Plan Review Details - Permit 18031000
Plan Review Stops For Permit 18031000
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-07-02 Cont ID  
Sent By jgomez Date 2018-07-02 Time 18:24 Rev Time 0.00
Received By jgomez Date 2018-07-02 Time 16:30 Sent To  
Notes
2018-07-02 18:18:01BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE INFILL DETAILS A, B, C AND E:
 A) COORDINATE WOOD STUDS AND CONNECTORS. 2X10 WOOD
 STUDS CAN NOT BE INSTALLED WITH SIMPSON SP6 CONNECTORS.
 B) PROVIDE CLEAR SPECIFICATIONS FOR ATTACHMENT OF TOP
 AND BOTTOM PLATES. TAPCON SIZE IS NOT CLEAR. ARCHITECT
 OF RECORD TO VERIFY THAT ANCHOR SPACING IS ADEQUATE TO
 RESIST THE WIND LOADS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-06-07 Cont ID  
Sent By jgomez Date 2018-06-07 Time 11:28 Rev Time 0.00
Received By jgomez Date 2018-06-07 Time 09:23 Sent To  
Notes
2018-06-07 09:28:28RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 1- A) IT LOOKS LIKE WINDOW IN BEDROOM #2 DOESN'T COMPLY
 WITH ALL THE EGRESS REQUIREMENTS OF SEC. R210
 FBC-RESIDENTIAL. DESIGN PROFESSIONAL TO PROVIDE SIZE
 AND TYPE OF WINDOW SHOWING COMPLIANCE.
  
 B) DESIGN PROFESSIONAL TO SPECIFY TYPE AND SIZE OF ALL
 NEW WINDOWS SHOWN ON PLANS. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) NEW WINDOWS AS SHOWN ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE.
 RESPONSE: REPEAT COMMENT.
  
 3- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE
 IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
  
 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS.
 SEC. R609.7.2.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-25 Cont ID  
Sent By jgomez Date 2018-05-25 Time 15:21 Rev Time 0.00
Received By jgomez Date 2018-05-25 Time 15:21 Sent To  
Notes
2018-05-25 15:23:01CONTRACTOR DIDN'T ADDRESS COMMENTS. SAME CHECKLIST
 APPLIES FOR RESUBMITTAL. JG.
  
  
  
 RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE COMPLETE DRAWINGS DRAWN TO SCALE AND SHOWING
 COMPLIANCE WITH ALL THE LOADS AS REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL. CONSTRUCTION DOCUMENTS TO
 SPECIFY ALL OPENINGS DIMENSIONS, REINFORCEMENT OF
 OPENING TO BE WIDENED INCLUDING, STRUCTURAL BEAM, ETC.
 ALSO, SPECIFY WINDOWS DESIGN PRESSURES.
  
 DESIGN CRITERIA
 SEC. R301.1 APPLICATION.
 BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD
 LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS,
 WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS
 CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES
 CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO
 COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
  
 2- PROVIDE COMPLETE FLOOR PLANS SHOWING THE NEW LAUNDRY
 ROOM DIMENSIONS/ FRAMING AND COMPLETE
 PLANS/SPECIFICATIONS FOR THE KITCHEN REMODELING. AND,
 DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) NEW WINDOWS A SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE.
  
 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS.
 SEC. R609.7.2.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-02 Cont ID  
Sent By jgomez Date 2018-04-02 Time 12:05 Rev Time 0.00
Received By jgomez Date 2018-04-02 Time 10:40 Sent To  
Notes
2018-04-02 12:05:36RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- PROVIDE COMPLETE DRAWINGS DRAWN TO SCALE AND SHOWING
 COMPLIANCE WITH ALL THE LOADS AS REQUIRED BY SEC.
 R301.1 FBC-RESIDENTIAL. CONSTRUCTION DOCUMENTS TO
 SPECIFY ALL OPENINGS DIMENSIONS, REINFORCEMENT OF
 OPENING TO BE WIDENED INCLUDING, STRUCTURAL BEAM, ETC.
 ALSO, SPECIFY WINDOWS DESIGN PRESSURES.
  
 DESIGN CRITERIA
 SEC. R301.1 APPLICATION.
 BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE
 CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD
 LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS,
 WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS
 CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL
 RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH
 THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS
 FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES
 CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO
 COMPLY WITH THE REQUIREMENTS OF THIS SECTION.
  
 2- PROVIDE COMPLETE FLOOR PLANS SHOWING THE NEW LAUNDRY
 ROOM DIMENSIONS/ FRAMING AND COMPLETE
 PLANS/SPECIFICATIONS FOR THE KITCHEN REMODELING. AND,
 DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL
 THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5).
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) NEW WINDOWS A SHOWN ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH
 THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE.
  
