Plan Review Details - Permit 18031052
Plan Review Stops For Permit 18031052
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2019-02-15 Cont ID  
Sent By shill Date 2019-02-15 Time 16:59 Rev Time 0.00
Received By shill Date 2019-02-15 Time 16:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 17:35 Rev Time 0.00
Received By shill Date 2018-12-21 Time 17:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-01 Cont ID  
Sent By shill Date 2018-11-01 Time 16:02 Rev Time 0.00
Received By shill Date 2018-11-01 Time 16:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 16:58 Rev Time 0.00
Received By shill Date 2018-09-02 Time 16:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-04-06 Time 15:21 Rev Time 0.00
Received By aclange Date 2018-04-05 Time 10:25 Sent To  
Notes
2018-04-06 15:21:08****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. FAIR HOUSING DESIGN MANUAL
  
 A) KITCHEN ISLAND DOES NOT HAVE 40 INCH CLEARANCE ON
 TWO SIDES.
  
 B. PROVIDE 32 INCHES CLEAR AT BATHROOM DOORS.
  
 C. IN THE FAIR HOUSING DESIGN MANUAL CHAPTER 7 SELECT
 WHETHER YOU WILL BE USING A OR B SPECIFICATIONS WHEN
 DESIGNING THE BATHROOMS. SHOW THIS ON THE PLANS AND
 ADJUST LAYOUT ACCORDINGLY.
  
 2. DOORS
  
 A. DOOR 111 NOT SHOWN ON SCHEDULE.
  
 B. PROVIDE INFORMATION ON DOOR 101C. ROLL DOWN SMOKE
 DOOR IF USED. NOTE, SINCE THE ELEVATOR IS PRESSURIZED
 THIS DOOR IS NOT REQUIRED.
  
 3. PROVIDE UNDERLAYMENT USED FOR WOOD FLOOR IN ROOM
 121A GYM. IF PLYWOOD UNDERLAYMENT IS USED SHOW
 COMPLIANCE WITH FBC 603.1 COMBUSTIBLE MATERIALS.
  
 4. PROVIDE THE FOLLOWING FLOOR UNDERLAYMENT SOUND
 PROOFING INFORMATION.
  
 STRUCTURAL BORNE SOUND TEST HAS BEEN RECEIVED.
  
 SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
  
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-24 Cont ID  
Sent By jleahy Date 2018-08-24 Time 16:51 Rev Time 0.00
Received By jleahy Date 2018-08-24 Time 16:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By jleahy Date 2018-05-04 Time 06:32 Rev Time 0.00
Received By jleahy Date 2018-05-04 Time 06:32 Sent To  
Notes
2018-05-04 10:18:38FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-1.1
  
 NOTE #4 UPDATE CODE EDITIONS
  
 NOTE #62 UPDATE NOTE TO REFLECT NEC CODE 2014 ARC
 FAULTS IN KITCHEN AND LAUNDRY AREAS
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS,
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS,
 OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 PAGE E-2.1
  
 OUTLET SPACING SEEMS TO BE DEFICIENT IN MOST ROOMS
 E3901.2.1 SPACING. RECEPTACLES SHALL BE INSTALLED SO
 THAT NO POINT MEASURED HORIZONTALLY ALONG THE FLOOR
 LINE OF ANY
 WALL SPACE IS MORE THAN 6 FEET (1829 MM), FROM A
 RECEPTACLE OUTLET. [210.52(A)(1)]
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
 1. 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN
 WIDTH, INCLUDING SPACE MEASURED AROUND CORNERS, AND
 THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
 2. 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR
 WALLS, EXCLUDING SLIDING PANELS.
 3. 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS
  
  
 OUTLETS MISSING ON BALCONY
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES
 (1981 MM) ABOVE GRADE, SHALL BE INSTALLED OUTDOORS AT
 THE FRONT AND BACK OF EACH DWELLING UNIT HAVING DIRECT
 ACCESS TO
 GRADE LEVEL. BALCONIES, DECKS, AND PORCHES THAT ARE
 ACCESSIBLE FROM INSIDE OF THE DWELLING UNIT SHALL HAVE
 AT LEAST ONE
 RECEPTACLE OUTLET INSTALLED WITHIN THE PERIMETER OF THE
 BALCONY, DECK, OR PORCH. THE RECEPTACLE SHALL BE
 LOCATED NOT MORE
 THAN 6 FEET, 6 INCHES (1981 MM) ABOVE THE BALCONY,
 DECK, OR PORCH SURFACE. [210.52(E)]
  
 KITCHEN AND LAUNDRY AREAS NEED ARC FAULT PROTECTION
 ALL 120-VOLT, SINGLE PHASE, 15 AND 20 AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS IN DWELLING UNIT KITCHENS,
 LAUNDRY ROOMS,
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS,
 OR SIMILAR AREAS OR ROOMS, SHALL HAVE AFCI PROTECTION.
 NEC 210.12; FBC RE3902.16
  
 PAGE E-4.1
  
 PANEL SCHEDULES NEED TO REFLECT NEW AFCL/GFCI
 PROVISIONS
  
 NEED TO SUBMIT FAULT CURRENT CALCULATIONS
  
 NEED TO SUBMIT A LOAD CALCULATION
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED
 PAGES INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER
 561-805-6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-08-07 Cont ID  
Sent By pleduc Date 2018-08-07 Time   Rev Time 0.00
Received By pleduc Date 2018-08-07 Time 13:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-04-11 Cont ID  
Sent By pleduc Date 2018-04-11 Time   Rev Time 0.00
Received By pleduc Date 2018-04-11 Time 11:14 Sent To  
Notes
2018-04-11 12:02:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) COVER SHEET - THE ADDRESS IN THE TITLE BLOCK
 INDICATES 1112 S FLAGLER. THE ADDRESS OF THE BUILDING
 IS 1100 S FAGLER.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 2) THERE IS SMOKEGAURD SMOKE CURTAIN INDICATED AT THE
 ELEVATOR LOBBY.
  
 THIS OPENING ALSO FUNCTION A AN EXIT/EXIT ACCESS TO
 THIS RESIDENCE. HOW WILL THIS OPENING/CURTAIN FUNCTION
 AS AN EXIT/EXIT ACCESS IN THE EVENT IT ACTIVATES AND IS
 IN THE DOWN POSITION?
  
 ADDITIONALLY, THE BUREAU HAS TESTED PREVIOUS PROPOSED
 SIMILAR CURTAINS THAT FAIL TO STAY SECURED DUE TO
 PRESSURIZATION OF OTHER LIFE SAFETY SYSTEMS. HAS THE
 PRESSURIZATION OF THE ELEVATOR BEEN CONSIDERED WITH THE
 EOR OF THIS BUILDING.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
 3) SHEET F O.1 - THE FIRE SPRINKLER DRAWINGS APPEAR TO
 HAVE AN ENGINEER STAMP AND/OR SEAL. THERE CAN BE ONLY
 ONE ENGINEEER OF RECORD FOR THE SPRINKLER SYSTEM.
  
 DOES THIS STAMPED SET CONFLICT WITH THE ORIGINAL EOR
 STAMP AND DOES THE EOR APPROVE OF THIS DESIGN.
  
 PLEASE REVIEW, CORRECT OR JUSTIFY WITH DETAILS.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2018-09-04 Cont ID  
Sent By gjohnson Date 2018-09-04 Time 10:14 Rev Time 0.00
Received By gjohnson Date 2018-09-04 Time 10:14 Sent To  
Notes
2018-09-04 10:14:21PROVISO:
 SHALL PROVIDE BEFORE ROUGH INSPECTIONS
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR COOK TOP.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR DRYER VENT.
 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR MASTER TUB DRAIN.
 PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-05-16 Cont ID  
Sent By gjohnson Date 2018-05-16 Time 11:30 Rev Time 0.00
Received By gjohnson Date 2018-05-16 Time 11:30 Sent To  
Notes
2018-05-16 11:43:431ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-2.2 SHOWS THE G/# RISER 3/4 NG TO UNIT SHOWS
 104 CFH THE TOTAL BTU LOAD ON THE ISOMETRIC IS ONLY 66
 CFH PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT P-2.2 SHOWS THE PIPING TO THE DRYER AS 1/2" THE
 ISOMETRIC ON SHT P-3.1 SHOWS 3/4" PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 3. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304
  
