| 2018-03-15 07:16:34 | 03/15/2018 **1ST GAS REVIEW DENIED ** |
| | |
| | 1. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN AT THE METER PER 2017 FBC FUEL GAS RES. |
| | SEC. G2413.2. |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC FUEL GAS RES. SEC. G2407.1 AND G2439.4 (CLOTHES |
| | DRYERS AND COOK-TOP). WHERE COMBUSTION AIR IS PROVIDED |
| | BY THE BUILDING?S MECHANICAL VENTILATION SYSTEM, THE |
| | SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE |
| | IN ADDITION TO THE REQUIRED VENTILATION AIR. THE |
| | MANUFACTURER'S SPECIFICATIONS SHALL NOTE THE CFM'S THAT |
| | ARE BEING EXHAUSTED BY THE DRYER. |
| | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| | TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| | DETAILS OF THE GAS VENT(S) FOR DRYER PER 2017 FBC FUEL |
| | GAS RES. SECS. G2426 THUR G2429.1. |
| | 4. SUBMIT MANUFACTURER?S SPECIFICATION |
| | SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS RES. SEC. |
| | G2408.1. (POOL HEATER, COOK-TOP, DRYER, GENERATOR AND |
| | FIRE PIT) GAS APPLIANCES SHALL BE LISTED AND LABELED. |
| | THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES/EQUIPMENT SHALL BE ONSIDE AT THE TIME OF |
| | INSPECTION. 2017 FBC FUEL GAS RES. SEC. G2413.2 AND |
| | G2404.3. |
| | 5. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| | DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| | OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| | ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| | SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3. |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| | 7. INDICATE ON BOTH GAS DRAWINGS HOW THE PIPING THROUGH |
| | THE EXTERIOR WILL BE PROTECTED. WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1. |
| | 8. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | 9. SHOW SEDIMENT TRAPS ON ISOMETRIC DOWNSTREAM OF THE |
| | APPLIANCE SHUTOFF VALVE AS CLOSE TO THE INLET OF THE |
| | APPLIANCE AS PRACTICAL 2017 FBC FUEL GAS RES. SEC. |
| | G2419.4 (408.4) SEDIMENT TRAP. |
| | 10. THE MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR |
| | SHALL BE ONSIDE FOR FINAL GAS INSPECTION. THE GENERATOR |
| | SHALL BE LISTED AND APPROVED. NFPA 58 SEC. 5.20.1. THE |
| | GENERATOR SHALL MEET THE REQUIREMENTS OF UL 2200. |
| | 11. NFPA 37, SECTION 4.1.4, ENGINES LOCATED OUTDOORS. |
| | ENGINES, AND THEIR WEATHERPROOF HOUSINGS, IF PROVIDED, |
| | THAT ARE INSTALLED OUTDOORS SHALL BE LOCATED AT LEAST 5 |
| | FT. FROM OPENINGS IN WALLS AND AT LEAST 5 FT. FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| | SEPARATION SHALL NOT BE REQUIRED WHERE EITHER OF THE |
| | FOLLOWING CONDITIONS EXIST; |
| | |
| | (1) ALL WALLS OF THE STRUCTURE THAT ARE CLOSER THAN 5 |
| | FT. FROM THE ENGINE ENCLOSURE HAVE A FIRE RESISTANCE |
| | RATING OF AT LEAST 1 HOUR. |
| | (2)*THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NONCOMBUSTIBLE MATERIALS AND IT HAS BEEN DEMONSTRATED |
| | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |