| 2018-03-30 15:23:14 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 18031260 |
| | W. P. B. PERMIT: 17100783 |
| | ADD: 480 HIBISCUS ST. SUITE: 115 |
| | CONT: IBS CONSTRUCTION |
| | TEL: 305-527-8303 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. MARCH 30/ 2018 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A201 SHOWS (2) ROOMS BEING BUILT UNDERNEATH |
| | THE MEZZANINE STAIRS. ROOMS 103 AND ROOM 104. PLEASE |
| | SHOW COMPLIANCE WITH; |
| | 2014 FBC-B 1009.9.3 ENCLOSURES UNDER INTERIOR |
| | STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE |
| | SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| | ENCLOSURE. |
| | |
| | 2) SHEET A202 AND A901 SHOW DETAILS OF THE USE FOR |
| | GLASS CEILINGS, GL9 & GL10. PLEASE PROVIDE HOW |
| | COMPLIANCE WILL BE ACHIEVED WITH EITHER SECTION: |
| | 2014 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND |
| | LIMITATIONS. SLOPED GLAZING SHALL BE ANY OF THE |
| | FOLLOWING MATERIALS, SUBJECT TO THE LISTED LIMITATIONS. |
| | OR |
| | 2014 FBC-B 2606.1. THE PROVISIONS OF THIS SECTION AND |
| | SECTIONS 2607 THROUGH 2611 SHALL GOVERN THE QUALITY AND |
| | METHODS OF APPLICATION OF LIGHT-TRANSMITTING PLASTICS |
| | FOR USE AS LIGHT-TRANSMITTING MATERIALS IN BUILDINGS |
| | AND STRUCTURES. FOAM PLASTICS SHALL COMPLY WITH SECTION |
| | 2603. LIGHT-TRANSMITTING PLASTIC MATERIALS THAT MEET |
| | THE OTHER CODE REQUIREMENTS FOR WALLS AND ROOFS SHALL |
| | BE PERMITTED TO BE USED IN ACCORDANCE WITH THE OTHER |
| | APPLICABLE CHAPTERS OF THE CODE. |
| | |
| | 3) SHEET A901 SHOWS GLASS PANEL SECTIONS GL 01 THRIUGH |
| | GL 08. THERE ARE NO DETAILS INDICATING THE TYPE OF |
| | GLAZING, THICKNESS OF GLAZING IN EITHER THE DOOR, AND |
| | OR SIDELIGHTS NEXT TO THE DOOR. PLEASE REVIEW SECTION |
| | 2406.4OF THE FBC-B, HAZARDOUS LOCATIONS. THE LOCATIONS |
| | SPECIFIED IN SECTIONS 2406.4.1 THROUGH 2406.4.7 SHALL |
| | BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING |
| | SAFETY GLAZING MATERIALS. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |