Plan Review Details - Permit 18030836
Plan Review Stops For Permit 18030836
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 10:10 Rev Time 0.00
Received By shill Date 2018-08-21 Time 10:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-07-02 Cont ID  
Sent By shill Date 2018-07-02 Time 11:35 Rev Time 0.00
Received By shill Date 2018-07-02 Time 11:34 Sent To  
Notes
2018-07-02 11:35:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. IT HAS COME TO MY ATTENTION THAT THE PLANS FOR THIS
 UNIT INCLUDE CHANGES TO WHAT WE CONSIDER "COMMON AREA".
 THIS CHANGE IS NOT CLOUDED, SO WAS NOT REVIEWED BY THE
 PREVIOUS REVIEWER.
  
 A LOCK HAS BEEN ADDED TO DOOR CN01. IT IS NOT CLEAR HOW
 EXITING FOR THE ADJACENT UNIT IS AFFECTED; THIS SHOULD
 BE A REVISION TO THE BASE BUILDING PLAN AND INCLUDE A
 REVISED LIFE SAFETY PLAN IF THIS WAS PREVIOUSLY SHOWN
 AS AN EXIT FOR THE ADJACENT UNIT.
  
 WHEN RESUBMITTING, ADDRESS THIS COMMENT AS WELL AS
 COMMENTS FROM PREVIOUS REVIEW. FOR YOUR CONVENIENCE,
 THEY ARE INCLUDED BELOW.
  
  
 ****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE.
  
 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS
 SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FLOOR SOUND UNDERLAYMENT
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
  
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
  
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO
 LOBBY FLOOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR
 WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE
 BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS
 AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR
 THIS ROOM.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM
 ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS
 PANELS WILL BE SUPPORTED ON ALL SIDES.
  
 FBC 2403.2 GLASS SUPPORTS.
 WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT
 FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD
 CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED
 SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE
 PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
  
 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED.
  
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
  
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
  
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-03-27 Cont ID  
Sent By aclange Date 2018-03-27 Time 12:41 Rev Time 0.00
Received By aclange Date 2018-03-27 Time 08:59 Sent To  
Notes
2018-03-27 11:30:15****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
  
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2017 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. PERMIT APPLICATIONS SUBMITTED AFTER 12/31/17 SHALL
 BE DESIGNED UNDER THE FLORIDA BUILDING CODE 2017 6TH
 EDITION INCLUDING MECHANICAL, PLUMBING, ENERGY
 CONSERVATION AND ACCESSIBILITY. CHANGE ALL CODE
 REFERENCES THROUGHOUT THE PLANS TO REFLECT THIS UPDATE.
  
 2. PROVIDE ELEVATIONS FOR KITCHEN AND BATHROOM COUNTERS
 SO THAT WE CAN CHECK FOR COMPLIANCE WITH FAIR HOUSING.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. FLOOR SOUND UNDERLAYMENT
  
 1) SUFFOLK CONSTRUCTION TO CONDUCT SITE TESTING FOR
 COMPLIANCE WITH THE 2010 FBC-B SECTIONS:
  
 FBC-B 2010 1207.2 AIR-BORNE SOUND.
 FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
  
 THE SOUND TESTS WILL BE CONDUCTED ON A 10 INCH CONCRETE
 SLAB UNDER THE MAIN PERMIT (15111020) AND SUBMITTED AS
 SOON AS RESULTS ARE PRINTED AND REVIEWED BY THE
 DESIGNER OF RECORD.
 NOTE: SITE TESTING FOR FLOOR INSULATION WILL REQUIRE
 THE APPLICANT TO REQUEST (IN WRITING) UNDER THE 2010 W.
 P. B. ADMINISTRATIVE CODE SECTION 104.11 ALTERNATE
 MATERIALS, DESIGN AND METHODS OF CONSTRUCTION FOR THE
 SOUND UNDERLAYMENT. THE LETTER SHOULD BE MADE OUT TO
 THE BUILDING OFFICIAL ROBERT BROWN.
  
