Plan Review Details - Permit 18031221
Plan Review Stops For Permit 18031221
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-18 Cont ID  
Sent By cthroop Date 2019-01-18 Time 12:26 Rev Time 0.00
Received By cthroop Date 2019-01-18 Time 11:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 17:53 Rev Time 0.00
Received By shill Date 2018-09-15 Time 17:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By aclange Date 2018-03-30 Time 16:04 Rev Time 0.00
Received By aclange Date 2018-03-30 Time 15:52 Sent To  
Notes
2018-03-30 16:04:32****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PROVIDE SIGNED AND SEALED DRAWINGS BY A STRUCTURAL
 ENGINEER. INCLUDE WINDLOAD CALCULATIONS AND SOIL DATA.
 SEE THESE NOTES ON PAGE E300 DETAILS E AND F.
  
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  
 A THOROUGH REVIEW COULD NOT BE COMPLETED AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED.
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-12-10 Cont ID  
Sent By cthroop Date 2019-01-18 Time 12:26 Rev Time 0.00
Received By jpearson Date 2018-12-10 Time 12:46 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-10-12 Cont ID  
Sent By jpearson Date 2018-10-12 Time 10:22 Rev Time 0.00
Received By jpearson Date 2018-10-12 Time 10:22 Sent To I
Notes
2018-10-12 09:05:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED. A CLASS L FUSE WILL ACCOMPLISH THIS
 REDUCTION IN FUSE SIZE. FYI, A FUSE REDUCER OF THIS
 SIZE DOES NOT EXIST.
 7. CORRECTED.
 8. PROVIDE ACCURATE LOAD BREAKDOWN. THE CURRENT
 EXPLANATION SHOWS THE NEW NORMAL LOAD TO BE 116 KW AND
 THE EMERGENCY LOAD TO BE 113 KW, BUT THE TOTAL PEAK
 DEMAND OF ONLY 113 KW. WHAT ARE THE LOADS FOR THE
 INDIVIDUAL SYSTEMS AND IS THE TOTAL CAPABLE OF BEING
 SUPPORTED BY THE NEW GENERATOR? PROVIDE CLARIFICATION.
 NEC 517.41(C) (AN ACCURATE LOAD CALCULATION, OR
 EQUIVALENT, WAS NOT PROVIDED. A FUTURE RECORDING IS NOT
 ACCEPTABLE. THIS INSTALLATION CANNOT BE APPROVED UNTIL
 ONE OF THE METHODS FOR LOAD DETERMINATION IS PROVIDED.
 IF NEC 220.87 IS INTENDED, A CERTIFIED RECORDING FOR 30
 DAYS WILL BE REQUIRED, OR DEMAND LOAD FOR A ONE YEAR
 PERIOD. ALL 3 ITEMS IN 220.87 ARE REQUIRED FOR APPROVAL
 UNDER THIS SECTION.)(3RD REVIEW: RESPONSE LETTER STATED
 THAT PROOF IN THE FORM OF AN EMAIL FROM FPL WAS TO BE
 PROVIDED. THIS WAS NOT INCLUDED IN THE PACKET. PROVIDE
 AS PREVIOUSLY REQUESTED.)
 9. PROVIDE DETAIL OF SEPARATION OF THE LIFE SAFETY
 BRANCH THE CRITICAL BRANCH. NEC 517.41(D) (BASED ON
 LOAD PROVIDED IN COMMENT 8, THIS MAY NOT BE NECESSARY
 IF LESS THAN 150 KW OF TOTAL LOAD.)(3RD REVIEW:
 CONFIRMATION OF LOAD NOT PROVIDED.)
 10. CORRECTED.
 11) WITH THE NEW DESIGN, PANEL MSB HAS BECOME A
 DOWNSTREAM PANEL AND IS REQUIRED TO HAVE THE GROUNDS
 AND NEUTRALS SEPARATED, AS WELL AS AN EGC INSTALLED IN
 THE EXISTING CONDUITS. THE GROUNDING ELECTRODE SYSTEM
 IS REQUIRED TO BE TIED IN AT THE MAIN SERVICE. PROVIDE
 CORRECTION. NEC 250.6, 250.24, 250.28, 250.30, 250.110,
 250.142(B)(3RD REVIEW: CORRECTION NOT PROVIDED ON PLAN
 FOR EXISTING WIRING TO MSB AND TO TRANSFER SWITCH THAT
 FEEDS PANEL E. BOTH OF THESE CONDUITS SHOW THE EXISTING
 FEED WITHOUT THE REQUIRED EQUIPMENT GROUNDING
 CONDUCTOR, SIZED PER CODE. PROVIDE CORRECTION AS
 PREVIOUSLY REQUESTED.)
  
