Plan Review Details - Permit 18030687
Plan Review Stops For Permit 18030687
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By tklarge Date 2018-03-23 Time 08:29 Rev Time 0.00
Received By tklarge Date 2018-03-23 Time 08:29 Sent To  
Notes
2018-03-23 08:30:25ENGINEERING REVIEW IS NOT REQUIRED ON THIS PERMIT. TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-04-05 Cont ID  
Sent By tklarge Date 2018-04-05 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-04-03 Time 09:39 Sent To  
Notes
2018-04-04 09:39:46RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-03-23 Cont ID  
Sent By tklarge Date 2018-03-23 Time 08:30 Rev Time 0.00
Received By tklarge Date 2018-03-15 Time 11:02 Sent To  
Notes
2018-03-22 15:33:093/22 ON TLARGE DESK
  
2018-03-16 11:03:39ROUTED TO PLUMB<5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-04-05 Cont ID  
Sent By tklarge Date 2018-04-05 Time 06:24 Rev Time 0.00
Received By tklarge Date 2018-04-05 Time 05:49 Sent To I
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-03-23 Cont ID  
Sent By tklarge Date 2018-03-23 Time 08:29 Rev Time 0.00
Received By tklarge Date 2018-03-23 Time 06:37 Sent To I
Notes
2018-03-23 08:29:361) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP IN
 ACCORDANCE WITH THE PLUMBING DRAINAGE INSTITUTE
 STANDARD PDI-G101.
 2) THE WORK INVOICE INDICATES A 30 POUND GREASE
 INTERCEPTOR IS TO BE INSTALLED BUT THE SUBMITTED
 SPECIFICATIONS ARE FOR A 40 POUND GREASE INTERCEPTOR.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  