Plan Review Details - Permit 18030997
Plan Review Stops For Permit 18030997
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-04-04 Cont ID  
Sent By aclange Date 2018-04-04 Time 14:19 Rev Time 0.00
Received By aclange Date 2018-04-04 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-06-12 Cont ID  
Sent By jpearson Date 2018-06-12 Time 13:25 Rev Time 0.00
Received By jpearson Date 2018-06-12 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-12 Cont ID  
Sent By jpearson Date 2018-04-12 Time 14:48 Rev Time 0.00
Received By jpearson Date 2018-04-12 Time 14:33 Sent To  
Notes
2018-04-12 14:32:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PANEL SCHEDULES SHOW NEW CIRCUITS BEING ADDED, BUT
 NO PLAN IS PROVIDED DETAILING LOCATION AND QUANTITY OF
 LIGHT FIXTURES OR THE DETAILS OF FEATURE PUMP. PROVIDE
 ELECTRICAL PLAN FOR REVIEW. FBC 107.2.1, 107.3.5
 2. PROVIDE EXTERIOR LIGHTING CONTROLS AS SPECIFIED IN
 THE FBC ENERGY CONSERVATION. FBC EC C405.2.5
 3. PROVIDE DETAILS OF COMPLIANCE WITH FBC EC C404.9.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-04-25 Cont ID  
Sent By tklarge Date 2018-04-25 Time 10:10 Rev Time 0.00
Received By tklarge Date 2018-04-25 Time 10:10 Sent To  
Notes
2018-04-25 10:11:30THERE IS NO GAS WORK BEING DONE UNDER THIS PERMIT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-07-05 Cont ID  
Sent By gjohnson Date 2018-07-05 Time 11:31 Rev Time 0.00
Received By gjohnson Date 2018-05-22 Time 15:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-05-04 Cont ID  
Sent By cpuell Date 2018-05-04 Time 16:01 Rev Time 0.00
Received By cpuell Date 2018-03-29 Time 13:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-07-05 Cont ID  
Sent By gjohnson Date 2018-07-05 Time 11:28 Rev Time 0.00
Received By gjohnson Date 2018-07-05 Time 11:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-25 Cont ID  
Sent By tklarge Date 2018-04-25 Time 10:10 Rev Time 0.00
Received By tklarge Date 2018-04-19 Time 09:34 Sent To  
Notes
2018-04-24 09:57:511) SUBMIT A COPY OF THE DEPT. OF HEALTH APPLICATION FOR
 POOL MODIFICATION FORM DH 4159 SHOWING VERIFICATION
 THAT THE DOH HAS RECEIVED THE APPLICATION.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE PUMP, SWIMMING
 POOL, SPA MAIN DRAIN AND FOUNTAIN.. WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) CLARIFY THE REASON FOR THE 1 1/2 INCH VENTS SHOWN ON
 THE GUTTTER SYSTEM ON SHT. P4.
 4) SHT. P4 - SHOW THE CONTINUATION OF THE RETURN LINE
 FROM THE POOL TO THE COLLECTOR TANK ON THE PLAN.
 5) SHT.P-5 - POOL PUMP CURVE - SUBMIT A LEGEND FOR THE
 BOXES A-F ON THE PUMP CURVE.
 6) SHT. P7 - 2017 FBC SEC.454.1.6.5.3.1 - THE LIP OF
 THE GUTTER SHALL BE UNIFORMLY LEVEL WITH A MAXIMUM
 TOLERANCE OF 1/4 INCH BETWEEN THE HIGH & LOW AREAS.
 7) SHT. P7 - OPEN TYPE GUTTERS SHALL COMPLY WITH 2017
 FBC 454.1.6.5.3.1.1.
 8) IDENTIFY THE TYPE OF GUTTER SYSTEM BEING INSTALLED,
 E.G."OPEN TYPE," "DECK LEVEL PERIMETER OVERFLOW", ETC.
 SO THE PROPER CODE SECTIONS CAN BE APPLIED.
 9) THE POOL DECK SHALL SHALL HAVE A MINIMUM OF 2% AND
 MAXIMUM 4% UNIFORM AWAY FROM THE POOL OR TO DECK
 DRAINS. 2017 FBC SEC. 454.1.3.1.2.
 10) THE GUTTER SHALL SLOPE 2 INCHES, +/- 1/4 INCH FROM
 THE LIP TO THE DRAINS. 2017 FBC SEC.454.1.6.5.3.1.1.
 11) INDICATE THE DIMENSIONS OF THE SLOTTED OPENINGS ON
 THE STONE GUTTER GRATE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-07-05 Cont ID  
Sent By lmarchan Date 2018-07-05 Time 13:49 Rev Time 0.00
Received By lmarchan Date 2018-07-05 Time 13:49 Sent To  
Notes
2018-07-05 11:30:527/5/18 DIG SIG PLUMB OK/GPJ
2018-04-04 14:20:14STRUCTURAL SIGNATURES OK.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-07-03 Cont ID  
Sent By aaponte Date 2018-07-03 Time 15:12 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-05-04 Cont ID  
Sent By AA Date 2018-05-04 Time 09:19 Rev Time 0.00
Received By aaponte Date 2018-05-04 Time 09:19 Sent To  
Notes
2018-05-04 09:21:48NEW POOL EQUIPMENT IS LOCATED ON EXISTING PLANTING
 AREA. LANDSCAPE AREA CANNOT BE REMOVED FOR EQUIPMENT
 UNLESS LANDSCAPE AREA IS REPLACED IN A NEW LOCATION.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.