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS SEC.
 402.2 ALSO PROVIDE INSTALLATION GUIDE FOR DRYER VENT.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2019-02-15 Cont ID  
Sent By shill Date 2019-02-15 Time 17:00 Rev Time 0.00
Received By shill Date 2019-02-15 Time 13:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2019-02-15 Cont ID  
Sent By lmarchan Date 2019-02-11 Time 13:45 Rev Time 0.00
Received By lmarchan Date 2019-01-21 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 17:35 Rev Time 0.00
Received By shill Date 2018-11-27 Time 15:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-11-07 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-01 Time 10:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-09-05 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-03 Time 13:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-16 Cont ID  
Sent By gjohnson Date 2018-05-16 Time 11:43 Rev Time 0.00
Received By gjohnson Date 2018-04-03 Time 16:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-04-06 Time 15:21 Rev Time 0.00
Received By aclange Date 2018-04-06 Time 15:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2019-02-11 Cont ID  
Sent By ccole Date 2019-02-11 Time 12:40 Rev Time 0.00
Received By ccole Date 2019-02-08 Time 17:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2018-12-21 Cont ID  
Sent By ccole Date 2018-12-21 Time 12:52 Rev Time 0.00
Received By ccole Date 2018-12-21 Time 08:58 Sent To  
Notes
2018-12-21 13:02:203RD REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 12/21/18
  
 PLAN REVIEW RESULTS: DENIED. (PLAN REVIEW I N PROGRESS,
 DO NOT PRINT).
  
 1) THE SPECS FOR THE DOWN DRAFT SYSTEMS DO NOT INDICATE
 SYSTEMS ARE DESIGNED FOR RECIRCULATION, AND BASED ON
 THE 1000 CFM MAXIMUM EXHAUST RATINGS, MAKEUP AIR WILL
 BE REQUIRED PER SECTION 505.2 FBC M.
  
 2) SHEETS M2.1 AND A4.6: THE PLANS DO NOT SHOW THE
 KITCHEN EXHAUST SYSTEMS ABOVE THE COOKTOPS ARE IN
 COMPLIANCE WITH SEVERAL ITEMS LISTED UNDER SECTION
 505.3 FBC M- SEE BELOW.
  
 505.3 COMMON EXHAUST SYSTEMS FOR DOMESTIC KITCHENS
 LOCATED IN MULTISTORY STRUCTURES.
  
 WHERE A COMMON MULTISTORY DUCT SYSTEM IS DESIGNED AND
 INSTALLED TO CONVEY EXHAUST FROM MULTIPLE DOMESTIC
 KITCHEN EXHAUST SYSTEMS, THE CONSTRUCTION OF THE SYSTEM
 SHALL BE IN ACCORDANCE WITH ALL OF THE FOLLOWING:
  
 5.THE EXHAUST FAN MOTOR DESIGN SHALL BE IN ACCORDANCE
 WITH SECTION 503.2. PLEASE REVIEW SECTION 503.2 AND
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR EF-C WITH
 INFORMATION INDICATING COMPLIANCE.
  
 6. THE EXHAUST FAN MOTOR SHALL BE LOCATED OUTSIDE OF
 THE AIRSTREAM.
  
 7.THE EXHAUST FAN SHALL RUN CONTINUOUSLY, AND SHALL BE
 CONNECTED TO A STANDBY POWER SOURCE.
  
 8. EXHAUST FAN OPERATION SHALL BE MONITORED IN AN
 APPROVED LOCATION AND SHALL INITIATE AN AUDIBLE OR
 VISUAL SIGNAL WHEN THE FAN IS NOT IN OPERATION.
  