 NEW COMMENTS:
 12. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 FYI, FOR THIS PROJECT, THE ADDITIONAL PLAN REVIEW FEE
 WILL BE $3,550.00 BASED ON THE JOB VALUE OF $200,000.
 13. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-08-31 Cont ID  
Sent By jpearson Date 2018-08-31 Time 13:02 Rev Time 0.00
Received By jpearson Date 2018-08-31 Time 09:22 Sent To  
Notes
2018-08-31 13:02:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. HOW WILL THE 500 AMP FUSE BE INSTALLED IN A 1600 AMP
 PIECE OF EQUIPMENT? PANEL MSB IS SHOWN WITH A 1600 AMP
 FUSE. OBVIOUSLY, THE FUSE SIZE WOULD BE DIFFERENT.
 PROVIDE CLARIFICATION. NEC110.3; FBC 107.2.1 (BY
 SEARCHING ONLINE, I WAS NOT ABLE TO FIND A REDUCER FROM
 1600 AMPS TO 600 AMPS. PROVIDE MANUFACTURERS SPEC SHEET
 FOR THIS PRODUCT. AS A SIDE NOTE, WHY IS THIS BEING
 INSTALLED, AS THE CONDUCTORS AND SERVICE EQUIPMENT
 UPSTREAM ARE PROTECTED AT 600 AMP? IT SEEMS THE
 ORIGINAL FUSES COULD REMAIN IN PLACE, AS EVERYTHING
 AHEAD OF IT IS PROTECTED. NO CODE VIOLATION WITH
 CHANGING THE FUSE, BUT WE WILL NEED TO SEE A LISTED
 PRODUCT FOR THIS.)
 7. CORRECTED.
 8. PROVIDE ACCURATE LOAD BREAKDOWN. THE CURRENT
 EXPLANATION SHOWS THE NEW NORMAL LOAD TO BE 116 KW AND
 THE EMERGENCY LOAD TO BE 113 KW, BUT THE TOTAL PEAK
 DEMAND OF ONLY 113 KW. WHAT ARE THE LOADS FOR THE
 INDIVIDUAL SYSTEMS AND IS THE TOTAL CAPABLE OF BEING
 SUPPORTED BY THE NEW GENERATOR? PROVIDE CLARIFICATION.
 NEC 517.41(C) (AN ACCURATE LOAD CALCULATION, OR
 EQUIVALENT, WAS NOT PROVIDED. A FUTURE RECORDING IS NOT
 ACCEPTABLE. THIS INSTALLATION CANNOT BE APPROVED UNTIL
 ONE OF THE METHODS FOR LOAD DETERMINATION IS PROVIDED.
 IF NEC 220.87 IS INTENDED, A CERTIFIED RECORDING FOR 30
 DAYS WILL BE REQUIRED, OR DEMAND LOAD FOR A ONE YEAR
 PERIOD. ALL 3 ITEMS IN 220.87 ARE REQUIRED FOR APPROVAL
 UNDER THIS SECTION.)
 9. PROVIDE DETAIL OF SEPARATION OF THE LIFE SAFETY
 BRANCH THE CRITICAL BRANCH. NEC 517.41(D) (BASED ON
 LOAD PROVIDED IN COMMENT 8, THIS MAY NOT BE NECESSARY
 IF LESS THAN 150 KW OF TOTAL LOAD.)
 10. CORRECTED.
  
 NEW COMMENT:
  
