Plan Review Details - Permit 18030987
Plan Review Stops For Permit 18030987
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-04-10 Cont ID  
Sent By jleahy Date 2018-04-10 Time 16:18 Rev Time 0.00
Received By jleahy Date 2018-04-10 Time 16:18 Sent To  
Notes
2018-04-10 16:18:48PLANS NEED TO SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN OF THE SYSTEM.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-03-28 Cont ID  
Sent By jleahy Date 2018-03-28 Time 11:47 Rev Time 0.00
Received By jleahy Date 2018-03-28 Time 11:47 Sent To I
Notes
2018-03-28 11:50:35FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT CUT SHEETS ON ALL EQUIPMENT.
  
 VALUE FOR JOB IS LOW, PLEASE SUBMIT A SIGNED CONTRACT
 FOR WORK.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-26 Cont ID  
Sent By scaldero Date 2018-03-26 Time 11:46 Rev Time 0.00
Received By scaldero Date 2018-03-26 Time 11:40 Sent To E
Notes
2018-03-26 11:46:40PERMIT # 18030987
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO:
  
 THE FOLLOWING REQUIREMENTS WILL BE VERIFIED IN THE
 FIELD AS A CONDITION OF APPROVAL:
  
 PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-10 Cont ID  
Sent By jleahy Date 2018-04-10 Time 16:19 Rev Time 0.00
Received By jleahy Date 2018-03-29 Time 13:12 Sent To  
Notes
2018-03-30 13:13:03RESUB ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-28 Cont ID  
Sent By jleahy Date 2018-03-28 Time 11:50 Rev Time 0.00
Received By jleahy Date 2018-03-22 Time 14:44 Sent To  
Notes
2018-03-23 14:44:24ROUTED TO FIRE INBOX