 3) SECTIONS 917.1 & 017.2 REQUIRE UL LISTING AND
 LABELING FOR THE MIELE COOKING APPLIANCES, HOWEVER I'M
 NOT SEEING ANY EVIDENCE OF UL LISTING IN THE SUBMITTED
 SPEC SHEETS.
  
 4) AS PREVIOUSLY NOTED, THE DRYER BOOSTER FAN SPECS DO
 NOT INDICATE THE FAN IS LISTED AND LABELED FOR USE WITH
 A CLOTHES DRYER- SECTION 504.6.4.1 FBC M.
  
 5) M2.1: PLEASE MODIFY NOTE #26 TO INDICATE THE DRYER
 BOOSTER FAN WILL ALSO BE ENCLOSED IN THE PLENUM RATED
 EXHAUST CHASE AND PROVIDE CONSTRUCTION DETAILS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-11-06 Cont ID  
Sent By ccole Date 2018-11-06 Time 17:23 Rev Time 0.00
Received By ccole Date 2018-11-06 Time 15:50 Sent To  
Notes
2018-11-06 17:37:332ND REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 11/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATION PRINTOUT IS INDICATING MIAMI AS
 THE PROJECT LOCATION. PLEASE PROVIDE CALCULATIONS USING
 THE CORRECT LOCATION, AND INCLUDE THE ADDRESS AND UNIT
 NUMBER ON THE CALCULATION PRINTOUT.
  
 2) M2.1: SMOKE DETECTORS ARE REQUIRED IN BOTH THE
 SUPPLY AND THE RETURN SYSTEMS OF THE HP'S- SECTION
 606.2 FBC M.
  
 3) M2.1: PROVIDE THE RETURN OPENING DIMENSIONS AT EACH
 HP CLOSET- SECTION 601.4 FBC M.
  
 4) M2.1: THERE IS INSUFFICENT INFORMATION AND DETAILS
 ON THE PLAN TO SHOW COMPLIANCE FOR THE REQUIRED KITCHEN
 EXHAUST SYSTEMS:
  
 A) PLEASE PROVIDE ENLARGED KITCHEN EXHAUST DETAILS ON
 THE PLAN SHOWING THE COOKTOP DOWNDRAFT EXHAUST DUCT
 RUNS AND TERMINATION LOCATIONS. CLARIFY IF TWO SYSTEMS
 WILL BE INSTALLED- ONE FOR THE GAS-FIRED COOKTOP AND
 ONE FOR THE ELECTRIC COOKTOP. SPECS HAVE BEEN SUBMITTED
 FOR EACH HOWEVER THE PLAN APPEARS TO SHOW ONLY ONE
 COOKTOP.
  
 B) THE COMB-OVEN, SPEED OVEN, AND CONVECTION OVEN EACH
 REQUIRE AN EXHAUST VENTILATION SYSTEM HOWEVER NO SPECS
 FOR THE VENTS HAVE BEEN SUBMITTED AND NO DETAILS HAVE
 BEEN PROVIDED ON THE PLAN.
  
 C) PLEASE REFER TO TABLE 403.3 WHICH REQUIRES AN
 EXHAUST VENTILATION RATE OF 25 CFMS PER SF. FOR
 CONTINUOUS VENTILATION, AND 100 CFMS PER SF. FOR
 INTERMITTENT VENTILATION.
  
 5) THE DRYER BOOSTER FAN SPECS DO NOT INDICATE THE FAN
 IS LISTED AND LABELED FOR USE WITH A CLOTHES DRYER-
 SECTION 504.6.4.1 FBC M
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-09-05 Cont ID  
Sent By ccole Date 2018-09-05 Time 16:24 Rev Time 0.00
Received By ccole Date 2018-09-05 Time 14:06 Sent To  
Notes
2018-09-05 17:04:271ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 9/5/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 PLEASE NOTE THAT ALL APARTMENT BUILDOUTS WILL BE
 DESIGNED UNDER THE 2010 FLORIDA BUILDING CODES UNTIL
 WHICH TIME THE ENTIRE BUILDING RECEIVES A CERTIFICATE
 OF OCCUPANCY.
  
