Plan Review Details - Permit 18030836
| Plan Review Stops For Permit 18030836 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-21 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-21 |
Time |
10:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2018-07-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-02 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-02 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2018-07-02 11:35:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. IT HAS COME TO MY ATTENTION THAT THE PLANS FOR THIS | | | UNIT INCLUDE CHANGES TO WHAT WE CONSIDER "COMMON AREA". | | | THIS CHANGE IS NOT CLOUDED, SO WAS NOT REVIEWED BY THE | | | PREVIOUS REVIEWER. | | | | | | A LOCK HAS BEEN ADDED TO DOOR CN01. IT IS NOT CLEAR HOW | | | EXITING FOR THE ADJACENT UNIT IS AFFECTED; THIS SHOULD | | | BE A REVISION TO THE BASE BUILDING PLAN AND INCLUDE A | | | REVISED LIFE SAFETY PLAN IF THIS WAS PREVIOUSLY SHOWN | | | AS AN EXIT FOR THE ADJACENT UNIT. | | | | | | WHEN RESUBMITTING, ADDRESS THIS COMMENT AS WELL AS | | | COMMENTS FROM PREVIOUS REVIEW. FOR YOUR CONVENIENCE, | | | THEY ARE INCLUDED BELOW. | | | | | | | | | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | | 2017 6TH EDITION | | | | | | 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL | | | BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH | | | EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY | | | CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE | | | REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE. | | | | | | 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS | | | SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. FLOOR SOUND UNDERLAYMENT | | | | | | 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR | | | COMPLIANCE WITH THE 2010 FBC-B SECTIONS: | | | | | | FBC-B 2010 1207.2 AIR-BORNE SOUND. | | | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | | | | THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE | | | SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS | | | SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE | | | DESIGNER OF RECORD. | | | NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE | | | THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W. | | | P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE | | | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE | | | SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO | | | THE BUILDING OFFICIAL ROBERT BROWN. | | | | | | SHEET: FINISHES. UNIT: | | | | | | FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR | | | INSULATION (FBC-B 2010) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE | | | ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS: | | | | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO | | | LOBBY FLOOR. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR | | | WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE | | | BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS | | | AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR | | | THIS ROOM. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM | | | ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS | | | PANELS WILL BE SUPPORTED ON ALL SIDES. | | | | | | FBC 2403.2 GLASS SUPPORTS. | | | WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT | | | FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD | | | CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED | | | SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE | | | PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL. | | | | | | 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED. | | | | | | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 | | | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR | | | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, | | | REPORTS OR OTHER DOCUMENTS. | | | | | | (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING | | | PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER | | | DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY | | | THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE | | | CHARGE. | | | (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT | | | BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE. | | | (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS | | | CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE | | | DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER | | | AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES | | | THE MANUAL SEALING PROCEDURE SET OUT IN RULE | | | 61G1-16.003, F.A.C. | | | (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A | | | DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL | | | ASSURE THAT THE DIGITAL SIGNATURE IS: | | | (A) UNIQUE TO THE PERSON USING IT; | | | (B) CAPABLE OF VERIFICATION; | | | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND | | | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE | | | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE | | | DOCUMENT ARE CHANGED. | | | (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN | | | AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST | | | DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD | | | PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012, | | | WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE | | | BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE | | | S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE | | | INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP | | | S/FIPS180-4/FIPS-180-4.PDF. | | | | | | | | | | | | | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2018-03-27 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-27 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-27 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2018-03-27 11:30:15 | ****PLAN REVIEW COMMENTS**** | | | | | | ART LANGE BUILDING PLANS EXAMINER | | | | | | DEVELOPMENT SERVICES DEPARTMENT | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33402 | | | | | | 561-805-6718 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE | | | 2017 6TH EDITION | | | | | | 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL | | | BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH | | | EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY | | | CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE | | | REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE. | | | | | | 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS | | | SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 3. FLOOR SOUND UNDERLAYMENT | | | | | | 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR | | | COMPLIANCE WITH THE 2010 FBC-B SECTIONS: | | | | | | FBC-B 2010 1207.2 AIR-BORNE SOUND. | | | FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | | | | THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE | | | SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS | | | SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE | | | DESIGNER OF RECORD. | | | NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE | | | THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W. | | | P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE | | | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE | | | SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO | | | THE BUILDING OFFICIAL ROBERT BROWN. | | | | | | SHEET: FINISHES. UNIT: | | | | | | FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR | | | INSULATION (FBC-B 2010) | | | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL | | | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR | | | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE | | | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A | | | 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE | | | ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS: | | | | | | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: | | | | | | 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. | | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | | E 90. | | | | | | 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS | | | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL | | | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A | | | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. | | | | | | 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO | | | LOBBY FLOOR. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR | | | WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE | | | BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS | | | AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR | | | THIS ROOM. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | | | | 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM | | | ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS | | | PANELS WILL BE SUPPORTED ON ALL SIDES. | | | | | | FBC 2403.2 GLASS SUPPORTS. | | | WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT | | | FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD | | | CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED | | | SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE | | | PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL. | | | | | | 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED. | | | | | | ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005 | | | PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR | | | ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS, | | | REPORTS OR OTHER DOCUMENTS. | | | | | | (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING | | | PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER | | | DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF | | | CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY | | | THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE | | | CHARGE. | | | (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT | | | BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE. | | | (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS | | | CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE | | | DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER | | | AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES | | | THE MANUAL SEALING PROCEDURE SET OUT IN RULE | | | 61G1-16.003, F.A.C. | | | (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A | | | DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL | | | ASSURE THAT THE DIGITAL SIGNATURE IS: | | | (A) UNIQUE TO THE PERSON USING IT; | | | (B) CAPABLE OF VERIFICATION; | | | (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND | | | (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE | | | ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE | | | DOCUMENT ARE CHANGED. | | | (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN | | | AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST | | | DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD | | | PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012, | | | WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE | | | BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE | | | S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE | | | INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP | | | S/FIPS180-4/FIPS-180-4.PDF. | | | | | | | | | | | | | | | | | | | | | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: | | | | | | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 | | | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. | | | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED | | | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS | | | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE | | | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE | | | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR | | | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN | | | THE PERMIT PACKAGE. | | | | | | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS | | | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
jpearson |
Date |
2018-08-21 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
jpearson |
Date |
2018-08-21 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2018-04-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2018-04-06 |
Time |