 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS.
 SEC. R609.7.2.1 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-06-27 Cont ID  
Sent By ppetty Date 2018-06-27 Time 14:14 Rev Time 0.00
Received By ppetty Date 2018-06-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By ppetty Date 2018-05-17 Time 09:49 Rev Time 0.00
Received By ppetty Date 2018-05-17 Time 09:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-09 Cont ID  
Sent By jpearson Date 2018-04-09 Time 15:40 Rev Time 0.00
Received By jpearson Date 2018-04-09 Time 14:33 Sent To I
Notes
2018-04-09 15:40:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 2. PROVIDE ELECTRICAL PLAN WITH A MINIMUM 1/8 INCH
 SCALE. "BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES." WPB FBC 107.2.1.3
 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE
 E3706.2, E3902
 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE
 EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC
 RE R314.3, R315.1; WPB FBC 107.2.1
 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2018-07-05 Cont ID  
Sent By lcrespo Date 2018-07-05 Time 16:14 Rev Time 0.00
Received By lcrespo Date 2018-07-05 Time 16:14 Sent To  
Notes
2018-07-06 07:29:4807/05/18 APPROVED BY PLUMBING AND SENT TO PROCESSING,
 LAC

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-06-01 Cont ID  
Sent By lcrespo Date 2018-06-01 Time 17:58 Rev Time 0.00
Received By lcrespo Date 2018-06-01 Time 17:58 Sent To  
Notes
2018-06-01 17:59:4706/01/2018 3RD GAS REVIEW**DENIED** WITH COMMENTS NOTE
 - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME
 AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED
 FOR THIS MASTER PERMIT.
  
 1. PLEASE COMBINE YOUR TWO ISOMETRIC DRAWINGS INTO ONE
 AND PUT THE TABLE NUMBER YOU ARE USING. WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017
 FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES
 DRYERS).
 3. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A
 ROOF. WPB AMEND. TO FBC SEC. 107.2.1
 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL.
 FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-25 Cont ID  
Sent By lcrespo Date 2018-05-25 Time 15:15 Rev Time 0.00
Received By lcrespo Date 2018-05-25 Time 15:15 Sent To  
Notes
2018-05-25 15:16:0903/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS,
 SECOND REQUEST
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 A SEPERATE GAS APPICATION AND INSPECTION IS REQUIRED
 FOR THIS MASTER PERMIT
  
 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC FUEL GAS RES. SEC.
 G2420.4.
 3. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS RES. SEC. G2413.2 AND G2404.3.
 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 7. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE POOL
 HEATER SHOW ON GAS ISOMERIC, APPLIANCE CONNECTION 2017
 FBC FUEL GAS RES. SEC. 2415.15.
 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 9. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN
 PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE
 DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-29 Cont ID  
Sent By lcrespo Date 2018-03-29 Time 15:21 Rev Time 0.00
Received By lcrespo Date 2018-03-29 Time 15:21 Sent To  
Notes
2018-03-29 14:33:5903/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 A SEPERATE GAS APPICATION AND INSPECTION IS REQUIRED
 FOR THIS MASTER PERMIT
  
 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC FUEL GAS RES. SEC.
 G2420.4.
 3. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC.
 G2408.1.
 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL
 GAS RES. SEC. G2413.2 AND G2404.3.
 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL
 GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, &
 G2413.3.
 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
 7. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE POOL
 HEATER SHOW ON GAS ISOMERIC, APPLIANCE CONNECTION 2017
 FBC FUEL GAS RES. SEC. 2415.15.
 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 9. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN
 PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE
 DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS.
  
 SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY
 RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING,
 IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING
 EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED
 SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-07-05 Cont ID  
Sent By lcrespo Date 2018-07-05 Time 16:14 Rev Time 0.00
Received By lcrespo Date 2018-06-18 Time 07:43 Sent To  
Notes
2018-07-03 14:31:267/3 TO LC DESK FOR GAS REVIEW
  
  
2018-06-20 07:43:21R03

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-06-07 Cont ID  
Sent By jgomez Date 2018-06-07 Time 11:34 Rev Time 0.00
Received By jgomez Date 2018-05-25 Time 10:03 Sent To I
Notes
2018-05-30 10:03:16RESUB ROUTED TO LCRESPO

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-05-25 Cont ID  
Sent By jgomez Date 2018-05-25 Time 15:23 Rev Time 0.00
Received By jgomez Date 2018-05-11 Time 14:32 Sent To  
Notes
2018-05-14 14:33:11R02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-23 Time 13:23 Sent To  
Notes
2018-03-26 13:23:47R05

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2018-04-02 Cont ID  
Sent By jgomez Date 2018-04-02 Time 12:13 Rev Time 0.00
Received By jgomez Date 2018-04-02 Time 12:13 Sent To  
Notes
2018-04-02 12:13:53NO MECHANICAL WORK SHOWN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-03-29 Cont ID  
Sent By lcrespo Date 2018-03-29 Time 15:22 Rev Time 0.00
Received By lcrespo Date 2018-03-29 Time 15:22 Sent To  
Notes
2018-03-29 15:24:31A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED
 FOR THIS MASTER PERMIT.
  
 03/29/18 APPROVED BY PLUMBING AND PUT BACK IN R5, LAC