 1) PLEASE REPLACE THE ENERGYGAUGE 2017 COMPLIANCE
 SUBMITTAL WITH THE 2010 VERSION AND PROVIDE PIPING
 SYSTEM COMPLIANCE DATA THAT IS MISSING FROM THE FORM.
  
 2) M2.1: SHOW THE LOCATION OF THE O/A DUCT THAT IS
 SUPPLYING THE UNITS VIA THE RETURN AIR PLENUM,
  
 3) M2.1: DUE TO THE FACT THAT THE AC CLOSETS ARE
 SHARING A COMMON PLENUM SMOKE DETECTORS SHALL BE
 PROVIDED IN THE RETUN AIR PLENUM IN ACCORDANCE WITH
 SECTION 606.2.2 FBC M.
  
 4) M2.1: REGARDING THE INTUMESCENT PAINT ON THE AC
 CLOSET DOORS, IT HAS BEEN DETERMINED THAT THE ENGINEER
 OF RECORD SHALL BE RESPONSIBLE FOR INSPECTING AND
 CERTIFYING THE APPLICATION PROCESS. PLACE A NOTE ON THE
 PLAN ACCORDINGLY.
  
 5) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP
 IS REFERENCING SHEET AXX FOR THE DRYER ENCLOSURE
 DETAIL. I WAS NOT ABLE TO LOCATE THE SHEET OR DETAIL.
  
 6) M2.1: THE RESPONSE NARRATIVE FROM THE JOHNSON GROUP
 IS REFERENCING A DIMENSIONED, SEGMENTED DRAWING OF THE
 DRYER EXHAUST DUCT WHICH I WAS UNABLE TO LOCATE. PLEASE
 PROVIDE THE DRAWING.
  
 7) M2.1 : CLARIFY THE NEED FOR THE DRYER EXHAUST
 BOOSTER FAN. PER THE EQUIVALENT LENGTH TABLE, THE 120
 FT. RUN DOES NOT EXCEED THE 125 FT. MAXIMUM RUN ALLOWED
 BY THE MANUFACTURER. IN ADDITION, PLEASE CONTACT FIRE
 CHIEF PETER LEDUC FOR PERMISSION TO INSTALL THE BOOSTER
 FAN. IF PERMITTED, AN ACCESS PANEL WILL BE REQUIRED FOR
 SERVICE AND REPLACEMENT OF THE FAN- SECTION 306.1.
  
 8) M2.1: THE COMBUSTION AIR CALCULATION TABLE LISTS THE
 KITCHEN AT 3860 SQ. FT. WHICH CLEARLY FROM THE DRAWINGS
 IT IS NOT. PLEASE PROVIDE AN ACCURATE CALCULATION.
  
 9) THE REQUESTED PRODUCT DATA SHEETS FOR THE GAS FIRED
 APPLIANCES AND DOWN DRAFT EXHAUST SYSTEM WERE NOT
 PROVIDED. PLEASE NOTE THAT AN EXHAUST HOOD MAY BE
 REQUIRED FOR THE OVENS PER SECTION 507.2.2 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-05-09 Cont ID  
Sent By ccole Date 2018-05-09 Time 09:21 Rev Time 0.00
Received By ccole Date 2018-05-08 Time 17:40 Sent To  
Notes
2018-05-09 10:18:371ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18031052
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: THE SE-2 DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE-
 SECTION 1023.5 FBC-17 BUILDING.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS. THE CALCULATIONS SUBMITTED UNDER THE MAIN
 BUILDING PERMIT ARE NOT VALID FOR THIS NEW INTERIOR
 BUILDOUT UNDER NEW OWNERSHIP AND SEPARATE PERMIT -
 SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 3) PROVIDE AN ENERGY COMPLIANCE REPORT. THE
 CALCULATIONS SUBMITTED UNDER THE MAIN BUILDING PERMIT
 ARE NOT VALID FOR THIS NEW INTERIOR BUILDOUT UNDER NEW
 OWNERSHIP AND SEPARATE PERMIT SECTION C101.5
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE
 HEAT PUMPS.
  
