Plan Review Details - Permit 18030770
Plan Review Stops For Permit 18030770
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-07 Cont ID  
Sent By dbattles Date 2019-02-07 Time 08:30 Rev Time 0.00
Received By dbattles Date 2019-02-07 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 11:22 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 11:22 Sent To  
Notes
2018-11-01 11:21:57PROVISOS:
  
 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS.
  
 F) SLIDING WINDOWS AS SHOWN ON PLANS.
  
 G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 H) FRENCH DOORS AS SHOWN ON PLANS.
  
 I) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 K) METAL ROOF. SUBMIT ROOFING PRODUCT APPROVALS WITH
 SUB PERMIT
  
 L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL. COORDINATE WITH ITEM #15
 ABOVE.
  
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-08-23 Cont ID  
Sent By dbattles Date 2018-08-23 Time 13:38 Rev Time 0.00
Received By dbattles Date 2018-08-23 Time 13:38 Sent To  
Notes
2018-08-23 13:40:34****CORRECTIONS****
 W.P.B. PERMIT: 18030770
 2ND REVIEW: AUGUST 23, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- OK
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
 3-2-[FBC R807]THIS IS FIRE DEPARTMENT ACCESS AND IS
 REQUIRED.
  
 4- PLANS NEED TO SPECIFY THE ATTIC LIVE LOADS AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: KEEP IN
 CONSIDERATION FOOTNOTE "G".
 4-2-ATTIC WILL BE ACCESSIBLE AND WILL NEED TO BE ABLE
 TO CARRY LIVE LOAD. PLEASE UPDATE WALL TYPES ON A-3 TO
 SHOW THAT THEY WILL BEAR THE FRAMED CEILING AND LIVE
 LOAD. ALSO, THE CEILNG FRAMING MEMBERS WILL NEED TO
 SUPPORT LIVE LOAD SPECIFIED. PLEASE SHOW WHAT GAUGE
 STEEL STUD TO SUPPORT LIVE LOAD.
  
  
 5- OK
  
 6- OK
  
 7- OK
  
 8- OK
  
 9- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 SEC. R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 9-2-DRAINAGE PLAN TO SHOW ELEVATIONS THAT KEEP DRAINAGE
 ON PROPERTY. ALSO, PLEASE PROVIDE 2 COPIES OF SURVEY.
 YOU CAN USE THE SURVEY AS BASIS FOR DRAINAGE PLAN.
  
 10- OK
  
 11- FLAT ROOF AREA ABOVE BEDROOM #1: SPECIFY SIZE OF
 CONCRETE SCUPPER AND PROVIDE COMPLETE INFORMATION
 (LOCATION AND SIZE) OF OVERFLOW DRAIN/SCUPPERS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
  
 11-2-I SEE A SCUPPER IN PLAN VIEW, BUT NO NOTES ABOUT
 IT. PLEASE PROVIDE DRAINAGE CALCULATIONS FOR FLAT ROOF
 AND INCLUDE THE WATER BEING CONTRIBUTED BY 6:12 ROOF
 AROUND IT. REFER TO [FBC R903.4]FOR SCUPPERS AND
 OVERFLOW DRAINS.
  
 12- OK
  
 13- PROVIDE DETAILS AND SPECIFICATIONS FOR DOORS AND
 WINDOWS STRUCTURAL BUCK DETAILS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 13-2-NOT PROVIDED. THESE ARE TYPICAL OPENING DETAILS
 THAT WOULD SHOW BUCK ATTACHMENT TO OPENINGS.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE 42" HIGH WALL SHOWN ON PLANS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 14-2-THIS IS THE WALL ON PATIO. PROVIDE DETAIL AS
 PREVIOUSLY REQUESTED.
  
 15- PROVIDE DETAILS AND SPECIFICATIONS FOR THE ROOF
 BATTENS THAT ARE GOING TO SUPPORT THE PROPOSED METAL
 ROOFING SYSTEM. COORDINATE WITH METAL ROOFING PRODUCT
 APPROVAL. SEC. R301.1 FBC-RESIDENTIAL.
  
 15-2-PROVIDE ROOFING SUBMITTAL, OR INDICATE THAT IT
 WILL BE DEFERRED UNTIL ROOFING SUB PERMIT.
  
 16- OK
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS.
  
 F) SLIDING WINDOWS AS SHOWN ON PLANS.
  
 G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 H) FRENCH DOORS AS SHOWN ON PLANS.
  
 I) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE.
  
 L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL. COORDINATE WITH ITEM #15
 ABOVE.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 18-2-PROVIDE PRODUCT APPROVALS, OR INDICATE THAT THEY
 WILL BE DEFERRED.
  
 [FBC AMENDED 107.3.4.1]DEFERRAL OF ANY SUBMITTAL ITEMS
 SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL FOR
 REVIEW, AND THEN FORWARED TO THE BUILDING OFFICIAL
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN. THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE
 INSTALLED UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN APPROVED BY THE BUILDING OFFICIAL.
 19- OK
  
 20- IMPORTANT: CONTRACTOR TO COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) FOR INSPECTIONS OF SPECIAL
 CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY
 AMENDMENTS TO AVOID CONFLICTS/DELAYS.
 KEN CONRAD (561)805-6666 OR E-MAIL [email protected]
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-02 Time 19:02 Rev Time 0.00
Received By jgomez Date 2018-04-02 Time 14:45 Sent To  
Notes
2018-04-02 15:09:43NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 2- ENTRY DOOR DOESN'T COMPLY WITH EGRESS. REVISE AS
 REQUIRED. SEC. R311.2 FBC-RESIDENTIAL.
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 4- PLANS NEED TO SPECIFY THE ATTIC LIVE LOADS AS
 REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL. NOTE: KEEP IN
 CONSIDERATION FOOTNOTE "G".
  
 5- PROVIDE COMPLETE FRAMING PLAN, DETAILS AND
 SPECIFICATIONS FOR ATTIC FLOOR. SEC R301.1
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM #4 ABOVE
 AND MECHANICAL PLAN.
  
 6- PROVIDE COMPLETE DETAILS ANS SPECIFICATIONS FOR
 INTERIOR PARTITIONS FRAMING. SPECIFY ALL FRAMING
 MEMBERS AND SPACING. PROVIDE COMPLETE
 DETAIL/SPECIFICATIONS FOR FRAMING AROUND DOOR OPENING.
 PROVIDE SPECIFICATIONS FOR WALLS IN WET AREAS. , ETC.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 7- CONCRETE STRENGTH SPECIFIED ON SHEET S-1 AND S-2 IS
 NOT CLEAR. CONCRETE STRENGTH SPECIFIED AT THE BOTTOM
 LEFT BY THE STRUCTURAL DESIGN LOADS IS 4,000 PSI WHILE
 CONCRETE STRENGTH SPECIFIED AT THE BOTTOM RIGHT BY THE
 ENGINEER'S STATEMENT IS 3,000PSI. REVISE AS REQUIRED TO
 MATCH AND COORDINATE WITH STRUCTURAL CALCULATIONS
 SUBMITTED ALSO. SEC. 107.2.1 CITY AMENDMENTS.
  
 8- STRUCTURAL CALCULATIONS NEED TO BE REVISED. THE
 CURRENT CODE IS THE FBC 6TH EDITION (2017) NOT THE FBC
 5TH EDITION (2014). CHAPTER 553 FLORIDA STATUTE. UPDATE
 AS REQUIRED.
  
 9- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 FBC-RESIDENTIAL.
 SEC. R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS
 SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 MM).
  
 10- NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320 FBC-RESIDENTIAL.
  
 11- FLAT ROOF AREA ABOVE BEDROOM #1: SPECIFY SIZE OF
 CONCRETE SCUPPER AND PROVIDE COMPLETE INFORMATION
 (LOCATION AND SIZE) OF OVERFLOW DRAIN/SCUPPERS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
  
 12- PROVIDE EVALUATION REPORT FOR THE WALL AND CEILING
 INSULATION SHOWING THE R-VALUES SPECIFIED ON PLANS.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R316
 FBC-RESIDENTIAL.
  
 13- PROVIDE DETAILS AND SPECIFICATIONS FOR DOORS AND
 WINDOWS STRUCTURAL BUCK DETAILS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 14- PROVIDE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE 42" HIGH WALL SHOWN ON PLANS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 15- PROVIDE DETAILS AND SPECIFICATIONS FOR THE ROOF
 BATTENS THAT ARE GOING TO SUPPORT THE PROPOSED METAL
 ROOFING SYSTEM. COORDINATE WITH METAL ROOFING PRODUCT
 APPROVAL. SEC. R301.1 FBC-RESIDENTIAL.
  
