| 2018-03-19 15:58:20 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO PLAN DRAWING SHEETS SUBMITTED WITH THIS |
| | PERMIT. |
| | |
| | PER NFPA 1 |
| | |
| | 1.14 PLAN REVIEW. |
| | |
| | 1.14.1 WHERE REQUIRED BY THE AHJ FOR NEW CONSTRUCTION, |
| | MODIFICATION, OR REHABILITATION, CONSTRUCTION DOCUMENTS |
| | AND SHOP DRAWINGS SHALL BE SUBMITTED, REVIEWED, AND |
| | APPROVED PRIOR TO THE START OF SUCH WORK AS PROVIDED IN |
| | SECTION 1.14. |
| | |
| | 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE |
| | THAT THE FOLLOWING CONDITIONS ARE MET: |
| | (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE |
| | PROTECTION REQUIREMENTS. |
| | (2) THE SHOP DRAWINGS ARE CORRECT AND IN COMPLIANCE |
| | WITH THE APPLICABLE CODES AND STANDARDS. |
| | (3) THE CONTRACTOR MAINTAINS AN APPROVED SET OF |
| | CONSTRUCTION DOCUMENTS ON SITE. |
| | |
| | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION |
| | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND |
| | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE |
| | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD |
| | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. |
| | |
| | PER NFPA 72 |
| | |
| | 7.1 APPLICATION. (SIG-FUN) |
| | 7.1.1 THE DOCUMENTATION OF THE DESIGN, ACCEPTANCE, AND |
| | COMPLETION OF NEW SYSTEMS REQUIRED UNDER THIS CODE |
| | SHALL |
| | COMPLY WITH THE MINIMUM REQUIREMENTS OF THIS CHAPTER. |
| | |
| | PLEASE SUBMIT A PLAN SHEET SHOWING ALL PROPOSED OR |
| | EXISTING LOCATIONS. |
| | |
| | |
| | |
| | |
| | 2) FOR ANY NEW EQUIPMENT A CIRCUIT DIAGRAM SHALL BE |
| | SUBMITTED INCLUDING RECALCULATED VOLTAGE. |
| | |
| | PER NFPA 72 |
| | |
| | 7.2* MINIMUM REQUIRED DOCUMENTATION. (SIG-FUN) |
| | 7.2.1 WHERE DOCUMENTATION IS REQUIRED BY THE ENFORCING |
| | AUTHORITY, |
| | THE FOLLOWING LIST SHALL REPRESENT THE MINIMUM |
| | DOCUMENTATION |
| | REQUIRED FOR ALL FIRE ALARM AND EMERGENCY |
| | COMMUNICATIONS |
| | SYSTEMS, INCLUDING NEW SYSTEMS AND ADDITIONS OR |
| | ALTERATIONS TO EXISTING SYSTEMS: |
| | (1)*WRITTEN NARRATIVE PROVIDING INTENT AND SYSTEM |
| | DESCRIPTION |
| | (2) RISER DIAGRAM |
| | (3) FLOOR PLAN LAYOUT SHOWING LOCATION OF ALL DEVICES |
| | AND |
| | CONTROL EQUIPMENT |
| | (4) SEQUENCE OF OPERATION IN EITHER AN INPUT/OUTPUT |
| | MATRIX |
| | OR NARRATIVE FORM |
| | (5) EQUIPMENT TECHNICAL DATA SHEETS |
| | (6) MANUFACTURERS PUBLISHED INSTRUCTIONS, INCLUDING |
| | OPERATION |
| | AND MAINTENANCE INSTRUCTIONS |
| | (7) BATTERY CALCULATIONS (WHERE BATTERIES ARE PROVIDED) |
| | (8) VOLTAGE DROP CALCULATIONS FOR NOTIFICATION |
| | APPLIANCE CIRCUITS |
| | (9)*COMPLETED RECORD OF INSPECTION AND TESTING IN |
| | ACCORDANCE |
| | WITH 7.6.6 AND 7.8.2 |
| | (10) COMPLETED RECORD OF COMPLETION IN ACCORDANCE WITH |
| | 7.5.6 AND 7.8.2 |
| | (11) COPY OF SITE-SPECIFIC SOFTWARE, WHERE APPLICABLE |
| | (12) RECORD (AS-BUILT) DRAWINGS |
| | (13) PERIODIC INSPECTION, TESTING, AND MAINTENANCE |
| | DOCUMENTATION |
| | IN ACCORDANCE WITH SECTION 7.6 |
| | (14) RECORDS, RECORD RETENTION, AND RECORD MAINTENANCE |
| | IN |
| | ACCORDANCE WITH SECTION 7.7 |
| | 7.2.2* THE PERSON RESPONSIBLE FOR SYSTEM DESIGN |
| | (LAYOUT) SHALL |
| | BE IDENTIFIED ON THE SYSTEM DESIGN DOCUMENTS. |
| | 7.2.3 ALL FIRE ALARM DRAWINGS SHALL USE SYMBOLS |
| | DESCRIBED IN |
| | NFPA 170, STANDARD FOR FIRE SAFETY AND EMERGENCY |
| | SYMBOLS, OR |
| | OTHER SYMBOLS ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION. |
| | 7.3 DESIGN (LAYOUT) DOCUMENTATION. |
| | 7.3.1* THE REQUIREMENTS OF SECTION 7.3 SHALL APPLY ONLY |
| | WHERE |
| | REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS; |
| | BY |
| | OTHER PARTS OF THIS CODE; OR BY PROJECT SPECIFICATIONS |
| | OR DRAWINGS. |
| | (SIG-FUN) |
| | |
| | PLEASE PROVIDE. |
| | |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |