Plan Review Details - Permit 18030801
Plan Review Stops For Permit 18030801
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-02-13 Cont ID  
Sent By tklarge Date 2019-02-13 Time 10:20 Rev Time 0.00
Received By tklarge Date 2019-02-13 Time 10:20 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2019-02-11 Cont ID  
Sent By tklarge Date 2019-02-11 Time 06:08 Rev Time 0.00
Received By tklarge Date 2019-02-11 Time 05:04 Sent To  
Notes
2019-02-11 05:31:091) A REVISED ORIGINAL PERMIT APPLICATION FOR THE GAS
 INSTALLATION MUST BE SUBMITTED. THE GAS PLAN SHOWS A
 FUTURE GENERATOR AND A POOL HEATER BUT THESE APPLIANCES
 ARE NOT LISTED ON THE GAS APPLICATION. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) THERE ARE TWO DIFFERENT GAS DRAWINGS IN THE PERMIT
 SUBMITTAL PACKAGE. REMOVE ALL OLD DOCUMENTS FROM THE
 SUBMITTAL PACKAGE AND SUBMIT TWO COMPLETE SETS OF PLANS
 SHOWING THE ENTIRE SCOPE OF WORK. WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) IDENTIFY THE MODEL OF GENERATOR TO BE INSTALLED ON
 THE MANUFACTURER'S SPECIFICATION SHEET. IS IT THE 9 OR
 11 KW? SHOW THE LOCATION OF THE GENERATOR ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 FIREPLACE. ONLY THE SPECIFICATIONS FOR THE SHUTOFF
 VALVE HAVE BEEN SUBMITTED. EQUIPMENT SHALL BE LISTED
 AND LABELED. 2017 FBC-RES. SEC. G2404.3.THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
 5) SUBMIT ADDITIONAL INFORMATION FOR THE GAS DRYER.
 WHAT HAS BEEN SUBMITTED INTERNET CONSUMER INFORMATION
 AND NOT MANUFACTURER'S SPECIFICATIONS. EQUIPMENT SHALL
 BE LISTED AND LABELED. 2017 FBC-RES. SEC. G2404.3. THE
 SPEC SHEETS SHALL SHOW THE BTU LOAD OF THE APPLIANCE.
 6) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. G2407.1, G2439.4,
 G2406.2, G2407.5.
 7) ) THE GAS PLAN SHOWS 3 DIFFERENT TYPES OF PIPING
 MATERIAL TO BE INSTALLED YET YOU REEFERENCE ONLY ONE
 GAS SIZING TABLE WHICH IS FOR PE PIPE. SUBMIT TWO
 COPIES OF THE APPLICABLE SIZING TABLES USED TO SIZE THE
 GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE 2017 FBC-FUEL GAS SECS. 401.4,
 401.8, 402.3, AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2017 FBC-RES. SEC. G2413.3, G2412.8, G2413.1, G2413.2,
 & G2413.3.
 8) THE GAS SIZING TABLE REFERENCED ON THE PLAN IS FOR A
 SYSTEM LESS THAN 2 PSI YET THE GAS DRAWING SHOWS A 2
 PSI SYSTEM. CLARIFY.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC
 SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 10) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 11) SHOW THE CORRESPONDING EHD OF THE CSST THAT IS
 BEING USED AND IDENTIFY THE SIZING TABLE FROM THE GAS
 CODE USED TO SIZE THE PIPING. WPB AMEND. TO FBC SEC.
 107.2.1.
 12) IDENTIFY ALL THE APPLIANCES ON THE GAS RISER AND
 SHOW THE LOCATION OF ALL GAS APPLIANCES AND EQUIPMENT
 ON SHEETS A-00 & A-01. WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. A-00 SHOWS 2 SEPARATE GAS BRANCH LINES PIPED
 TO THE EAST SIDE OF THE STRUCTURE. IDENTIFY THE
 APPLIANCE/EQUIPMENT THAT WILL BE CONNECTED TO THESE
 LINES. WPB AMEND. TO FBC SEC. 107.2.1.
 14) SHOW THE GAS SHUTOFF VALVES ON THE GAS RISER FOR
 THE APPLIANCES. 2017 FBC-RES. SEC. G2420.1.
 15) SHOW THE DISTANCE FROM OUTLET OF THE GAS REGULATORS
 TO THE APPLIANCES.WPB AMEND. TO FBC SEC. 107.2.1.
  
 **NOTE: I SUGGEST CONTACTING THIS PLAN REVIEWER TO SET
 AN APPOINTMENT TO GO OVEERR THESE COMMENTS BEFORE
 RESUBMITTING CORRECTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By tklarge Date 2018-03-23 Time 12:07 Rev Time 0.00
Received By tklarge Date 2018-03-23 Time 10:15 Sent To I
Notes
2018-03-23 11:44:221) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
 2) SHOW THE LOCATION OF ALL OPERABLE DOORS AND WINDOWS
 IN RELATION TO THE LOCATION OF THE TANKLESS WATER
 HEATER. THE TANKLESS WATER HEATER SHALL BE A MINIMUM OF
 4 FEET FROM ANY OPERABLE DOOR OR WINDOW PER THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 DESCRIPTION OF WORK ON THE APPLICATION NOTES THAT THE
 TANKLESS WATER HEATER IS BEING MOVED. THE SUBMITTED
 PLAN IS UNCLEAR AS TO THE EXISTING LOCATION AND THE NEW
 LOCATION. CLARIFY.
 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. 2017 FBC-FUEL GAS SEC. G2407.1, G2439.4,
 G2406.2, G2407.5.
 4) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2. THIS APPLIES TO THE LOW
 PRESSURE GAS PIPING FROM 2 PSI TO 1/2 LB REGULATOR FOR
 THE DRYER, STOVE AND FIREPLACE.
 7) THE PLAN NOTES "S.S GAS PIPING IN SLEEVE UNDER
 FLOOR". I ASSUME THIS IS CSST MATERIAL. SUBMIT THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING AND TWO COPIES OF THE APPLICABLE SIZING
 TABLE FOR THIS PORTION OF THE SYSTEM.2017 FBC-
 RESIDENTIAL SEC.G2413.3. SHOW THE TYPE OF SLEEVE
 MATERIAL AND SIZE.
 8) INDICATE THE TYPE OF PIPING ON THE EXISTING
 SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 9) IS THE FLOOR A WOOD FLOOR AND THE PIPING BEING
 INSTALLED IN A CRAWL SPACE? IS IT BEING INSTALLED
 UNDERGROUND? THE SLEEVE SHALL BE VENTED IN ACCORDANCE
 WITH 2017 FBC-RES. SEC.2415.14. CLARIFY AND PROVIDE
 ADDITTIONAL INFORMATION.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SUBMIT TWO COPIES OF A FLOOR PLAN SHOWING THE
 LOCATION OF THE GAS APPLIANCES. THE FLOOR PLAN CAN BE
 HAND DRAWN.WPB AMEND. TO FBC SEC. 107.2.1.
 11) SIZE ALL SECTIONS OF PIPING DOWNSTREAM OF THE
 REGULATOR AT THE TANKLESS WATER HEATER INCLUDING ALL
 SECTIONS BETWEEN THE TEES FOR EACH BRANCH TO DRYER,
 STOVE AND FIREPLACE.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-13 Cont ID  
Sent By tklarge Date 2019-02-13 Time 10:20 Rev Time 0.00
Received By tklarge Date 2019-02-13 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-11 Cont ID  
Sent By tklarge Date 2019-02-11 Time 06:08 Rev Time 0.00
Received By tklarge Date 2019-02-06 Time 14:05 Sent To  
Notes
2019-02-07 14:07:02RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By tklarge Date 2018-03-23 Time 12:07 Rev Time 0.00
Received By tklarge Date 2018-03-20 Time 14:26 Sent To  
Notes
2018-03-21 14:26:19PLUMB<5K