17:25 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2018-04-06 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2018-04-06 15:49:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-101.00 | | | | | | AT THE END OF MOST LIGHTING CIRCUITS THERE IS ASYMBOL A | | | TRIANGLE NOT SHON OF SYMBOL LIST. LIGHTING SYSTEM, IF | | | SO NEED CUT SHEETS | | | | | | MASTER BDROM, STUDY, LIVING RM, DINING RM, FAMILY RM, | | | BDRMS 2,3,4 OUTLET SPACING PER CODE E3901.1, E3901.2.2, | | | FIXED PANELS | | | E3901.2.2 WALL SPACE. | | | AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE | | | FOLLOWING: [210.52(A)(2)] | | | | | | 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH, | | | INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS | | | UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR | | | OPENINGS, FIREPLACES, AND FIXED CABINETS. | | | | | | 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS, | | | EXCLUDING SLIDING PANELS. | | | | | | 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS | | | RAILINGS AND FREESTANDING BAR-TYPE COUNTERS. | | | | | | UTILITY ROOM GFCI, AFCI PER 2014 NEC | | | E3902.9 LAUNDRY AREAS. | | | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES | | | INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT | | | CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL. | | | [210.8(A)(9)] | | | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS | | | | | | KITCHEN OUTLETS | | | E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- | | | AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY | | | ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, | | | DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, | | | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS | | | | | | BATH OUTLETS FRO TV AND OTHER APPLIANCES | | | E3902.7 SINK RECEPTACLES. | | | 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES | | | THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE | | | EDGE OF A SINK SHALL HAVE GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. | | | RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP | | | POSITION IN THE WORK SURFACES OR COUNTERTOPS. | | | [210.8(A)(7)] | | | | | | E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES. | | | 125-VOLT, SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES | | | THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE | | | EDGE OF A BATHTUB OR SHOWER STALL SHALL HAVE | | | GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR | | | PERSONNEL. [210.8(A)(8)] | | | | | | LOAD CALCULATION REQUIRED PER NEC | | | | | | E3602.1AMPACITY OF UNGROUNDED CONDUCTORS. | | | UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF | | | NOT LESS THAN THE LOAD SERVED. FOR ONE-FAMILY | | | DWELLINGS, THE AMPACITY OF THE UNGROUNDED CONDUCTORS | | | SHALL BE NOT LESS THAN 100 AMPERES, 3 WIRE. FOR ALL | | | OTHER INSTALLATIONS, THE AMPACITY OF THE UNGROUNDED | | | CONDUCTORS SHALL BE NOT LESS THAN 60 AMPERES. | | | [230.42(B), 230.79(C) & (D)] | | | | | | RISER DIAGRAM REQUIRED | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2018-03-27 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2018-03-27 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2018-03-27 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2018-03-27 13:38:09 | PERMIT # 18030836 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED WITH COMMENTS: | | | | | | 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF | | | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS. | | | | | | 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2018-04-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-09 |
Time |
08:03 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-09 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2018-04-09 08:05:27 | APPROVED UNDER MASTER # 15111120 | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-21 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-13 |
Time |
13:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2018-04-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2018-03-23 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2018-03-27 |
|
|
Cont ID |
|
| Sent By |
aclange |
Date |
2018-03-27 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
aclange |
Date |
2018-03-27 |
Time |
12:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2018-08-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2018-08-28 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2018-08-28 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2018-08-28 14:50:00 | PASS PROVISO | | | | | | PERMIT #18030836 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW | | | O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD | | | PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY | | | CONTROLLED. | | | | | | 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE | | | MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A | | | FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY | | | CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED | | | DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF | | | COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE | | | CLARIFY. | | | | | | 3) M-101.00: IN REGARD TO NOTE #5 WE REQUIRE THAT THE | | | ENGINEER OF RECORD CONDUCT THE INSPECTIONS OF THE | | | INTUMESCENT PAINT APPLICATION ON THE AC CLOSET DOORS | | | | | | 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET | | | APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE | | | DETECTOR IS REQUIRED IN ALL THREE CLOSETS IN COMPLIANCE | | | WITH SECTION 606.2.2 FBC-10 MECH. | | | | | | 5) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES | | | INDICATE THE APPLIANCE HAS BEEN TESTED TO THE | | | APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1 | | | FBC-10 FUEL GAS AT ROUGH INSPECTION. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-08-21 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-08-21 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2018-08-21 14:36:25 | 1ST REVIEW FBC-2010 MECHANICAL, ENERGY CONSERVATION | | | CODE | | | PERMIT #18030836 | | | 8/21/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW | | | O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD | | | PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY | | | CONTROLLED. | | | | | | 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE | | | MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A | | | FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY | | | CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED | | | DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF | | | COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE | | | CLARIFY. | | | | | | 3) M-101.00: IN REGARD TO NOTE #5, THE CITY OF WEST | | | PALM BEACH REQUIRES THAT THE ENGINEER OF RECORD CONDUCT | | | THE INSPECTIONS OF THE INTUMESCENT PAINT APPLICATION ON | | | THE AC CLOSET DOORS, AND PROVIDE THE DEPARTMENT WITH A | | | SIGNED SEALED LETTER CERTIFYING THE APPLICATION | | | PROCEDURE WAS COMPLETED ACCORDING TO THE MANUFACTURER'S | | | SPECIFICATIONS. PLEASE PLACE A NOTE ON THE PLAN TO THAT | | | EFFECT- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC. | | | | | | 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET | | | APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE | | | DETECTOR IS REQUIRED IN THE CLOSET IN COMPLIANCE WITH | | | SECTION 606.2.2 FBC-10 MECH. | | | | | | 5) M-102.00: PLEASE LABEL THE SUBDUCT DETAILS AS EITHER | | | DRYER, TOILET, OR KITCHEN EXHAUST. | | | | | | 6) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES | | | INDICATE THE APPLIANCE HAS BEEN TESTED TO THE | | | APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1 | | | FBC-10 FUEL GAS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2018-04-09 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2018-04-09 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2018-04-09 |
Time |
14:58 |
Sent To |
|
|
| Notes |
| 2018-04-09 15:46:17 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18030836 | | | 4/9/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-101.00: THE 30"X10" DUCT IS NOT PERMITTED TO | | | PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE- | | | SECTION 1023.5 FBC-17 BUILDING. | | | | | | 2) M-101.00: PROVIDE A INSTALLATION DETAIL FROM THE | | | FIRE/SMOKE DAMPER MANUFACTURER SHOWING HOW THE DAMPERS | | | ARE TO BE INSTALLED IN THE DUCT RUNS AS SHOWN IN THE | | | APARTMENT CORE. | | | | | | 3) M-101.00: EXHAUST SYSTEMS ARE REQUIRED IN THE MASTER | | | BATHS- TABLE 403.1.1. | | | | | | 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY | | | CONSERVATION. | | | | | | 5) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5 | | | | | | 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE | | | HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY | | | CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY | | | CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE | | | HEAT PUMPS. | | | | | | 7) M1.01.00 SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY | | | TRUNKS OF HP-G- SECTION 606.2.1. | | | | | | 8) M1.01.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED | | | FOR THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2 | | | FBC-17 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY | | | CONSERVATION. | | | | | | 9) M1.01.00: PROVIDE A SECTION CUT OF THE COVE RETURNS | | | THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT | | | CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2 | | | | | | 10) M.101.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE | | | A DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT | | | INTO THE SHAFT. | | | | | | 11) M1.01.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR | | | THE DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION | | | OF THE EXHAUST DUCT INTO THE SHAFT. | | | | | | 12) M-102.00: PLEASE INDICATE WHICH OF THE SUBDUCT | | | DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET | | | EXHAUST, AND THE RANGE EXHAUST. | | | | | | 13) M-102.03: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR | | | THE DUCT WRAP WITH SHOP DRAWING APPROVAL STAMP BY THE | | | EOR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-08-21 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-08-21 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2018-04-09 |
|
|
Cont ID |
|
| Sent By |
gjohnson |
Date |
2018-04-09 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
gjohnson |
Date |
2018-04-07 |
Time |
14:36 |
Sent To |
|
|
| Notes |
| 2018-04-07 16:06:37 | 1ST REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SHT. A601 SHOWER PAN DETAIL THE WATER PROF MEMBRANE | | | SHALL PITCH TO THE DRAIN THE MEMBRANE SHOWN ON THE | | | CONCRETE SLAB DOES NOT APPEAR TO COMPLY WITH FBC PL | | | 417.5.2 | | | | | | 2. PLEASE SPECIFY ON PLAN THE MANUFACTURE OF THE WATER | | | PROF MEMBRANE AND PROVIDE SPECIFICATIONS AND | | | INSTALLATION GUIDE. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. PLEASE PROVIDE ELEVATION DETAILS FOR GRAB BAR | | | BACKING AND THE VANITY'S IN HER BATHROOM AS IT IS | | | DESIGNATED A SPEC B BATHROOM FOR THE FHA REQUIREMENTS. | | | PER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENTS #6 AND | | | #7 | | | | | | 4. THE TUB IS MISSING ON THE SANITARY ISOMETRIC IN HER | | | MASTER BATHROOM. PER WPB AMEND TO FBC 107.2.1 | | | | | | 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND INSTALL | | | MANUAL FOR THE STEAM GENERATOR. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2023-01-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2023-01-28 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2023-01-28 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2018-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-08-21 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-08-21 |
Time |
10:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2018-07-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2018-07-02 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2018-07-02 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2018-07-02 11:49:45 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN | | | ACCORDANCE WITH FS 471, FS 481 AS (F,M,E,P). NEW SHEETS | | | SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE REVIEW. | | | | | | 2. ARCHITECTURAL PAGES ARE NOT DIGITALLY SIGNED AND | | | SEALED, FS481. | | | | | 2018-04-09 16:32:22 | MECH SIGS GOOD | | 2018-03-27 12:32:25 | DIGITAL SIGNATURES NOT PROVIDE ON THE ARCHITECTURAL | | | PAGES. |
|
|
|