Plan Review Details - Permit 18031215
Plan Review Stops For Permit 18031215
Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-10-04 Cont ID  
Sent By rrossano Date 2018-10-04 Time   Rev Time 0.00
Received By rrossano Date 2018-10-04 Time   Sent To M
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-05-18 Cont ID  
Sent By mgonzale Date 2018-05-18 Time   Rev Time 1.00
Received By mgonzale Date 2018-05-18 Time   Sent To M
Notes
2018-05-18 14:35:04RESUMIT PLANS WITH MISSING INFORMATION OF EXISTING
 UTILITIES.
 OTHER UTILITIES INCLUDE PUBLIC GAS, BELLSOUTH, AT&T AND
 FPL.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-04-24 Cont ID  
Sent By Mgonzale Date 2018-04-24 Time   Rev Time 1.00
Received By mgonzale Date 2018-04-24 Time   Sent To M
Notes
2018-04-24 16:18:53PLEASE RESPOND TO COMMENTS IN WRITING:
  
 #1 PROVIDE BETTER DETAIL AS TO THE INSTALLATION OF THE
 WM ON 10TH ST.
 DOUBLE VALVE, SOURCE, VENT. SEQUENCE OF TRANSFER FROM
 EXISTING WATER MAIN TO NEW ONE.
  
 #2 FIRELINE TO THE BUILDING TO THE NORTH DOES NOT SHOW
 ON THE PLAN.
 LOCATION 310 N OLIVE AVE
 MUNICIPALITY WEST PALM BEACH
 PARCEL NO. 74434322120070010
  
 #3 CUT AND CAP FOR THE SITE EXISTING FIRELINE IS NOT
 SHOWN.
 ANY OTHER SERVICES SHALL BE CUT BACK TO MAIN OR REUSED.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-09-24 Cont ID  
Sent By J,Walker Date 2018-09-24 Time   Rev Time 0.00
Received By   Date 2018-09-20 Time   Sent To ENG
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-04 Cont ID  
Sent By pleduc Date 2018-05-04 Time   Rev Time 0.00
Received By pleduc Date 2018-05-04 Time 10:14 Sent To ENG
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-03-29 Cont ID  
Sent By pleduc Date 2018-03-29 Time   Rev Time 0.00
Received By pleduc Date 2018-03-29 Time 09:30 Sent To ENG
Notes
2018-03-29 11:37:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET 11 OF 16 & 12 OF 16 - THERE APPEARS TO BE ONE
 (1) FIRE LINE WATER SUPPLY LEADING TO EACH HIGH RISE'S
 FIRE PUMPS.
  
 PER NFPA 101 AND THE FLORIDA BUILDING CODE 2 SEPARATE
 WATER SUPPLIES ARE REQUIRED FOR EACH RIE PUMP.
  
 2014 NFPA 101 CHAPTER 11.
  
 11.1.6 MINIMUM CONSTRUCTION REQUIREMENTS. MINIMUM
 CONSTRUCTION REQUIREMENTS SHALL BE IN ACCORDANCE WITH
 THE APPLICABLE
 OCCUPANCY CHAPTER AND WITH THE FLORIDA BUILDING CODE.
  
 2014 FLORIDA BUIL;DING CODE:
  
 [F] 403.3.2 WATER SUPPLY TO REQUIRED FIRE PUMPS.
 REQUIRED FIRE PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO
 NO FEWER THAN TWO WATER MAINS LOCATED IN DIFFERENT
 STREETS. SEPARATE SUPPLY PIPING SHALL BE PROVIDED
 BETWEEN EACH CONNECTION TO THE WATER MAIN AND THE
 PUMPS. EACH CONNECTION AND THE SUPPLY PIPING BETWEEN
 THE CONNECTION AND THE PUMPS SHALL BE SIZED TO SUPPLY
 THE FLOW AND PRESSURE REQUIRED FOR THE PUMPS TO
 OPERATE.
  
 EXCEPTION: TWO CONNECTIONS TO THE SAME MAIN SHALL BE
 PERMITTED PROVIDED THE MAIN IS VALVED SUCH THAT AN
 INTERRUPTION CAN BE ISOLATED SO THAT THE WATER SUPPLY
 WILL CONTINUE WITHOUT INTERRUPTION THROUGH NO FEWER
 THAN ONE OF THE CONNECTIONS.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-10-10 Time   Rev Time 0.00
Received By lmarchan Date 2018-09-14 Time 15:23 Sent To  
Notes
2018-09-17 15:24:06ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2018-05-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-05-02 Time 15:51 Sent To  
Notes
2018-05-02 15:51:22RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-27 Time 13:52 Sent To  
Notes
2018-03-28 13:53:03ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-10 Cont ID  
Sent By ccole Date 2018-10-10 Time 10:54 Rev Time 0.00
Received By ccole Date 2018-10-10 Time 10:46 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-21 Cont ID  
Sent By ccole Date 2018-05-21 Time 10:57 Rev Time 0.00
Received By ccole Date 2018-05-21 Time 10:53 Sent To I
Notes
2018-05-21 11:02:06 
 2ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18031215
 5/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMMENTS FROM THE 1ST REVIEW WERE NOT ADDRESSED.
 I HAVE REPRINTED THEM BELOW- PLEASE COMPLY.
  
  
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18031215
 4/26/18
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIRELINE PIPING, VALVES, AND FITTINGS. CLARIFY HOW THE
 PIPING AND FITTINGS WILL RESTRAINED AGAINST MOVEMENT.
  
 2) ADVISORY: A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-26 Cont ID  
Sent By ccole Date 2018-04-26 Time 10:54 Rev Time 0.00
Received By ccole Date 2018-04-26 Time 10:54 Sent To I
Notes
2018-04-26 11:02:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18031215
 4/26/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIRELINE PIPING, VALVES, AND FITTINGS. CLARIFY HOW THE
 PIPING AND FITTINGS WILL RESTRAINED AGAINST MOVEMENT.
  
 2) ADVISORY: A SEPARATE PERMIT IS REQUIRED FOR THE
 BACKFLOW PREVENTER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  