 11) WITH THE NEW DESIGN, PANEL MSB HAS BECOME A
 DOWNSTREAM PANEL AND IS REQUIRED TO HAVE THE GROUNDS
 AND NEUTRALS SEPARATED, AS WELL AS AN EGC INSTALLED IN
 THE EXISTING CONDUITS. THE GROUNDING ELECTRODE SYSTEM
 IS REQUIRED TO BE TIED IN AT THE MAIN SERVICE. PROVIDE
 CORRECTION. NEC 250.6, 250.24, 250.28, 250.30, 250.110,
 250.142(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-11 Cont ID  
Sent By jpearson Date 2018-04-11 Time 14:42 Rev Time 0.00
Received By jpearson Date 2018-04-11 Time 07:28 Sent To I
Notes
2018-04-11 14:42:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE DETAIL OF LEVEL OF PATIENT CARE AT THIS
 FACILITY NEC 517.40(B); FBC 107.2.1
 2. FAULT CURRENT FROM MAIN TO ATS IS SHOWN AS 29925
 AMPS. THE ATS IS SHOWN AS RATED FOR 22,000 AIC. PROVIDE
 CORRECTION. NEC 110.9
 3. FEEDER SCHEDULE DOES NOT INCLUDE THE 500 AMP FEEDER
 SHOWN ON PLAN. THE FAULT CURRENT CALCULATION SHOWS A
 500 AL CONDUCTOR, WHICH IS NOT RATED FOR 500 AMPS.
 PROVIDE ACCURATE FEEDER DESCRIPTION. FBC 107.2.1; NEC
 215.2, 215.5, 310.15(B)(16)
 4. PROVIDE DETAIL FOR THE METHOD OF CERTIFICATION THAT
 WILL BE USED BY A NRTL TO PROVIDE LISTING FOR THE
 ALTERED SWITCH GEAR (PANEL MSB). NEC 110.3; FBC 107.2.1
 5. BY ALTERING THE BUS OF MSB, HOW WILL THIS AFFECT THE
 AIC RATING OF THE EQUIPMENT? PROVIDE CLARIFICATION. NEC
 110.3; FBC 107.2.1
 6. HOW WILL THE 500 AMP FUSE BE INSTALLED IN A 1600 AMP
 PIECE OF EQUIPMENT? PANEL MSB IS SHOWN WITH A 1600 AMP
 FUSE. OBVIOUSLY, THE FUSE SIZE WOULD BE DIFFERENT.
 PROVIDE CLARIFICATION. NEC110.3; FBC 107.2.1
 7. PROVIDE CONTROL WIRING SCHEMATIC FOR EXISTING
 TRANSFER SWITCH TO EXPLAIN THE METHOD OF CONNECTION
 DETAILED IN NOTE # 5 ON SHEET E400. AS THE SENSING
 MECHANISM IS NORMALLY BUILT INTO A TRANSFER SWITCH,
 WHERE WOULD THIS BE TIED IN TO THE NORMAL POWER SO THAT
 THERE WOULD BE NO CONFLICT WITH THE NORMAL TRANSFER
 SWITCH FEED TO PANEL MSB? WOULD THIS VIOLATE THE
 LISTING OF THE EXISTING TRANSFER SWITCH BY RELOCATING
 THIS WIRING TO A DIFFERENT LOCATION? PROVIDE
 CLARIFICATION. NEC 110.3; FBC 107.2.1
 8. PROVIDE ACCURATE LOAD BREAKDOWN. THE CURRENT
 EXPLANATION SHOWS THE NEW NORMAL LOAD TO BE 116 KW AND
 THE EMERGENCY LOAD TO BE 113 KW, BUT THE TOTAL PEAK
 DEMAND OF ONLY 113 KW. WHAT ARE THE LOADS FOR THE
 INDIVIDUAL SYSTEMS AND IS THE TOTAL CAPABLE OF BEING
 SUPPORTED BY THE NEW GENERATOR? PROVIDE CLARIFICATION.
 NEC 517.41(C)
 9. PROVIDE DETAIL OF SEPARATION OF THE LIFE SAFETY
 BRANCH THE CRITICAL BRANCH. NEC 517.41(D)
 10. PROVIDE DETAIL OF COMPLIANCE WITH NEC517.42. WILL
 THE NORMAL AND ESSENTIAL TRANSFER AT THE SAME TIME, OR
 WILL THERE BE A DELAY? SHOW ON PLAN. FBC 107.2.1; NEC
 517.42
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-24 Cont ID  
Sent By scaldero Date 2018-08-24 Time 09:35 Rev Time 0.00
Received By scaldero Date 2018-08-24 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-30 Cont ID  
Sent By scaldero Date 2018-03-30 Time 11:40 Rev Time 0.00
Received By scaldero Date 2018-03-30 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-18 Cont ID  
Sent By cthroop Date 2019-01-18 Time 12:26 Rev Time 0.00
Received By cthroop Date 2018-12-07 Time 10:28 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-10-12 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-01 Time 15:12 Sent To  
Notes
2018-10-02 15:12:43RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 17:53 Rev Time 0.00
Received By shill Date 2018-08-16 Time 15:32 Sent To  
Notes
2018-08-17 15:32:21B14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-27 Time 14:29 Sent To  
Notes
2018-03-28 14:29:36B14

Review Stop Z ZONING
Rev No 4 Status N Date 2018-12-11 Cont ID  
Sent By awooten Date 2018-12-11 Time 08:26 Rev Time 0.00
Received By awooten Date 2018-12-11 Time 08:26 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-04 Cont ID  
Sent By awooten Date 2018-10-04 Time   Rev Time 0.00
Received By awooten Date 2018-10-04 Time   Sent To E
Notes
2018-10-04 16:32:01THE NEW GENERATOR LOCATION IS APPROVED INSIDE OF THE
 EXISTING GENERATOR ENCLOSURE ONLY. PER THE CIVIL PLANS.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-08-29 Time   Rev Time 0.00
Received By   Date 2018-08-29 Time   Sent To  
Notes
2018-08-29 15:37:44***************************************ZONING REVIEW
 FAILED****************************************
  
 REVISED LOCATION FOR NEW GENERATOR EQUIPMENT IS IN
 PARKING SPACES. PLEASE SHOW THAT THE REQUIRED AMOUNT OF
 PARKING IS STILL MET WITH THE REDUCTION OF THE NUMBER
 OF SPACES DUE TO THE NEW GENERATOR LOCATION.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By AW Date 2018-04-06 Time   Rev Time 0.00
Received By awooten Date 2018-04-05 Time 13:53 Sent To  
Notes
***NONE***