 SHEET: FINISHES. UNIT:
  
 FLOOR FINISHES. BLDG TYPE: TYPE I/ TYPE II FLOOR
 INSULATION (FBC-B 2010)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 10 INCH CONCRETE FLOOR ASSEMBLY AS PER PLAN OR PROVIDE
 ONSITE TESTING TO THE LISTED BELOW ASTM STANDARDS:
  
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4. SHOW FLOOR TRANSITION DETAIL FROM CONDO FLOOR TO
 LOBBY FLOOR.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. IN THE STEAM ROOM WINDOWS ARE SHOWN ON THE EXTERIOR
 WALL OPENING INWARD. HAS THE EXTERIOR ENVELOPE OF THE
 BUILDING CHANGED. PLEASE PROVIDE A DETAIL FOR THIS
 AREA. THERE IS NOT A WINDOW SHOWN ON THE SCHEDULE FOR
 THIS ROOM.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE DETAILS FOR GLASS ENCLOSURES USED AT STEAM
 ROOM, SHOWERS AND TOILET ROOMS. SHOW IF THESE GLASS
 PANELS WILL BE SUPPORTED ON ALL SIDES.
  
 FBC 2403.2 GLASS SUPPORTS.
 WHERE ONE OR MORE SIDES OF ANY PANE OF GLASS ARE NOT
 FIRMLY SUPPORTED, OR ARE SUBJECTED TO UNUSUAL LOAD
 CONDITIONS, DETAILED CONSTRUCTION DOCUMENTS, DETAILED
 SHOP DRAWINGS AND ANALYSIS OR TEST DATA ENSURING SAFE
 PERFORMANCE FOR THE SPECIFIC INSTALLATION SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL.
  
 7. ARCHITECTURAL PAGES NOT DIGITALLY SIGNED.
  
 ARCHITECT DIGITAL SIGNING & SEALING PLANS. 61G1-16.005
 PROCEDURES FOR DIGITALLY SIGNING AND SEALING AND FOR
 ELECTRONICALLY TRANSMITTING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 (1) INFORMATION STORED IN ELECTRONIC FILES REPRESENTING
 PLANS, SPECIFICATIONS, PLATS, REPORTS, OR OTHER
 DOCUMENTS WHICH MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 481, F.S., SHALL BE SIGNED, DATED AND SEALED BY
 THE ARCHITECT OR INTERIOR DESIGNER IN RESPONSIBLE
 CHARGE.
 (A) A SCANNED IMAGE OF AN ORIGINAL SIGNATURE SHALL NOT
 BE USED IN LIEU OF A DIGITAL OR ELECTRONIC SIGNATURE.
 (B) THE DATE THAT THE ELECTRONIC SIGNATURE FILE WAS
 CREATED OR THE DIGITAL SIGNATURE WAS PLACED INTO THE
 DOCUMENT MUST APPEAR ON THE DOCUMENT IN THE SAME MANNER
 AS DATE IS REQUIRED TO BE APPLIED WHEN A LICENSEE USES
 THE MANUAL SEALING PROCEDURE SET OUT IN RULE
 61G1-16.003, F.A.C.
 (2) AN ARCHITECT OR INTERIOR DESIGNER UTILIZING A
 DIGITAL SIGNATURE TO SEAL CONSTRUCTION DOCUMENTS SHALL
 ASSURE THAT THE DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 ELECTRONIC SIGNATURE IS INVALIDATED IF ANY DATA IN THE
 DOCUMENT ARE CHANGED.
 (3) EACH ELECTRONICALLY SIGNED FILE SHALL HAVE AN
 AUTHENTICATION CODE DEFINED AS A MESSAGE DIGEST
 DESCRIBED IN FEDERAL INFORMATION PROCESSING STANDARD
 PUBLICATION 180-4 ?SECURE HASH STANDARD,? MARCH 2012,
 WHICH IS HEREBY ADOPTED AND INCORPORATED BY REFERENCE
 BY THE BOARD AND CAN BE OBTAINED FROM HTTP://WWW.FLRULE
 S.ORG/GATEWAY/REFERENCE.ASP?NO=REF-01340 OR THE
 INTERNET WEBSITE: HTTP://CSRC.NIST.GOV/PUBLICATIONS/FIP
 S/FIPS180-4/FIPS-180-4.PDF.
  