 16- ENERGY CALCULATIONS FORM R405-2017 SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. THE ADDRESS IS INCORRECT. NEED THE OWNER'S AND
 BUILDER'S INFORMATION. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 B) WALL INFORMATION ON ITEM #9 DOESN'T MATCH PLANS.
 REVISE TYPE OF CONSTRUCTION AND INSULATION R VALUE TO
 MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) CEILING INFORMATION ON ITEM #10 DOESN'T MATCH PLANS.
 REVISE INSULATION R VALUE TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ENGINEER SIGNING AND SEALING THE CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER 471 F.S.
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 E) CLARIFY WHY THE R-VALUE SHOWN ON PAGE 2 OF 4 DOESN'T
 MATCH THE R-VALUE SHOWN ON ITEM #10 ON PAGE 1 OF 4.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-RESIDENTIAL.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 17- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) ENTRY DOORS WITH TRANSOM ABOVE AS SHOWN ON PLANS.
  
 B) SLIDING GLASS DOORS WITH TRANSOM ABOVE AS SHOWN ON
 PLANS.
  
 C) SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 D) CASEMENT WINDOWS AS SHOWN ON PLANS.
  
 E) FIXED WINDOWS AS SHOWN ON PLANS.
  
 F) SLIDING WINDOWS AS SHOWN ON PLANS.
  
 G) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY MARK
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE CALCULATED
 DESIGN PRESSURES.
  
 H) FRENCH DOORS AS SHOWN ON PLANS.
  
 I) SLIDING GLASS DOORS AS SHOWN ON PLANS.
  
 J) HURRICANE SHUTTERS IF ABOVE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
  
 K) METAL ROOF. NOTE: COORDINATE WITH ITEM #15 ABOVE.
  
 L) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL.
  
 18- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $166,424 AS REQUIRED BY
 SEC. 109.3 CITY AMENDMENTS. THE PERMIT FEE BALANCE IS
 $3412.65.
  
 SEC. 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 20- IMPORTANT: CONTRACTOR TO COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) FOR INSPECTIONS OF SPECIAL
 CONSTRUCTION AS REQUIRED BY SEC. 110.3.9 CITY
 AMENDMENTS TO AVOID CONFLICTS/DELAYS.
 KEN CONRAD (561)805-6666 OR E-MAIL [email protected]
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-10-03 Cont ID  
Sent By jpearson Date 2018-10-03 Time 10:17 Rev Time 0.00
Received By jpearson Date 2018-10-03 Time 09:38 Sent To  
Notes
2018-10-03 10:17:45NO CHANGES TO PREVIOUSLY APPROVED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-08-06 Cont ID  
Sent By ppetty Date 2018-08-06 Time 14:42 Rev Time 0.00
Received By ppetty Date 2018-08-06 Time 14:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-04-03 Cont ID  
Sent By jpearson Date 2018-04-03 Time 09:03 Rev Time 0.00
Received By jpearson Date 2018-04-03 Time 06:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2019-02-05 Cont ID  
Sent By fmittner Date 2019-02-05 Time 09:32 Rev Time 0.00
Received By fmittner Date 2019-02-05 Time 09:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2018-11-29 Cont ID  
Sent By fmittner Date 2018-11-29 Time 14:14 Rev Time 0.00
Received By fmittner Date 2018-11-29 Time 14:14 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By destabro Date 2018-08-21 Time 09:53 Rev Time 0.00
Received By destabro Date 2018-08-21 Time 09:53 Sent To Z
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-03-29 Cont ID  
Sent By destabro Date 2018-03-29 Time 08:38 Rev Time 0.00
Received By destabro Date 2018-03-29 Time 08:38 Sent To Z
Notes
2018-03-29 08:40:383/28/2018 - HPB CASE NO. 17-78, RECEIVED HPB APPROVAL
 FOR INFILL CONSTRUCTION IN DECEMBER OF 2017. APPLICANT
 HAS MET THE FOLLOWING CONDITIONS OF APPROVAL:
 1.) REVISE FRONT SETBACK TO FALL BETWEEN THE RANGE OF
 16? TO 25?.
 2.) ADJUST THE MASSING ON THE REAR OF THE STRUCTURE TO
 COMPLEMENT THE FRONT FA?ADE. THE BOXY PROJECTIONS AT
 THE SIDE ELEVATIONS SHOULD BE CAPPED WITH A HIP OR
 GABLE ROOF FOR ARCHITECTURALLY CONTINUITY.
 3.) APPLICANT SHALL USE SMOOTH STUCCO CLADDING FOR ALL
 PROPOSED MODELS. IF HARDIBOARD IS TO BE USED, IT SHALL
 COVER THE ENTIRE BUILDING ENVELOPE AND BE SMOOTH IN
 TEXTURE.
 4.) ROOFING MATERIAL SHALL BE CONSISTENT. APPLICANT
 SHOWS A STANDING SEAM METAL TYPE OF ROOFING ON THE
 RENDERINGS, BUT DESCRIBES ELASTOMERIC PAINT BEING
 APPLIED TO THE CONCRETE SURFACE IN THE PLANS.
 5.) ALL WINDOWS SHOULD BE CLEAR GLASS, NOT TINTED, PER
 THE DESIGN GUIDELINES OF THE HISTORIC DISTRICT. ON THE
 RIGHT AND LEFT ELEVATIONS, A WIDER 6/1-LIGHT WINDOW IS
 PRESENT AND SHOULD BE RECONFIGURED TO CREATE A PAIRED
 4/1-LIGHT WINDOWS FOR CONTINUITY OF DESIGN. THE FIXED
 GLASS WINDOW ON THE FRONT ELEVATION FOR THE BATHROOM
 SPACE SHOULD BE ADJUSTED TO A 4/1-LIGHT.
 DLE
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-07 Cont ID  
Sent By dbattles Date 2019-02-07 Time 08:30 Rev Time 0.00
Received By dbattles Date 2019-02-01 Time 15:47 Sent To  
Notes
2019-02-05 15:41:03ROUTED FROM ZONING TO PERMIT LIBRARIAN 2/5/2019 EL
2019-02-01 15:47:47RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-29 Cont ID  
Sent By dbattles Date 2018-11-29 Time 15:29 Rev Time 0.00
Received By dbattles Date 2018-09-27 Time 11:49 Sent To  
Notes
2018-11-08 12:16:19ROUTED FROM ZONING TO LM 11/8/18
 FAILED THROUGH ZONING WITH NEW COMMENTS
2018-11-01 14:33:09REMOVED BIN # AND PUT IN ZONING BOX
2018-10-03 13:49:01R17
2018-10-01 11:50:03LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-08-27 Cont ID  
Sent By jgomez Date 2018-08-27 Time 12:04 Rev Time 0.00
Received By jgomez Date 2018-07-27 Time 13:52 Sent To I
Notes
2018-07-30 13:52:46R14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-04 Time 16:20 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 13:54 Sent To I
Notes
2018-03-20 13:54:22R11

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-02-01 Cont ID  
Sent By dbattles Date 2019-02-01 Time 08:54 Rev Time 0.00
Received By dbattles Date 2019-02-01 Time 08:54 Sent To  
Notes
2019-02-01 09:03:38MU 2018-32319
 SEE E-MAIL FROM WILLIE SWOOPE IN PERMIT DOCUMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 11:23 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 11:23 Sent To  
Notes
2018-11-01 11:24:01[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-04-02 Cont ID  
Sent By jgomez Date 2018-04-02 Time 15:10 Rev Time 0.00
Received By jgomez Date 2018-04-02 Time 15:09 Sent To  
Notes
2018-04-02 15:11:54BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-29 Cont ID  
Sent By cmontell Date 2018-10-29 Time 14:40 Rev Time 0.00
Received By cmontell Date 2018-10-29 Time 14:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-08-27 Cont ID  
Sent By jgomez Date 2018-08-27 Time 12:02 Rev Time 0.00
Received By jgomez Date 2018-08-27 Time 11:54 Sent To  
Notes
2018-08-27 12:03:02NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017).
  
 ORIGINAL COMMENT:
 1- THE TRANSFER DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN AIR
 SEC. M1602.3. NEED TO INCLUDE ALL THE SUPPLY AIR
 ENTERING THE MASTER SUITE.
  
