Plan Review Details - Permit 18030885
Plan Review Stops For Permit 18030885
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-04-18 Cont ID  
Sent By shill Date 2018-04-18 Time 09:10 Rev Time 0.00
Received By shill Date 2018-04-18 Time 09:10 Sent To  
Notes
2018-04-18 09:12:29***PROVISO***
  
 APPROVED ASSEMBLY WAS NOT SELECTED. ENGINEERING FOR
 ENHANCED FASTENING WAS NOT PROVIDED, FBC BUILDING 1609.
  
 THIS PERMIT IS ISSUED AT APPLICANT'S RISK. AT
 INSPECTION, PROVIDE ENGINEERING (RAS 117 CALCULATIONS).
 THE ENGINEERING SHOULD ALSO SPECIFY THE ASSEMBLY
 PROPOSED.
  
 THIS PERMIT IS BEING ISSUED WITHOUT THE REQUIRED
 INFORMATION AS THE ROOF HAS BEEN LEAKING FOR WEEKS.
 OWNER WAS ADVISED THAT, IF THE INSTALLATION IS NOT DONE
 IN ACCORDANCE WITH THE CODE OR THE ENGINEERING IS NOT
 PROVIDED, ADDITIONAL WORK OR ADDITIONAL ENGINEERING MAY
 BE REQUIRED.
  
  
  
 INTERNAL USE ONLY RE: HISTORIC:
  
 SPOKE WITH F.MITTNER; SHE DOES NOT NEED TO RE-REVIEW
 PLAN. SCOPE PROPOSED (EXISTING ROOF, ROOF STRUCTURE,
 COLUMNS AND BEAMS TO REMAIN OR BE REPAIRED/REPLACED IN
 SAME LOCATION AS NEEDED), WALLS INSTALLED WITHOUT
 PERMIT TO BE REMOVED, REROOF ENTIRE BUILDING) IS OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By cthroop Date 2018-04-06 Time 13:54 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 13:31 Sent To  
Notes
2018-04-06 14:00:37BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PLAN IS INCONSISTANT WITH SCOPE OF WORK ON
 APPLICATION.
 2. SOW DIRECTS THE REMOVAL OF THE ILLEGAL ADDITION.
 3. PLANS SHOW LEAVING THE COLUMNS AND BEAMS.
 4. HAVE THE ENGINEER OF RECORD DEMONSTRATE THE
 STABILITY OF THE COLUMNS AND BEAMS WITHOUT A ROOF
 DIAPHRAM. YOU MAY SUBMIT A SIGNED AND SEALED LETTER ON
 HIS LETTERHEAD TO SATISFY THIS REQUIREMENT.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-03-30 Cont ID  
Sent By fmittner Date 2018-03-30 Time 15:14 Rev Time 0.00
Received By fmittner Date 2018-03-30 Time 15:14 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-06 Cont ID  
Sent By cthroop Date 2018-04-06 Time 14:09 Rev Time 0.00
Received By cthroop Date 2018-03-21 Time 10:37 Sent To I
Notes
2018-03-23 10:37:17ROUTED TO ZONING INBOX

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-04-06 Cont ID  
Sent By cthroop Date 2018-04-06 Time 13:54 Rev Time 0.00
Received By cthroop Date 2018-04-06 Time 13:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-30 Cont ID  
Sent By fmittner Date 2018-03-30 Time 15:14 Rev Time 0.00
Received By fmittner Date 2018-03-30 Time 15:14 Sent To  
Notes
***NONE***