| 2018-04-03 10:06:42 | 04/03/2018 1ST GAS REVIEW**DENIED** |
| | |
| | 1) YOUR VALUE OF TOTAL JOB SEEMS LOW. PER WPB AMEND TO |
| | THE FBC 109.3 PROVIDE A SIGNED BONA FIDE CONTRACT |
| | SHOWING TOTAL JOB VALUE.VALUE MUST INCLUDE THE COST OF |
| | THE GAS COOK TOP ALONG WITH ALL MATERIAL, LABOR, |
| | OVERHEAD, AND PROFIT. |
| | |
| | 2) PROVIDE COOK TOP MANUFACTURE INSTALLATION MANUAL. |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 3) CITY RECORDS SHOW AN EXISTING GAS POOL HEATER LISTED |
| | AT 405,000 BTU THAT IS NOT SHOWING ON YOUR ISOMETRIC. |
| | LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU |
| | LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | |
| | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE NEW |
| | COOK TOP PER THE 2017 FBC-FUEL GAS CODE SEC.304.1, 2017 |
| | FBC-RES. SEC. G 2407.1 |
| | |