 M1602.3 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 (1).TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (2).TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-WALL TRANSFER GRILLES AND USING AN UNRESTRICTED
 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (3).HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 RESPONSE:
 SIZE OF DUCT WAS REVISED TO 14". ACCORDING TO EXCEPTION
 #3 OF SEC. M1602.3 FBC-RESIDENTIAL NEED AT LEAST 15"
 DUCT. REVISE AS REQUIRED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-04 Time 15:38 Rev Time 0.00
Received By jgomez Date 2018-04-04 Time 15:38 Sent To  
Notes
2018-04-04 15:38:30NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017).
  
 1- REVISE MECHANICAL FLOOR PLAN. THE RETURN AIR CAN NOT
 BE LESS THAN 10 FEET FROM THE KITCHEN RANGE. REVISE AS
 REQUIRED. SEC. M1602.2 FBC-RESIDENTIAL.
  
 2- THE TRANSFER DUCT SIZE SPECIFIED FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH THE BALANCED RETURN AIR
 SEC. M1602.3. NEED TO INCLUDE ALL THE SUPPLY AIR
 ENTERING THE MASTER SUITE.
  
 M1602.3 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 (1).TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (2).TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-WALL TRANSFER GRILLES AND USING AN UNRESTRICTED
 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 (3).HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
  
  
 3- IT LOOKS LIKE THE EQUIPMENT SIZING CALCULATIONS WERE
 DONE BASED ON THE INFORMATION USED IN THE ENERGY
 CALCULATIONS DONE BY THE SAME ENGINEER. ENERGY
 CALCULATIONS NEED TO BE REVISED. SEE COMMENTS IN THE
 BUILDING REVIEW REGARDING THE ENERGY CALCULATIONS.
 REVISE THE EQUIPMENT SIZING CALCULATIONS REFLECTING THE
 CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ADDRESS SPECIFIED IN THE EQUIPMENT SIZING
 CALCULATIONS IS INCORRECT. REVISE AS REQUIRED TO MATCH
 ACTUAL LOCATION OF HOUSE. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ENGINEER SIGNING AND SEALING THE CALCULATIONS TO
 PROVIDE HIS INFORMATION AS REQUIRED BY CHAPTER 471 F.S.
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
 4- ENGINEER TO REVISE THE DUCT HANGING DETAILS TO MATCH
 ACTUAL CONSTRUCTION SHOWN ON PLANS. THIS IS NOT WOOD
 FRAMED CEILING. SEC. R301.1 FBC-RESIDENTIAL.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DON'T STAPLE OLD DRAWINGS TO PLANS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-10-17 Cont ID  
Sent By gjohnson Date 2018-10-17 Time 08:11 Rev Time 0.00
Received By gjohnson Date 2018-10-17 Time 08:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-08-22 Cont ID  
Sent By lcrespo Date 2018-08-22 Time 16:38 Rev Time 0.00
Received By lcrespo Date 2018-08-22 Time 16:38 Sent To  
Notes
2018-08-22 16:39:0708/22/2018 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE SECOND REQUEST, PLUMBING RISER DIAGRAM REQUIRED
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (11)
 RESIDENTIAL PLUMBING
 2. HOT WATER HEATER DISCHARGE ON P-1 DETAIL CALL FOR
 THE DRAIN TO DISCHARGE IN THE GARAGE BUT THE HEATER IS
 NOT IN THE GARAGE. IT MAY DISCHARGE OUTSIDE THROUGH A
 DRAIN LINE PLEASE CORRECT, FBC R 2804.6.1. THE PAN
 DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE OVER A
 SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR SHALL
 EXTEND TO THE EXTERIOR OF THE BUILDING AND TERMINATE
 NOT LESS THAN 6 INCHES FBC R 2801.6.2
 4. SECOND REQUEST, WASHING MACHINE BOX SHALL BE ABLE TO
 BE SHUT OFF WITHOUT MOVING UNIT, PLEASE PROVIDE VALVES
 A LOCATION THAT CAN BE REACHED FBC R 2903.9.3 FIXTURE
 VALVES AND ACCESS. FIXTURE VALVES AND ACCESS.
 ACCESSIBLE, SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL
 OF AN ACCESS PANEL OR SIMILAR REMOVABLE OBSTRUCTION.
 5. THE SECOND REQUEST, ON P-1, HAS A NOTE THAT REFERS
 TO MIAMI-DADE CODE SECTION 8-31 MAXIMUM FLOW RATE WHICH
 IS NOT A ENFORCE SECTION BY THIS MUNICIPALITY, PLEASE
 DELETE AMENDED CONSTRUCTION DOCUMENTS FBC WPB A 107.4
 6. THE SECOND REQUEST, WATER HEATER E.F AT 0.91 NEW
 CODE REQUIRES .095 AS PER NECA APRIL 15, 2015
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-30 Cont ID  
Sent By lcrespo Date 2018-03-30 Time 14:00 Rev Time 0.00
Received By lcrespo Date 2018-03-30 Time 14:00 Sent To  
Notes
2018-03-30 14:01:2703/29/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLUMBING RISER DIAGRAM REQUIRED WPB AMENDMENTS TO
 THE FBC SEC. 107.3.5.3 (11) RESIDENTIAL PLUMBING
 2. HOT WATER HEATER RELIEF NEED TO DISCHARGE THROUGH AN
 AIR GAP LOCATED IN THE SAME ROOM AS THE WATER HEATER.
 FBC R 2804.6.1
 3. THE PAN DRAIN SHALL EXTEND FULL-SIZE AND TERMINATE
 OVER A SUITABLY LOCATED INDIRECT WASTE RECEPTOR OR
 SHALL EXTEND TO THE EXTERIOR OF THE BUILDING AND
 TERMINATE NOT LESS THAN 6 INCHES FBC R 2801.6.2
 4. WASHING MACHINE BOX SHALL BE ABLE TO BE SHUT OFF
 WITHOUT MOVING UNIT, PLEASE PROVIDE VALVES A LOCATION
 THAT CAN BE REACH FBC R 2903.9.3 FIXTURE VALVES AND
 ACCESS.
 5. ON P-1 HAS A NOTE THAT REFERS TO MIAMI-DADE CODE
 SECTION 8-31 MAXIMUM FLOW RATE WHICH IS NOT A ENFORCE
 SECTION BY THIS MUNICIPALITY, PLEASE DELETE AMENDED
 CONSTRUCTION DOCUMENTS FBC WPB A 107.4
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 [email protected]
 561-805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 11:22 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 11:22 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2018-08-23 Cont ID  
Sent By dbattles Date 2018-08-23 Time 13:40 Rev Time 0.00
Received By dbattles Date 2018-08-23 Time 13:40 Sent To  
Notes
2018-08-23 13:41:34SEE BUILDING COMMENTS FOR ROOFING PRODUCT APPROVALS
 NEEDED, OR REQUEST TO DEFER.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-04-04 Cont ID  
Sent By jgomez Date 2018-04-04 Time 15:39 Rev Time 0.00
Received By jgomez Date 2018-04-04 Time 15:39 Sent To  
Notes
2018-04-04 15:39:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 A) METAL ROOF.
  
 B) BEDROOM #1 FLAT ROOF COATING SHOWING COMPLIANCE WITH
 SEC. R905.15 FBC-RESIDENTIAL.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2019-01-22 Cont ID  
Sent By dbattles Date 2019-01-22 Time 15:35 Rev Time 0.00
Received By dbattles Date 2019-01-22 Time 15:35 Sent To  
Notes
2019-01-22 15:35:20RESIDENT INSPECTOR
 GUSTAVO GARRIDO
 407-485-4158

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By dbattles Date 2018-11-01 Time 13:46 Rev Time 0.00
Received By dbattles Date 2018-11-01 Time 13:46 Sent To  
Notes
2018-11-01 13:49:02FORM WAS SENT TO '[email protected]' ON 10/31/18
 THEY ARE GOING TO SEND FOR THREE PERMITS
 18030768, 18030770 AND 18030765

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2020-01-13 Cont ID  
Sent By rbrown Date 2020-01-13 Time 19:01 Rev Time 0.00
Received By rbrown Date 2020-01-13 Time 19:01 Sent To  
Notes
2020-01-13 19:01:25PERMIT FEES WERE PAID ON 9/23/19. ALSO, RECEIVED LETTER
 REQUESTING EXTENSION OF THE PERMIT. PERMIT APPLICATION
 EXTENDED TO 4/13/20. RB

Review Stop Z ZONING
Rev No 4 Status P Date 2019-02-05 Cont ID  
Sent By elevesqu Date 2019-02-05 Time 15:40 Rev Time 0.00
Received By elevesqu Date 2019-02-05 Time 15:40 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2018-11-08 Cont ID  
Sent By elevesqu Date 2018-11-08 Time 12:13 Rev Time 0.00
Received By elevesqu Date 2018-11-08 Time 12:13 Sent To HIST
Notes
2018-11-06 15:33:07PLEASE SEE NEW COMMENTS BASED ON DOWNTOWN MASTER PLAN
 AREA CODE REQUIREMENTS:
  
  
 1. PLEASE SUBMIT A SURVEY OF THE PROPERTY.
 2. PLEASE PROVIDE A SITE PLAN IDENTIFYING THE LOCATION
 OF THE ADJACENT STRUCTURE IN ORDER TO DETERMINE THE
 REQUIRED CONTEXTUAL SETBACK.
 3. PLEASE CLARIFY THE DIFFERENCE BETWEEN GROSS SQUARE
 FOOTAGE AND NET SQUARE FOOTAGE.
 4. IF THE LOT IS MORE THAN 7,500SF THE CUMULATIVE SIDE
 SETBACK IS 20 FEET.
 5. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH FLOOR AREA RATIO ACCORDING WITH THE PROPERTY SIZE
 9SECTION 94-84 (4) AND (5).
 6. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT IN
 COMPLIANCE WITH THE REQUIRED LANDSCAPE PROVISIONS FOR
 SINGLE FAMILY HOUSES (SEC94-442(2)).
 7. PLEASE INDICATE THE LOCATION OF THE REQUIRED PARKING
 FOR THE RESIDENTIAL UNIT. IF THE PARKING IS PROVIDED ON
 THE STREET, PLEASE INDICATE THE LOCATION OF THE
 ON-STREET PARKING ON THE SITE PLAN.
 8. PLEASE INDICATE ANY TREES ON SITE OR PROPOSED FOR
 REMOVAL/RELOCATION. - LANDSCAPE PERMIT.
 9. MECHANICAL EQUIPMENT SHALL BE SCREENED WITH A HEDGE.
  
 FOR ADDITIONAL INFORMATION PLEASE CONTACT
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-08-21 Cont ID  
Sent By destabro Date 2018-08-21 Time 09:53 Rev Time 0.00
Received By destabro Date 2018-08-21 Time 09:53 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-03-29 Cont ID  
Sent By AA Date 2018-03-29 Time 08:40 Rev Time 0.00
Received By destabro Date 2018-03-29 Time 08:40 Sent To B
Notes
2018-03-29 08:41:123/28/2018 - HPB CASE NO. 17-78, RECEIVED HPB APPROVAL
 FOR INFILL CONSTRUCTION IN DECEMBER OF 2017. APPLICANT
 HAS MET THE FOLLOWING CONDITIONS OF APPROVAL:
 1.) REVISE FRONT SETBACK TO FALL BETWEEN THE RANGE OF
 16? TO 25?.
 2.) ADJUST THE MASSING ON THE REAR OF THE STRUCTURE TO
 COMPLEMENT THE FRONT FA?ADE. THE BOXY PROJECTIONS AT
 THE SIDE ELEVATIONS SHOULD BE CAPPED WITH A HIP OR
 GABLE ROOF FOR ARCHITECTURALLY CONTINUITY.
 3.) APPLICANT SHALL USE SMOOTH STUCCO CLADDING FOR ALL
 PROPOSED MODELS. IF HARDIBOARD IS TO BE USED, IT SHALL
 COVER THE ENTIRE BUILDING ENVELOPE AND BE SMOOTH IN
 TEXTURE.
 4.) ROOFING MATERIAL SHALL BE CONSISTENT. APPLICANT
 SHOWS A STANDING SEAM METAL TYPE OF ROOFING ON THE
 RENDERINGS, BUT DESCRIBES ELASTOMERIC PAINT BEING
 APPLIED TO THE CONCRETE SURFACE IN THE PLANS.
 5.) ALL WINDOWS SHOULD BE CLEAR GLASS, NOT TINTED, PER
 THE DESIGN GUIDELINES OF THE HISTORIC DISTRICT. ON THE
 RIGHT AND LEFT ELEVATIONS, A WIDER 6/1-LIGHT WINDOW IS
 PRESENT AND SHOULD BE RECONFIGURED TO CREATE A PAIRED
 4/1-LIGHT WINDOWS FOR CONTINUITY OF DESIGN. THE FIXED
 GLASS WINDOW ON THE FRONT ELEVATION FOR THE BATHROOM
 SPACE SHOULD BE ADJUSTED TO A 4/1-LIGHT.
 DLE