  
  
  
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By jpearson Date 2018-08-21 Time 11:08 Rev Time 0.00
Received By jpearson Date 2018-08-21 Time 11:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-04-06 Cont ID  
Sent By jleahy Date 2018-04-06 Time 17:25 Rev Time 0.00
Received By jleahy Date 2018-04-06 Time 15:17 Sent To  
Notes
2018-04-06 15:49:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-101.00
  
 AT THE END OF MOST LIGHTING CIRCUITS THERE IS ASYMBOL A
 TRIANGLE NOT SHON OF SYMBOL LIST. LIGHTING SYSTEM, IF
 SO NEED CUT SHEETS
  
 MASTER BDROM, STUDY, LIVING RM, DINING RM, FAMILY RM,
 BDRMS 2,3,4 OUTLET SPACING PER CODE E3901.1, E3901.2.2,
 FIXED PANELS
 E3901.2.2 WALL SPACE.
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING: [210.52(A)(2)]
  
 1.ANY SPACE THAT IS 2 FEET (610 MM) OR MORE IN WIDTH,
 INCLUDING SPACE MEASURED AROUND CORNERS, AND THAT IS
 UNBROKEN ALONG THE FLOOR LINE BY DOORWAYS AND SIMILAR
 OPENINGS, FIREPLACES, AND FIXED CABINETS.
  
 2.THE SPACE OCCUPIED BY FIXED PANELS IN EXTERIOR WALLS,
 EXCLUDING SLIDING PANELS.
  
 3.THE SPACE CREATED BY FIXED ROOM DIVIDERS SUCH AS
 RAILINGS AND FREESTANDING BAR-TYPE COUNTERS.
  
 UTILITY ROOM GFCI, AFCI PER 2014 NEC
 E3902.9 LAUNDRY AREAS.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 INSTALLED IN LAUNDRY AREAS SHALL HAVE GROUND-FAULT
 CIRCUIT INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(9)]
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS
  
 KITCHEN OUTLETS
 E3902.16 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS
  
 BATH OUTLETS FRO TV AND OTHER APPLIANCES
 E3902.7 SINK RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE
 EDGE OF A SINK SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP
 POSITION IN THE WORK SURFACES OR COUNTERTOPS.
 [210.8(A)(7)]
  
 E3902.8 BATHTUB OR SHOWER STALL RECEPTACLES.
 125-VOLT, SINGLE PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF THE OUTSIDE
 EDGE OF A BATHTUB OR SHOWER STALL SHALL HAVE
 GROUND-FAULT CIRCUIT INTERRUPTER PROTECTION FOR
 PERSONNEL. [210.8(A)(8)]
  
 LOAD CALCULATION REQUIRED PER NEC
  
 E3602.1AMPACITY OF UNGROUNDED CONDUCTORS.
 UNGROUNDED SERVICE CONDUCTORS SHALL HAVE AN AMPACITY OF
 NOT LESS THAN THE LOAD SERVED. FOR ONE-FAMILY
 DWELLINGS, THE AMPACITY OF THE UNGROUNDED CONDUCTORS
 SHALL BE NOT LESS THAN 100 AMPERES, 3 WIRE. FOR ALL
 OTHER INSTALLATIONS, THE AMPACITY OF THE UNGROUNDED
 CONDUCTORS SHALL BE NOT LESS THAN 60 AMPERES.
 [230.42(B), 230.79(C) & (D)]
  
 RISER DIAGRAM REQUIRED
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-03-27 Cont ID  
Sent By scaldero Date 2018-03-27 Time 13:38 Rev Time 0.00
Received By scaldero Date 2018-03-27 Time 13:27 Sent To  
Notes
2018-03-27 13:38:09PERMIT # 18030836
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 2) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 08:03 Rev Time 0.00
Received By gjohnson Date 2018-04-09 Time 08:03 Sent To  
Notes
2018-04-09 08:05:27APPROVED UNDER MASTER # 15111120
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 15:04 Rev Time 0.00
Received By shill Date 2018-08-13 Time 13:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-04-09 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-23 Time 08:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-03-27 Cont ID  
Sent By aclange Date 2018-03-27 Time 12:39 Rev Time 0.00
Received By aclange Date 2018-03-27 Time 12:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-08-28 Cont ID  
Sent By hmoser Date 2018-08-28 Time 14:50 Rev Time 0.00
Received By hmoser Date 2018-08-28 Time 14:11 Sent To  
Notes
2018-08-28 14:50:00PASS PROVISO
  
 PERMIT #18030836
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW
 O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD
 PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY
 CONTROLLED.
  
 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE
 MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A
 FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY
 CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED
 DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF
 COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE
 CLARIFY.
  
 3) M-101.00: IN REGARD TO NOTE #5 WE REQUIRE THAT THE
 ENGINEER OF RECORD CONDUCT THE INSPECTIONS OF THE
 INTUMESCENT PAINT APPLICATION ON THE AC CLOSET DOORS
  
 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET
 APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE
 DETECTOR IS REQUIRED IN ALL THREE CLOSETS IN COMPLIANCE
 WITH SECTION 606.2.2 FBC-10 MECH.
  
 5) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES
 INDICATE THE APPLIANCE HAS BEEN TESTED TO THE
 APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1
 FBC-10 FUEL GAS AT ROUGH INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-21 Cont ID  
Sent By ccole Date 2018-08-21 Time 14:34 Rev Time 0.00
Received By ccole Date 2018-08-21 Time 11:53 Sent To  
Notes
2018-08-21 14:36:251ST REVIEW FBC-2010 MECHANICAL, ENERGY CONSERVATION
 CODE
 PERMIT #18030836
 8/21/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101.00: THE PLAN DOES NOT CLEARLY SHOW HOW
 O/A IS BEING PROVIDED TO HP-G (IN CLOSET BY FOOD
 PANTRY), AND HP-B AND HOW THAT AIR IS AUTOMATICALLY
 CONTROLLED.
  
 2) SHEET A-101, A-501, & M-101.00: NOTE #5 ON THE
 MECHANICAL PLAN CALLS OUT INTUMESCENT PAINT ON A
 FIRE-RATED FLUSH DOOR AT THE HP-G CLOSET (CLOSET BY
 CORE CORRIDOR). IT IS NOT CLEAR WHY THIS FIRE-RATED
 DOOR WOULD NEED INTUMESCENT PAINT. IS THE DOOR MADE OF
 COMBUSTIBLE MATERIALS AND NOT PLENUM RATED? PLEASE
 CLARIFY.
  
 3) M-101.00: IN REGARD TO NOTE #5, THE CITY OF WEST
 PALM BEACH REQUIRES THAT THE ENGINEER OF RECORD CONDUCT
 THE INSPECTIONS OF THE INTUMESCENT PAINT APPLICATION ON
 THE AC CLOSET DOORS, AND PROVIDE THE DEPARTMENT WITH A
 SIGNED SEALED LETTER CERTIFYING THE APPLICATION
 PROCEDURE WAS COMPLETED ACCORDING TO THE MANUFACTURER'S
 SPECIFICATIONS. PLEASE PLACE A NOTE ON THE PLAN TO THAT
 EFFECT- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 4) M-101.00: DUE TO THE FACT THAT THE HP-B CLOSET
 APPEARS TO BE PART OF THE RETURN AIR PLENUM, A SMOKE
 DETECTOR IS REQUIRED IN THE CLOSET IN COMPLIANCE WITH
 SECTION 606.2.2 FBC-10 MECH.
  
 5) M-102.00: PLEASE LABEL THE SUBDUCT DETAILS AS EITHER
 DRYER, TOILET, OR KITCHEN EXHAUST.
  
 6) THE SUBMITTED CUT SHEET FOR THE WOLF COOKTOP DOES
 INDICATE THE APPLIANCE HAS BEEN TESTED TO THE
 APPROPRIATE ANSI STANDARD LISTED UNDER SECTION 623.1
 FBC-10 FUEL GAS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-09 Cont ID  
Sent By ccole Date 2018-04-09 Time 15:32 Rev Time 0.00
Received By ccole Date 2018-04-09 Time 14:58 Sent To  
Notes
2018-04-09 15:46:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18030836
 4/9/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-101.00: THE 30"X10" DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR STAIRWELL ENCLOSURE-
 SECTION 1023.5 FBC-17 BUILDING.
  
 2) M-101.00: PROVIDE A INSTALLATION DETAIL FROM THE
 FIRE/SMOKE DAMPER MANUFACTURER SHOWING HOW THE DAMPERS
 ARE TO BE INSTALLED IN THE DUCT RUNS AS SHOWN IN THE
 APARTMENT CORE.
  
 3) M-101.00: EXHAUST SYSTEMS ARE REQUIRED IN THE MASTER
 BATHS- TABLE 403.1.1.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 HEAT PUMPS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 5) PROVIDE AN ENERGY COMPLIANCE REPORT- SECTION C101.5
  
 6) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 SPACE IN ACCORDANCE WITH TABLE 403.1.1, AND INDICATE
 HOW THE OUTDOOR AIR FLOW WILL BE AUTOMATICALLY
 CONTROLLED- SEE SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION. CLARIFY HOW O/A IS BEING SUPPLIED TO THE
 HEAT PUMPS.
  
 7) M1.01.00 SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 TRUNKS OF HP-G- SECTION 606.2.1.
  
 8) M1.01.00 & A-4: NON-COMBUSTIBLE DOORS ARE REQUIRED
 FOR THE AC CLOSETS IN COMPLIANCE WITH SECTION 602.2
 FBC-17 MECHANICAL, AND C403.2.9.2 FBC-17 ENERGY
 CONSERVATION.
  
 9) M1.01.00: PROVIDE A SECTION CUT OF THE COVE RETURNS
 THAT SHOWS THE DIMENSIONS OF THE OPENING, AND WHAT
 CONSTRUCTION MATERIALS WILL BE USED- SECTION 602.2
  
 10) M.101.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE GAS RANGE, EXHAUST HOOD, AND EXHAUST DUCT. PROVIDE
 A DETAIL SHOWING THE CONNECTION OF THE EXHAUST DUCT
 INTO THE SHAFT.
  
 11) M1.01.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE DRYER, AND PROVIDE A DETAIL SHOWING THE CONNECTION
 OF THE EXHAUST DUCT INTO THE SHAFT.
  
 12) M-102.00: PLEASE INDICATE WHICH OF THE SUBDUCT
 DETAILS APPLIES TO THE DRYER EXHAUST, THE TOILET
 EXHAUST, AND THE RANGE EXHAUST.
  
 13) M-102.03: PROVIDE MANUFACTURER'S SPECIFICATIONS FOR
 THE DUCT WRAP WITH SHOP DRAWING APPROVAL STAMP BY THE
 EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By gjohnson Date 2018-08-21 Time 13:41 Rev Time 0.00
Received By gjohnson Date 2018-08-21 Time 13:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-04-09 Cont ID  
Sent By gjohnson Date 2018-04-09 Time 08:01 Rev Time 0.00
Received By gjohnson Date 2018-04-07 Time 14:36 Sent To  
Notes
2018-04-07 16:06:371ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A601 SHOWER PAN DETAIL THE WATER PROF MEMBRANE
 SHALL PITCH TO THE DRAIN THE MEMBRANE SHOWN ON THE
 CONCRETE SLAB DOES NOT APPEAR TO COMPLY WITH FBC PL
 417.5.2
  
 2. PLEASE SPECIFY ON PLAN THE MANUFACTURE OF THE WATER
 PROF MEMBRANE AND PROVIDE SPECIFICATIONS AND
 INSTALLATION GUIDE. PER WPB AMEND TO FBC 107.2.1
  
 3. PLEASE PROVIDE ELEVATION DETAILS FOR GRAB BAR
 BACKING AND THE VANITY'S IN HER BATHROOM AS IT IS
 DESIGNATED A SPEC B BATHROOM FOR THE FHA REQUIREMENTS.
 PER FAIR HOUSING ACT DESIGN MANUAL REQUIREMENTS #6 AND
 #7
  
 4. THE TUB IS MISSING ON THE SANITARY ISOMETRIC IN HER
 MASTER BATHROOM. PER WPB AMEND TO FBC 107.2.1
  
 5. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND INSTALL
 MANUAL FOR THE STEAM GENERATOR. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2023-01-28 Cont ID  
Sent By shill Date 2023-01-28 Time 14:16 Rev Time 0.00
Received By shill Date 2023-01-28 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By shill Date 2018-08-21 Time 10:10 Rev Time 0.00
Received By shill Date 2018-08-21 Time 10:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-07-02 Cont ID  
Sent By shill Date 2018-07-02 Time 11:48 Rev Time 0.00
Received By shill Date 2018-07-02 Time 11:48 Sent To  
Notes
2018-07-02 11:49:45SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DIGITAL SIGNATURES/SEALS (PLAN PAGES) ARE IN
 ACCORDANCE WITH FS 471, FS 481 AS (F,M,E,P). NEW SHEETS
 SUBMITTED IN THE NEXT REVIEW CYCLE REQUIRE REVIEW.
  
 2. ARCHITECTURAL PAGES ARE NOT DIGITALLY SIGNED AND
 SEALED, FS481.
  
2018-04-09 16:32:22MECH SIGS GOOD
2018-03-27 12:32:25DIGITAL SIGNATURES NOT PROVIDE ON THE ARCHITECTURAL
 PAGES.