Plan Review Details - Permit 18031000
| Plan Review Stops For Permit 18031000 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2018-07-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-07-02 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-07-02 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2018-07-02 18:18:01 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE INFILL DETAILS A, B, C AND E: | | | A) COORDINATE WOOD STUDS AND CONNECTORS. 2X10 WOOD | | | STUDS CAN NOT BE INSTALLED WITH SIMPSON SP6 CONNECTORS. | | | B) PROVIDE CLEAR SPECIFICATIONS FOR ATTACHMENT OF TOP | | | AND BOTTOM PLATES. TAPCON SIZE IS NOT CLEAR. ARCHITECT | | | OF RECORD TO VERIFY THAT ANCHOR SPACING IS ADEQUATE TO | | | RESIST THE WIND LOADS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-06-07 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-06-07 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2018-06-07 09:28:28 | RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW | | | CHECKLIST. | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- A) IT LOOKS LIKE WINDOW IN BEDROOM #2 DOESN'T COMPLY | | | WITH ALL THE EGRESS REQUIREMENTS OF SEC. R210 | | | FBC-RESIDENTIAL. DESIGN PROFESSIONAL TO PROVIDE SIZE | | | AND TYPE OF WINDOW SHOWING COMPLIANCE. | | | | | | B) DESIGN PROFESSIONAL TO SPECIFY TYPE AND SIZE OF ALL | | | NEW WINDOWS SHOWN ON PLANS. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) NEW WINDOWS AS SHOWN ON PLANS. | | | RESPONSE: REPEAT COMMENT. | | | | | | B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK | | | SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH | | | THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE. | | | RESPONSE: REPEAT COMMENT. | | | | | | 3- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE | | | IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT | | | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS | | | | | | 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS. | | | SEC. R609.7.2.1 FBC-RESIDENTIAL. | | | RESPONSE: REPEAT COMMENT. | | | | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-25 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-25 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2018-05-25 15:23:01 | CONTRACTOR DIDN'T ADDRESS COMMENTS. SAME CHECKLIST | | | APPLIES FOR RESUBMITTAL. JG. | | | | | | | | | | | | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- PROVIDE COMPLETE DRAWINGS DRAWN TO SCALE AND SHOWING | | | COMPLIANCE WITH ALL THE LOADS AS REQUIRED BY SEC. | | | R301.1 FBC-RESIDENTIAL. CONSTRUCTION DOCUMENTS TO | | | SPECIFY ALL OPENINGS DIMENSIONS, REINFORCEMENT OF | | | OPENING TO BE WIDENED INCLUDING, STRUCTURAL BEAM, ETC. | | | ALSO, SPECIFY WINDOWS DESIGN PRESSURES. | | | | | | DESIGN CRITERIA | | | SEC. R301.1 APPLICATION. | | | BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE | | | CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD | | | LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS, | | | WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS | | | CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN | | | ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL | | | RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH | | | THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS | | | FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING | | | ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES | | | CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO | | | COMPLY WITH THE REQUIREMENTS OF THIS SECTION. | | | | | | 2- PROVIDE COMPLETE FLOOR PLANS SHOWING THE NEW LAUNDRY | | | ROOM DIMENSIONS/ FRAMING AND COMPLETE | | | PLANS/SPECIFICATIONS FOR THE KITCHEN REMODELING. AND, | | | DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL | | | THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE | | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) NEW WINDOWS A SHOWN ON PLANS. | | | | | | B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK | | | SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH | | | THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE. | | | | | | 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS. | | | SEC. R609.7.2.1 FBC-RESIDENTIAL. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-04-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-02 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-02 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2018-04-02 12:05:36 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS | | | CODE: FBC 6TH EDITION (2017). | | | | | | 1- PROVIDE COMPLETE DRAWINGS DRAWN TO SCALE AND SHOWING | | | COMPLIANCE WITH ALL THE LOADS AS REQUIRED BY SEC. | | | R301.1 FBC-RESIDENTIAL. CONSTRUCTION DOCUMENTS TO | | | SPECIFY ALL OPENINGS DIMENSIONS, REINFORCEMENT OF | | | OPENING TO BE WIDENED INCLUDING, STRUCTURAL BEAM, ETC. | | | ALSO, SPECIFY WINDOWS DESIGN PRESSURES. | | | | | | DESIGN CRITERIA | | | SEC. R301.1 APPLICATION. | | | BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE | | | CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD | | | LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS, | | | WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS | | | CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN | | | ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL | | | RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH | | | THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS | | | FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING | | | ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES | | | CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO | | | COMPLY WITH THE REQUIREMENTS OF THIS SECTION. | | | | | | 2- PROVIDE COMPLETE FLOOR PLANS SHOWING THE NEW LAUNDRY | | | ROOM DIMENSIONS/ FRAMING AND COMPLETE | | | PLANS/SPECIFICATIONS FOR THE KITCHEN REMODELING. AND, | | | DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE | | | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL | | | THAT IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND | | | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. | | | SUCH DRAWINGS AND SPECIFICATIONS SHALL | | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | | AS TO THE QUALITY OF MATERIALS, WHERE | | | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL | | | CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN. (SEE ALSO SECTION 107.3.5). | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.001 FOR: | | | A) NEW WINDOWS A SHOWN ON PLANS. | | | | | | B) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK | | | SIZE OF MULLION TO BE USED TO VERIFY COMPLIANCE WITH | | | THE DESIGN PRESSURES. COORDINATE WITH ITEM #1 ABOVE. | | | | | | 4- PROVIDE STRUCTURAL BUCK DETAILS FOR NEW WINDOWS. | | | SEC. R609.7.2.1 FBC-RESIDENTIAL. | | | | | | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2018-06-27 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-06-27 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-06-27 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-05-17 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2018-05-17 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2018-05-17 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-04-09 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-04-09 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-04-09 |
Time |
14:33 |
Sent To |
I |
|
| Notes |
| 2018-04-09 15:40:18 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2017 6TH ED. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON | | | RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS | | | 481.229; WPB FBC 107.2.1, 107.3.5.1.2 | | | 2. PROVIDE ELECTRICAL PLAN WITH A MINIMUM 1/8 INCH | | | SCALE. "BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 | | | INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER | | | ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS | | | AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO | | | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE | | | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, | | | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. | | | ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE | | | REQUIREMENTS OF FLORIDA STATUTES." WPB FBC 107.2.1.3 | | | 3. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED | | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE | | | E3706.2, E3902 | | | 4. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED | | | PER CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | RE R314.3, R315.1; WPB FBC 107.2.1 | | | 5. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A | | | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 | | | 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE | | | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF | | | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL | | | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. | | | FBC EC R404.1 | | | 7. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC | | | 210.8(D); FBC RE E3902.10 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-07-05 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-07-05 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2018-07-06 07:29:48 | 07/05/18 APPROVED BY PLUMBING AND SENT TO PROCESSING, | | | LAC |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2018-06-01 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-06-01 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-06-01 |
Time |
17:58 |
Sent To |
|
|
| Notes |
| 2018-06-01 17:59:47 | 06/01/2018 3RD GAS REVIEW**DENIED** WITH COMMENTS NOTE | | | - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS TIME | | | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED | | | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED | | | FOR THIS MASTER PERMIT. | | | | | | 1. PLEASE COMBINE YOUR TWO ISOMETRIC DRAWINGS INTO ONE | | | AND PUT THE TABLE NUMBER YOU ARE USING. WPB AMENDMENTS | | | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 | | | FBC FUEL GAS SEC. 304.1, 614.5 (CLOTHES DRYERS) OR 2017 | | | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES | | | DRYERS). | | | 3. INDICATE ON THE PLAN IF THE GRILL IS LOCATED UNDER A | | | ROOF. WPB AMEND. TO FBC SEC. 107.2.1 | | | 4. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. | | | FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-05-25 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-05-25 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2018-05-25 15:16:09 | 03/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS, | | | SECOND REQUEST | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | A SEPERATE GAS APPICATION AND INSPECTION IS REQUIRED | | | FOR THIS MASTER PERMIT | | | | | | 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR | | | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC FUEL GAS RES. SEC. | | | G2420.4. | | | 3. SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. | | | G2408.1. | | | 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL | | | GAS RES. SEC. G2413.2 AND G2404.3. | | | 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL | | | GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & | | | G2413.3. | | | 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC | | | FUEL GAS RES. SEC. G2421.1. | | | 7. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE POOL | | | HEATER SHOW ON GAS ISOMERIC, APPLIANCE CONNECTION 2017 | | | FBC FUEL GAS RES. SEC. 2415.15. | | | 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION | | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND | | | DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 9. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN | | | PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE | | | DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-03-29 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-03-29 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2018-03-29 14:33:59 | 03/29/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | A SEPERATE GAS APPICATION AND INSPECTION IS REQUIRED | | | FOR THIS MASTER PERMIT | | | | | | 1. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE | | | CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR | | | EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. FBC FUEL GAS RES. SEC. | | | G2420.4. | | | 3. SUBMIT MANUFACTURER?S SPECIFICATION | | | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO | | | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. | | | G2408.1. | | | 4. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE | | | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT | | | SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL | | | GAS RES. SEC. G2413.2 AND G2404.3. | | | 5. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE | | | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM | | | THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE | | | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL | | | GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & | | | G2413.3. | | | 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | | INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC | | | FUEL GAS RES. SEC. G2421.1. | | | 7. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE POOL | | | HEATER SHOW ON GAS ISOMERIC, APPLIANCE CONNECTION 2017 | | | FBC FUEL GAS RES. SEC. 2415.15. | | | 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE | | | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION | | | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN | | | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER | | | HEATER SHALL COMPLY WITH THE MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND | | | DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. | | | INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 9. A SET OF PLANS HAS BEEN SUBMITTED THAT IS DRAWN IN | | | PENCIL. PLANS DONE IN PENCIL ARE UNACCEPTABLE AS THE | | | DRAWING CAN BE MODIFIED/CHANGED. WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1.4 QUALITY OF BUILDING PLANS. | | | | | | SUBMITTAL OF ADDITIONAL AND/OR REVISED MATERIALS MAY | | | RESULT IN NEW PLAN REVIEW COMMENTS. WHEN RESUBMITTING, | | | IT IS HELPFUL TO PROVIDE A RESPONSE LETTER ADDRESSING | | | EACH ITEM ALONG WITH THE CITY RESUBMITTAL FORM. | | | ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL | | | SUBMITTAL AND REMOVE OR VOID THE PREVIOUSLY REVIEWED | | | SHEETS. | | | | | | LUIS A. CRESPO | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | [email protected] | | | 561-805-6720 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2018-07-05 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-07-05 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-06-18 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2018-07-03 14:31:26 | 7/3 TO LC DESK FOR GAS REVIEW | | | | | | | | 2018-06-20 07:43:21 | R03 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2018-06-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-06-07 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-25 |
Time |
10:03 |
Sent To |
I |
|
| Notes |
| 2018-05-30 10:03:16 | RESUB ROUTED TO LCRESPO |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-05-25 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-05-25 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-05-11 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-03-23 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2018-04-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2018-04-02 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2018-04-02 |
Time |
12:13 |
Sent To |
|
|
| Notes |
| 2018-04-02 12:13:53 | NO MECHANICAL WORK SHOWN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2018-03-29 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2018-03-29 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2018-03-29 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2018-03-29 15:24:31 | A SEPARATE GAS APPLICATION AND INSPECTION IS REQUIRED | | | FOR THIS MASTER PERMIT. | | | | | | 03/29/18 APPROVED BY PLUMBING AND PUT BACK IN R5, LAC |
|
|
|
Account Summary | Usage Policy | Privacy Policy