 7) M2.1: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY SYSTEM OF HP-G- SECTION 606.2.1. THIS
 REQUIREMENT MAY BE WAIVED IF MANUFACTURER'S
 SPECIFICATIONS INDICATE THE UNIT CANNOT PRODUCE OVER
 2000 CFMS OF SUPPLY AIR.
  
 8) M2.1 & A9.1: NON-COMBUSTIBLE DOORS ARE REQUIRED FOR
 THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 FBC-17
 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY CONSERVATION.
  
 10) M2.1: DRYER: A) PER NOTES #12 & 26 : PROVIDE
 CONSTRUCTION DETAILS OR MANUFACTURER'S SPECIFICATIONS
 FOR THE DRYER EXHAUST DUCT PLENUM ENCLOSURE- SECTION
 504.4. B) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE
 DRYER THAT LISTS THE MAXIMUM LENGTH OF THE EXHAUST DUCT
 RUN- 504.8.4. C) PROVIDE A DRAWING THAT SHOWS THE TOTAL
 RUN LENGTH OF THE EXHAUST DUCT FROM THE DRYER OUTLET
  
 TO THE SHAFT INCLUDING SEGMENTED LENGTH MEASUREMENTS,
 AND THE EQUIVALENT LENGTHS OF THE ELBOWS- 504.8.4. D)
 INDICATE WHICH SUBDUCT DETAIL ON SHEET M2.4 IS
 APPLICABLE TO THE DRYER EXHAUST. E) PROVIDE MAKEUP AIR
 FOR THE DRYER PER SECTION 504.6.
  
 11) M2.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 COOKTOPS, THE OVENS, AND THE RECIRCULATING DOWN DRAFT
 EXHAUST SYSTEMS. NO HOODS ARE SHOWING ON THE PLANS FOR
 THE OVENS, HOWEVER THEY MAY BE REQUIRED PER
 MANUFACTURER'S SPECIFICATIONS. PLEASE NOTE THAT
 COMMERCIAL COOKING APPLIANCES ARE NOT PERMITTED FOR USE
 IN DWELLING UNITS- SECTION 917.2 FBC-17 MECHANICAL, AND
  
 623.3 FBC-17 FUEL GAS.
  
 12) M2.1 FOR GAS-FIRED COOKING APPLIANCES, INDICATE HOW
 COMBUSTION AIR IS BEING PROVIDED AND PROVIDE
 CALCULATIONS- SECTION 304 FBC-17 FUEL GAS.
  
 13) M2.1, MASTER BATH 133: THE PLAN DOES NOT CLEARLY
 SHOW HOW THE EXHAUST SYSTEMS ARE WORKING IN BATHS 134A
 AND 135A. IT APPEARS THAT THE EF-B'S ARE CONNECTING TO
 THE RETURN AIR PLENUM PER NOTE #6 , HOWEVER NOTE #23
 INDICATES THE RETURN GRILLS ARE PROVIDED OUTDOOR AIR.
 A) REFER TO FOOTNOTE G TABLE 403.3 WHICH LIMITS
 RECIRCULATION OF AIR FROM THE BATHROOMS TO 10% OF THE
 TOTAL
  
 SUPPLY AIR PROVIDED TO THE SPACES. THE PLAN APPEARS TO
 INDICATE NON-COMPLIANCE.
  
 14) M2.1: EXHAUST IS REQUIRED FOR BATHROOMS 119B, 120B,
 AND 121B. THE PLAN SHOWS EXHAUST PROVIDED ONLY FOR THE
 SHOWERS.
  
 15) M2.4: PLEASE INDICATE WHICH OF THE SUBDUCT DETAILS
 IS FOR THE TOILET EXHAUST.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-09-04 Cont ID  
Sent By gjohnson Date 2018-09-04 Time 10:12 Rev Time 0.00
Received By gjohnson Date 2018-09-02 Time 11:04 Sent To  
Notes
2018-09-04 10:13:44PROVISO:
 SHALL PROVIDE BEFORE ROUGH INSPECTIONS
 1. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR COOK TOP.
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR DRYER VENT.
 3. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR MASTER TUB DRAIN.
 PER WPB AMEND TO FBC 107.2.1
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-05-16 Cont ID  
Sent By gjohnson Date 2018-05-16 Time 10:43 Rev Time 0.00
Received By gjohnson Date 2018-05-15 Time 16:44 Sent To  
Notes
2018-05-16 11:29:141ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THIS BUILDING IS REQUIRED TO COMPLY WITH THE FAIR
 HOUSING ACT PLEASE INDICATE ON THE PLAN WHICH DESIGN
 DOCUMENT THAT WAS USED IN DESIGNING THIS UNIT TO COMPLY
 WITH FHA . PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE INDICATE ON THE PLAN WHICH BATHROOM OR
 BATHROOMS ARE USABLE AND WHICH DESIGN SPECIFICATION A
 OR B THAT WAS USED TO COMPLY WITH FHA REQUIREMENTS # 6
 +7
  
 3. PLEASE PROVIDE A ENLARGED FLOOR PLAN SHOWING THE
 REQUIRED CLEAR FLOOR SPACE FHA REQUIREMENTS # 7
  
 4. PROVIDE ELEVATION DETAILS SHOWING MOUNTING HEIGHTS
 FOR THE GRAB BAR BACKING PER FHA REQUIREMENT # 6
  
 5. SHT. P-3.2 THE DETAIL FOR THE KITCHEN AND PANTRY
 SHOWS A STACK THAT IS NOT LABELED OR SIZED IT HAS A
 CLEAN OUT BUT NO FIXTURE ITS LOCATED NEXT TO THE SK
 PLEASE LABEL AND SIZE. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2019-02-15 Cont ID  
Sent By shill Date 2019-02-15 Time 17:00 Rev Time 0.00
Received By shill Date 2019-02-15 Time 17:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2019-02-11 Cont ID  
Sent By ccole Date 2019-02-11 Time 12:47 Rev Time 0.00
Received By ccole Date 2019-02-11 Time 12:47 Sent To  
Notes
2019-02-11 12:49:364TH REVIEW FBC-2010 MECHANICAL
 PERMIT #18031052
 2/11/19
  
 1) SHEET A4.6 NOT DIGITALLY SIGNED AND SEALED- SEE
 PREVIOUS REVIEW COMMENT FROM 12/21/2018 BELOW.
  
  
 ****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 NEW PAGE A4.6 IS NOT DIGITALLY SIGNED (OTHER PAGES OK).
  
 THE PREVIOUSLY PASSED SIGNATURE REVIEWS HAVE BEEN
 FAILED TO PREVENT THE PERMIT FROM BEING PRINTED IN
 ERROR.
  
 PROVIDE DIGITALLY SIGNED PAGES AS REQUIRED BY FLORIDA
 STATUTE 471, 481.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 17:32 Rev Time 0.00
Received By shill Date 2018-12-21 Time 17:32 Sent To  
Notes
2018-12-21 17:35:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 NEW PAGE A4.6 IS NOT DIGITALLY SIGNED (OTHER PAGES OK).
  
 THE PREVIOUSLY PASSED SIGNATURE REVIEWS HAVE BEEN
 FAILED TO PREVENT THE PERMIT FROM BEING PRINTED IN
 ERROR.
  
 PROVIDE DIGITALLY SIGNED PAGES AS REQUIRED BY FLORIDA
 STATUTE 471, 481.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-02 Time 17:00 Rev Time 0.00
Received By shill Date 2018-09-02 Time 17:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By aclange Date 2018-04-06 Time 15:24 Rev Time 0.00
Received By aclange Date 2018-04-06 Time 15:24 Sent To  
Notes
2018-05-09 11:35:14MECH DIG/SIGS OK
 CCOLE-5/8/18
2018-04-06 15:24:42ALL SIGNATURES OK.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved