-03 Cont ID  
Sent By pleduc Date 2018-04-03 Time   Rev Time 0.00
Received By pleduc Date 2018-04-02 Time 14:35 Sent To  
Notes
2018-04-02 15:42:09THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF FIRE SPRINKLER WORK
 UNDER SEPARATE SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICBALE NOTE.
  
  
 2) THERE ARE NO INDICATION THAT THE CEILING OF THE ROOM
 UNDER THE INTERIOR EXIT STAIRS ARE RATED PER NFPA 101,
 CHAPTER 7.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS,
 PROVIDED THAT BOTH ALL OF THE FOLLOWING CRITERIA ARE
 MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE
 SAME FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM
 WITHIN THE STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3.)
 (3) THE SPACE IS NOT USED FOR THE STORAGE OF
 COMBUSTIBLE OR
 FLAMMABLE LIQUIDS, OR OTHERWISE HAZARDOUS MATERIALS.
  
 PLEASE PROVIDE DETAILS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-22 Cont ID  
Sent By shill Date 2018-05-22 Time 06:47 Rev Time 0.00
Received By shill Date 2018-05-02 Time 15:48 Sent To  
Notes
2018-05-04 10:36:41FROM ZONING TO LAURA MERCHANT 5/4/18
2018-05-02 15:48:26B26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-18 Cont ID  
Sent By cpuell Date 2018-04-18 Time 11:09 Rev Time 0.00
Received By cpuell Date 2018-03-28 Time 13:24 Sent To  
Notes
2018-03-29 13:23:58B31

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-05-15 Cont ID  
Sent By ccole Date 2018-05-15 Time 12:04 Rev Time 0.00
Received By ccole Date 2018-05-10 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-03 Cont ID  
Sent By ccole Date 2018-04-03 Time 17:00 Rev Time 0.00
Received By ccole Date 2018-04-03 Time 14:55 Sent To  
Notes
2018-04-03 17:14:461ST REVIEW FBC-2014 MECHANICAL
 REVISION #18031260
 MASTER #17100783
 4/3/18
  
 1) PROVIDE REVISED AC LOAD AND ENERGY CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By gjohnson Date 2018-04-06 Time 17:23 Rev Time 0.00
Received By gjohnson Date 2018-04-06 Time 16:03 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-05-04 Cont ID  
Sent By elevesqu Date 2018-05-04 Time 10:36 Rev Time 0.00
Received By elevesqu Date 2018-05-04 Time 10:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-04-18 Cont ID  
Sent By AA Date 2018-04-18 Time 10:12 Rev Time 0.00
Received By elevesqu Date 2018-04-18 Time 10:12 Sent To  
Notes
***NONE***